Littelfuse
201-100-DPDT
201-100-DPDT - 201-XXX-DPDT Series
- Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
- Sconti sulla rivendita fino al 40%!
Invia una richiesta di prezzo
1
Metodi di pagamento:
Additional Information
- Part Number
- 201-100-DPDT
Specifications
- Input Voltage (V)
- 95 to 120VAC
- Maximum Input Power
- 5W
- Input AC Line Frequency (Hz)
- 50/60Hz
- Output Form
- DPDT
- Output Load Rating (VA)
- Pilot Duty: 480VA @ 240VAC; General Purpose: 10A @ 240VAC
- Restart Delay Range
- After a Fault or Complete Power Loss: 2s
- Trip Delay Range
- Low Voltage: 4s; Unbalance Phasing Faults: 2s
- Trip Point Accuracy (%)
- ±1%
- Undervoltage Trip Voltage
- 90%
- Undervoltage Reset Voltage (%)
- 93%
- Voltage Unbalance Trip Point (%)
- 6%
- Voltage Unbalance Reset (%)
- 4.50%
- Termination Type
- Torque: 12 in-lbs; Wire: Stranded or solid 10-22AWG
- Mounting Method
- DIN rail or surface mount (plug-in to OT11-PC socket)
- Operating Temperature
- -40° to 70°C (-40° to 158°F)
- Humidity
- 95% non-condensing per IEC 68-2-3
- Dimensions
- 1.75 in H x 2.38 in W x 4.13 in D (44.5 x 60.3 x 104.8 mm)
- Weight (lbs/g)
- 0.65 lb. (10.4 oz. 294.8 g)
Documenti
Data Sheet
ScaricareAltre categorie
AttuatoriBlocchiCavi, tubi e manichetteCompressoriControlloGiunzioni e raccordiCilindri e PistoniElettronicaFiltriHVACPC industriali e HMIsIlluminazioneTecnica lineareMotoriAlimentatoreTrasmissione di potenzaPompe e ValvoleEnergia rinnovabileRoboticaGuarnizioni, Anelli e ConnettoriSensori e dispositivi di misuraStrumenti e AccessoriCNCAltro