Mersen
USFMBB5
1 / 1
Descrizione
Mersen UltraSafe Fuse Modules (USFM) have a unique, compact design suited for use with 45mm wide IEC contactors. These modules also offer other features not found on other class CC and midget UltraSafe fuseholders such as an auxiliary contact option. When the auxiliary is wired to an adjacent contactor the load is dropped out by the contactor immediately once the fuse extractor handle is opened. Additionally, the fuse module features padlock capabilities, compact bus bars for line side terminations, and tool free removal from DIN rail. Yet the fuse modules still incorporate well known UltraSafe features such as IP20 protection, easy operating fuse extraction handles and an open fuse visual indication option.- Part Number
- USFMBB5
- UPC
- 782001382155
- Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
- Sconti sulla rivendita fino al 40%!
Invia una richiesta di prezzo
1
Metodi di pagamento:
Product Details
- SCCR
- 200, 100, kA
- Ampere Range
- 0-30 A
- Standards
- UL Listed to standard 4248-4, File E52283 CSA Certified C22.2, Class 6225, File 32169 UL Listed to standard 508, File E336456 UL Recognized Component to standard 4248-1, File E319605 UL Recognized Component to standard 4248-14, File E52283 CSA Certified C22.2, Class 6225, File 32169 IEC Compliant to 60269-2-1, 60947-3
- ROHS Compliant
- Consult Technical Services
- UL Certification
- E52283 IZLT.E52283E52283 IZLT2.E52283
- CSA Certification
- 6225-01 032169_0_0006225-01 3211-37
- Body Material
- Latamid
- CE conformity
- Consult Technical Services
- Class
- Midget Class CC Accessory
- DC Voltage Range
- 240 - 600 VDC
- Connection Terminal Type
- Pressure Plate
- Materials Contact
- Tin-plated Copper Copper
- Wiring Range
- #10 to 16 AWG, #10 to 6 AWG
- Lead Free
- Consult Technical Services
- Enclosure
- IP20
- Applications
- Primarily for replacement of circuit breakers in motor circuits to achieve higher SCCR Circuits up to 600V for motors, control, transformers, etc…Applications requiring lock-out / tag-out procedures
- AC Voltage Range
- 240 - 600 VAC
- Number of Poles
- 3
- Mounting
- DIN-rail
Altre categorie
AttuatoriBlocchiCavi, tubi e manichetteCompressoriControlloGiunzioni e raccordiCilindri e PistoniElettronicaFiltriHVACPC industriali e HMIsIlluminazioneTecnica lineareMotoriAlimentatoreTrasmissione di potenzaPompe e ValvoleEnergia rinnovabileRoboticaGuarnizioni, Anelli e ConnettoriSensori e dispositivi di misuraStrumenti e AccessoriCNCAltro