Phoenix Contact
2320542
DC/DC converter, protective coating - QUINT-PS/24DC/24DC/ 5/CO - 2320542
- Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
- Sconti sulla rivendita fino al 40%!
Invia una richiesta di prezzo
1
Metodi di pagamento:
Un totale di 1 Part In-Stock da 6 Distributors
Condizioni del prodotto:
Offerta con tempi di consegna del produttore
Spedizione in:Su richiesta
Miglior prezzo:
Invia una richiesta di prezzo
Additional Information
- Part Number
- 2320542
- UPC
- 4046356765930
- Country of Origin
- CN
- ETIM
- Group Code : EG000017
- Group Description : Low-voltage Industrial Components
- Class Description : Power supply transformer
- Class Code : EC002046
- Version : 7
Input data
- Nominal input voltage range
- 24 V DC
- Input voltage range
- 18 V DC - 32 V DC
- Extended input voltage range in operation
- 14 V DC - 18 V DC (Derating)
- Current consumption
- 7 A (24 V, IBOOST)
- Inrush current
- typ. 15 A
- Mains buffering time
- typ. 10 ms (24 V DC)
- Input fuse
- 15 A (device protection)
- Recommended breaker for input protection
- 10 A - 16 A (Characteristics B, C, D, K)
- Type of protection
- Transient surge protection
- Protective circuit/component
- Varistor
Standards
- EMC requirements for noise immunity
- EN 61000-6-1
- EMC requirements for noise immunity
- EN 61000-6-2
- EMC requirements for noise emission
- EN 61000-6-3
- EMC requirements for noise emission
- EN 61000-6-4
- Standard - Electrical safety
- EN 60950-1/VDE 0805 (SELV)
- Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
- EN 50178/VDE 0160 (PELV)
- Standard – Safety extra-low voltage
- EN 60950-1 (SELV)
- Standard – Safety extra-low voltage
- EN 60204-1 (PELV)
- Standard - Safe isolation
- DIN VDE 0100-410
- Rail applications
- EN 50121-4
- Rail applications
- EN 50155
Dimensions
- Width
- 32 mm
- Height
- 130 mm
- Depth
- 125 mm
- Width with alternative assembly
- 122 mm
- Height with alternative assembly
- 130 mm
- Depth with alternative assembly
- 35 mm
- Installation distance right/left
- 0 mm / 0 mm (≤ 70 °C)
- Installation distance left/right (active)
- 15 mm / 15 mm (≤ 70 °C)
- Installation distance top/bottom
- 50 mm / 50 mm (≤ 70 °C)
- Installation distance top/bottom (active)
- 50 mm / 50 mm (≤ 70 °C)
Output data
- Nominal output voltage
- 24 V DC ±1 %
- Setting range of the output voltage (USet)
- 18 V DC - 29.5 V DC (> 24 V DC, constant capacity restricted)
- Nominal output current (IN)
- 5 A (-25 °C - 60 °C)
- POWER BOOST (IBoost)
- 6.25 A (-25°C - 40°C permanent, UOUT = 24 V DC )
- Selective Fuse Breaking (ISFB)
- 30 A (12 ms)
- Derating
- 60 °C - 70 °C (2.5%/K)
- Connection in parallel
- Yes, for redundancy and increased capacity
- Connection in series
- yes
- Feedback voltage resistance
- 35 V DC
- Protection against overvoltage at the output (OVP)
- < 35 V DC
- Max. capacitive load
- unlimited
- Active current limitation
- Approximately 7.2 A
- Control deviation
- < 1 % (change in load, static 10 % - 90 %)
- Control deviation
- < 2 % (change in load, dynamic 10 % - 90 %)
- Control deviation
- < 0.1 % (change in input voltage ±10 %)
- Residual ripple
- < 20 mVPP
- Peak switching voltages nominal load
- < 10 mVPP (20 MHz)
- Maximum power dissipation in no-load condition
- 2.4 W
- Power loss nominal load max.
- 11.4 W
Connection data, input
- Connection method
- Pluggable screw connection
- Conductor cross section solid min.
- 0.2 mm²
- Conductor cross section solid max.
- 2.5 mm²
- Conductor cross section flexible min.
- 0.2 mm²
- Conductor cross section flexible max.
- 2.5 mm²
- Conductor cross section AWG min.
- 24
- Conductor cross section AWG max.
- 12
- Stripping length
- 8 mm
- Screw thread
- M3
Connection data, output
- Connection method
- Pluggable screw connection
- Conductor cross section solid min.
- 0.2 mm²
- Conductor cross section solid max.
- 2.5 mm²
- Conductor cross section flexible min.
- 0.2 mm²
- Conductor cross section flexible max.
- 2.5 mm²
- Conductor cross section AWG min.
- 24
- Conductor cross section AWG max.
- 12
- Stripping length
- 7 mm
- Screw thread
- M3
Ambient conditions
- Degree of protection
- IP20
- Ambient temperature (operation)
- -25 °C - 70 °C (> 60 °C derating, 2.5 %/K, startup at -40°C type-tested)
- Ambient temperature (start-up type tested)
- -40 °C
- Ambient temperature (storage/transport)
- -40 °C - 85 °C
- Max. permissible relative humidity (operation)
- 100 % (at 25 °C, non-condensing)
- Climatic class
- 3K3 (in acc. with EN 60721)
- Degree of pollution
- 2
Connection data for signaling
- Conductor cross section solid min.
- 0.2 mm²
- Conductor cross section solid max.
- 2.5 mm²
- Conductor cross section flexible min.
- 0.2 mm²
- Conductor cross section flexible max.
- 2.5 mm²
- Conductor cross section AWG min.
- 24
- Conductor cross section AWG max.
- 12
- Screw thread
- M3
Conformance/approvals
- UL approvals
- UL/C-UL listed UL 508
- UL approvals
- UL/C-UL Recognized UL 60950-1
- UL approvals
- UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
- Shipbuilding approval
- DNV GL (EMC B)
Environmental Product Compliance
- REACh SVHC
- Lead 7439-92-1
- China RoHS
- Environmentally Friendly Use Period = 25;
- China RoHS
- For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'
EMC data
- Electromagnetic compatibility
- Conformance with EMC Directive 2014/30/EU
- Electrostatic discharge
- EN 61000-4-2
- Contact discharge
- 8 kV (Test Level 4)
- Discharge in air
- 15 kV (Test Level 4)
- Electromagnetic HF field
- EN 61000-4-3
- Frequency range
- 80 MHz - 1 GHz
- Frequency range
- 1 GHz - 2 GHz
- Frequency range
- 2 GHz - 3 GHz
- Test field strength
- 10 V/m
- Comments
- Criterion A
- Fast transients (burst)
- EN 61000-4-4
- Input
- 2 kV (Test Level 3 - asymmetrical)
- Output
- 2 kV (Test Level 3 - asymmetrical)
- Signal
- 2 kV (Test Level 4 - asymmetrical)
- Surge voltage load (surge)
- EN 61000-4-5
- Input
- 1 kV (Test Level 2 - symmetrical)
- Output
- 1 kV (Test Level 2 - symmetrical)
- Signal
- 1 kV (Test Level 2 - asymmetrical)
- I/O/S
- asymmetrical
- Frequency range
- 0.15 MHz - 80 MHz
- Voltage
- 10 V (Test Level 3)
- Criterion A
- Normal operating behavior within the specified limits.
- Criterion B
- Temporary impairment to operational behavior that is corrected by the device itself.