Head-mounted transducer - MCR-FL-HT-T-I - 2864529
2864529
  • Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
  • Sconti sulla rivendita fino al 40%!
Registrati
Invia una richiesta di prezzo
1
Metodi di pagamento:
Offerta con tempi di consegna del produttore
Spedizione in:1 - 2 Molti giorni lavorativi
Miglior prezzo:
Invia una richiesta di prezzo

Additional Information

Part Number
2864529
UPC
4017918893224
Country of Origin
DE
ETIM
Group Code : EG000026
Group Description : Sensors
Class Description : Temperature transmitter
Class Code : EC002919
Version : 7

Input data

Configurable/programmable
Yes, programmable
Sensor types (RTD) that can be used
Pt, Ni (100, 500, 1000); minimum measurement range 10 K
Sensor types that can be used (TC)
B, C, D, E, J, K, L, N, R, S, T, U; minimum measurement range 50 K/500 K
Linear resistance measuring range
Resistance-type sensor from 10 Ω to 400 Ω and from 10 Ω to 2000 Ω; minimum measurement range 10 Ω/100 Ω
Connection technology
2, 3, 4-wire

Connection data

Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² - 1.75 mm²
Conductor cross section flexible
0.2 mm² - 1.75 mm²
Conductor cross section AWG
24 - 15

Output data

Output name
Current output
Number of outputs
1
Configurable/programmable
Yes
Current output signal
4 mA - 20 mA
Current output signal
20 mA - 4 mA
Output current with wire break
≤ 3.6 mA or ≥ 21 mA (adjustable)
Output current with short-circuit
≤ 3.6 mA or ≥ 21 mA (adjustable, not for thermocouples)
Output current range with overrange/underrange
≤ 20.5 mA / ≥ 3.8 mA (linear increase/decrease)
Load/output load current output
max (Vsupply - 8 V) / 0.025 A (current output)

Ambient conditions

Ambient temperature (operation)
-40 °C - 85 °C
Degree of protection
IP00
Degree of protection
IP66 (Installed in the connection head)
Noise immunity
EN 61326-1 (IEC 61326) and NAMUR NE 21

Environmental Product Compliance

China RoHS
Environmentally friendly use period: unlimited = EFUP-e
China RoHS
No hazardous substances above threshold values

Standards and Regulations

Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61326-1 (IEC 61326) and NAMUR NE 21
Noise immunity
EN 61326-1 (IEC 61326) and NAMUR NE 21
Connection in acc. with standard
CUL
Conformance
CE-compliant
UL, USA/Canada
Class I, Div. 2, Groups A, B, C, D

Power supply

Designation
Loop-powered
Supply voltage range
8 V DC - 35 V DC
Max. current consumption
< 3.5 mA