Phoenix Contact
2864794
Signal duplicator 2864794
- Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
- Sconti sulla rivendita fino al 40%!
$309.00
1
Metodi di pagamento:
Un totale di 8 Parts In-Stock da 4 Distributors
Condizioni del prodotto:
Additional Information
- Part Number
- 2864794
- UPC
- 4017918974978
- Country of Origin
- DE
Input data
- Number of inputs
- 1
- Configurable/programmable
- Yes, preconfigured
- Voltage input signal
- 0 V - 10 V
- Voltage input signal
- 1 V - 5 V
- Current input signal
- 0 mA - 20 mA
- Current input signal
- 4 mA - 20 mA
- Max. input voltage
- 30 V
- Max. input current
- 50 mA
- Input resistance of voltage input
- approx. 100 kΩ
- Input resistance current input
- approx. 50 Ω
Note
- Utilization restriction
- EMC: class A product, see manufacturer's declaration in the download area
Dimensions
- Width
- 6.2 mm
- Height
- 93.1 mm
- Depth
- 102.5 mm
Connection data
- Connection method
- Screw connection
- Conductor cross section solid min.
- 0.2 mm²
- Conductor cross section solid max.
- 2.5 mm²
- Conductor cross section AWG min.
- 26
- Conductor cross section AWG max.
- 12
- Conductor cross section flexible min.
- 0.2 mm²
- Conductor cross section flexible max.
- 2.5 mm²
- Stripping length
- 12 mm
- Screw thread
- M3
Output data
- Number of outputs
- 2
- Configurable/programmable
- Yes, preconfigured
- Current output signal
- 2x 0 mA - 20 mA
- Current output signal
- 2x 4 mA - 20 mA
- Max. output current
- approx. 22 mA
- Load/output load current output
- ≤ 250 Ω (at 20 mA)
- Ripple
- < 20 mVPP (at 250 Ω)
Ambient conditions
- Ambient temperature (operation)
- -20 °C - 60 °C
- Ambient temperature (storage/transport)
- -40 °C - 85 °C
Environmental Product Compliance
- China RoHS
- Environmentally Friendly Use Period = 50
- China RoHS
- For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
EMC data
- Designation
- Electromagnetic RF field
- Standards/regulations
- EN 61000-4-3
- Typical deviation from the measuring range final value
- 5 %
- Designation
- Fast transients (burst)
- Standards/regulations
- EN 61000-4-4
- Typical deviation from the measuring range final value
- 5 %
- Designation
- Conducted interferences
- Standards/regulations
- EN 61000-4-6
- Typical deviation from the measuring range final value
- 5 %
Standards and Regulations
- Electromagnetic compatibility
- Conformance with EMC directive
- Noise emission
- EN 61000-6-4
- Connection in acc. with standard
- CUL
- Standards/regulations
- EN 61000-4-2
- Designation
- Electromagnetic RF field
- Standards/regulations
- EN 61000-4-3
- Standards/regulations
- EN 61000-4-4
- Standards/regulations
- EN 61000-4-5
- Designation
- Conducted interferences
- Standards/regulations
- EN 61000-4-6
- Electrical isolation
- Basic insulation according to EN 61010
- Conformance
- CE-compliant
- ATEX
- II 3 G Ex nA IIC T4 Gc X
- UL, USA/Canada
- UL 508 Recognized
- UL, USA/Canada
- Class I, Div. 2, Groups A, B, C, D T5
- GL
- GL EMC 2 D
- Fire protection for rail vehicles (DIN EN 45545-2) R22
- HL 1 - HL 2
- Fire protection for rail vehicles (DIN EN 45545-2) R23
- HL 1 - HL 2
- Fire protection for rail vehicles (DIN EN 45545-2) R24
- HL 1 - HL 2
Power supply
- Nominal supply voltage
- 24 V DC
- Supply voltage range
- 19.2 V DC - 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
- Max. current consumption
- < 30 mA (at 24 V DC incl. load)
- Power consumption
- < 600 mW