Phoenix Contact
2902914
1 / 1
Descrizione
Universal Termination Carrier for redundantly connecting 16 PSR-ETP modules to digital output cards, via two D-SUB connectors, 37-pos. (1:1 connection). Solution for Fire & Gas (F&G) applications- Country of Origin
- DE
- Part Number
- 2902914
- Tariff Code
- 85369010
- EAN
- 4046356703710
- UPC
- 4046356703710
- ETIM
- Group Code : EG000024
- Group Description : PLC's
- Class Description : Interface module
- Class Code : EC002780
- Version : 7
- Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
- Sconti sulla rivendita fino al 40%!
Invia una richiesta di prezzo
1
Metodi di pagamento:
Note
- Utilization restriction
- EMC: class A product, see manufacturer's declaration in the download area
Dimensions
- Width
- 304 mm
- Height
- 170 mm
- Depth
- 160 mm
Connection data 2
- Connection name
- Controller level
- Connection method
- D-SUB pin strip
- Number of connections
- 2
- Number of positions
- 37
Connection data
- Connection name
- Power supply
- Connection method
- Screw connection
- Stripping length
- 7 mm
- Number of connections
- 1
- Number of positions
- 6
- Conductor cross section solid
- 0.14 mm² - 2.5 mm²
- Conductor cross section flexible
- 0.14 mm² - 2.5 mm²
- Conductor cross section AWG
- 24 - 12
Supply
- Designation
- Device supply
- Input voltage range
- 21.1 V DC - 26.4 V DC
- Input current
- ≤ 2 A
- Redundant supply
- yes, decoupled from diodes
- Polarization and surge protection
- Yes
- Output name
- Switching output
- Contact type
- 1 N/C contact (alarm = open)
- Fuse
- 2.5 A on PCB, slow-blow (replaceable)
- Status display
- 2 x red LED (error)
- Status display
- 2x green LEDs (PWR1 and PWR2)
Ambient conditions
- Ambient temperature (operation)
- -20 °C - 60 °C
- Ambient temperature (storage/transport)
- -40 °C - 80 °C
- Maximum altitude
- ≤ 2000 m
- Permissible humidity (operation)
- 5 % - 95 % (non-condensing)
- Degree of protection
- IP00
- Shock
- 15g, according to IEC 60068-2-27
- Vibration (operation)
- 2g, according to IEC 60068-2-6
Environmental Product Compliance
- REACh SVHC
- Lead 7439-92-1
- China RoHS
- Environmentally Friendly Use Period = 50 years
- China RoHS
- For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'
Standards and Regulations
- Designation
- Air clearances and creepage distances
- Standards/regulations
- DIN EN 50178
- Rated insulation voltage
- 50 V
- Rated surge voltage
- 0.5 kV
- Insulation
- Basic insulation
- Shock
- 15g, according to IEC 60068-2-27
- Vibration (operation)
- 2g, according to IEC 60068-2-6
- UL, USA/Canada
- UL 61010 Listed
- UL, USA/Canada
- Class I, Div. 2, Groups A, B, C, D T4
- UL, USA/Canada
- Class I, Zone 2, Group IIC
Modelli CAD
traceparts
Scaricare