Descrizione

Universal Termination Carrier for redundantly connecting 16 PSR-ETP modules to digital output cards, via two D-SUB connectors, 37-pos. (1:1 connection). Solution for Fire & Gas (F&G) applications
Country of Origin
DE
Part Number
2902914
Tariff Code
85369010
EAN
4046356703710
UPC
4046356703710
ETIM
Group Code : EG000024
Group Description : PLC's
Class Description : Interface module
Class Code : EC002780
Version : 7
  • Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
  • Sconti sulla rivendita fino al 40%!
Registrati
Invia una richiesta di prezzo
1
Metodi di pagamento:
Richiedete un preventivo e vi invieremo informazioni su disponibilità e prezzi.

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
304 mm
Height
170 mm
Depth
160 mm

Connection data 2

Connection name
Controller level
Connection method
D-SUB pin strip
Number of connections
2
Number of positions
37

Connection data

Connection name
Power supply
Connection method
Screw connection
Stripping length
7 mm
Number of connections
1
Number of positions
6
Conductor cross section solid
0.14 mm² - 2.5 mm²
Conductor cross section flexible
0.14 mm² - 2.5 mm²
Conductor cross section AWG
24 - 12

Supply

Designation
Device supply
Input voltage range
21.1 V DC - 26.4 V DC
Input current
≤ 2 A
Redundant supply
yes, decoupled from diodes
Polarization and surge protection
Yes
Output name
Switching output
Contact type
1 N/C contact (alarm = open)
Fuse
2.5 A on PCB, slow-blow (replaceable)
Status display
2 x red LED (error)
Status display
2x green LEDs (PWR1 and PWR2)

Ambient conditions

Ambient temperature (operation)
-20 °C - 60 °C
Ambient temperature (storage/transport)
-40 °C - 80 °C
Maximum altitude
≤ 2000 m
Permissible humidity (operation)
5 % - 95 % (non-condensing)
Degree of protection
IP00
Shock
15g, according to IEC 60068-2-27
Vibration (operation)
2g, according to IEC 60068-2-6

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Standards and Regulations

Designation
Air clearances and creepage distances
Standards/regulations
DIN EN 50178
Rated insulation voltage
50 V
Rated surge voltage
0.5 kV
Insulation
Basic insulation
Shock
15g, according to IEC 60068-2-27
Vibration (operation)
2g, according to IEC 60068-2-6
UL, USA/Canada
UL 61010 Listed
UL, USA/Canada
Class I, Div. 2, Groups A, B, C, D T4
UL, USA/Canada
Class I, Zone 2, Group IIC