Pluggable device protection, according to type 3/class III, for 1-phase power supply networks with separate N and PE (3-conductor system: L1, N, PE), with integrated surge-proof fuse and remote indication contact. Also suitable for DC applications.
Country of Origin
DE
Part Number
2905228
Tariff Code
85363030
EAN
4046356939690
UPC
4046356939690
ETIM
Group Code : EG000021
Group Description : Earthing, lightning and surge protection
Class Description : Surge protection device for terminal equipment
Class Code : EC000942
Version : 7
$150.00
net
1
Metodi di pagamento:
Migliore offerta da:
USFornitore Automa.Net di fiducia
Disponibilità:
1 pz.
Disponibile
Aggiornato il: 07-11-2024
Garanzia:
12 mesi
Consegna stimata:
Su richiesta
Condizione:
Nuove eccedenze
Nuove eccedenze - Un articolo nuovo, inutilizzato e non danneggiato senza garanzia del produttore. L'articolo può arrivare senza confezione originale o in una confezione sostitutiva. Se fornita, la scatola potrebbe essere stata aperta.
Processo di Pagamento Sicuro
Politiche di Reso e Rimborso
Politiche di Spedizione
Politiche di Garanzia

UL indicator/remote signaling

Tightening torque
5 lbf-in. - 7 lbf-in.
Conductor cross section AWG
14 - 12

UL specifications

SPD Type
4CA
Maximum continuous operating voltage MCOV
150 V AC
Maximum continuous operating voltage MCOV
150 V DC
Nominal voltage
120 V DC
Rated load current IL
25 A
Mode of protection
L-N
Mode of protection
L-G
Mode of protection
N-G
Mode of protection
(L+) - (L-)
Mode of protection
(L+) - G
Mode of protection
(L-) - G
Power distribution system
Single phase
Nominal frequency
50/60 Hz
Measured limiting voltage MLV (L-N)
780 V
Measured limiting voltage MLV (L-G)
760 V
Measured limiting voltage MLV (N-G)
760 V
Measured limiting voltage MLV (L+) - (L-)
780 V
Measured limiting voltage MLV (L+) - G
760 V
Measured limiting voltage MLV (L-) - G
760 V
Nominal discharge current In
3 kA

Dimensions

Height
90 mm
Width
17.7 mm
Depth
74.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch
1 Div.

Connection data

Connection method
Screw connection
Conductor cross section flexible
0.2 mm² - 2.5 mm²
Conductor cross section solid
0.2 mm² - 4 mm²
Conductor cross section AWG
24 - 12
Screw thread
M3
Tightening torque
0.8 Nm
Stripping length
8 mm

Indicator/remote signaling

Switching function
N/C contact
Operating voltage
250 V AC
Operating voltage
125 V DC (200 mA DC)
Operating current
3 A AC
Operating current
1 A DC (30 V DC)
Connection method
Screw connection
Conductor cross section flexible
0.2 mm² - 2.5 mm²
Conductor cross section solid
0.2 mm² - 4 mm²
Conductor cross section AWG
24 - 12
Screw thread
M3
Tightening torque
0.8 Nm
Stripping length
8 mm

Ambient conditions

Degree of protection
IP20
Ambient temperature (operation)
-40 °C - 70 °C
Ambient temperature (storage/transport)
-40 °C - 70 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % - 95 %
Shock (operation)
30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)
5g (10 - 150 Hz/20 cycles/axis/X, Y, Z)

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Protective circuit

Nominal voltage UN
120 V AC (TN-S)
Nominal voltage UN
120 V AC (TT - only in use with RCD)
Nominal frequency fN
50 Hz (60 Hz)
Maximum continuous voltage UC
150 V AC
Maximum continuous voltage UC
150 V DC
Rated load current IL
26 A (30 °C)
Residual current IPE
≤ 5 µA
Nominal discharge current In (8/20) µs
3 kA
Standby power consumption PC
≤ 150 mVA (at UREF)
Standby power consumption PC
≤ 175 mVA (at UC)
Reference test voltage UREF
132 V AC
Combination wave UOC
6 kV
Voltage protection level Up (L-N)
≤ 0.85 kV
Voltage protection level Up (L-PE)
≤ 0.95 kV
Voltage protection level Up (N-PE)
≤ 0.95 kV
TOV behavior at UT (L-N)
240 V AC (5 s / withstand mode)
TOV behavior at UT (L-N)
240 V AC (120 min / withstand mode)
TOV behavior at UT (L-PE)
240 V AC (5 s / withstand mode)
TOV behavior at UT (L-PE)
240 V AC (120 min / withstand mode)
TOV behavior at UT (L-PE)
1332 V AC (200 ms / safe failure mode)
TOV behavior at UT (N-PE)
1200 V AC (200 ms / safe failure mode)
Response time tA (L-N)
≤ 25 ns
Response time tA (L-PE)
≤ 100 ns
Response time tA (N-PE)
≤ 100 ns
Short-circuit current rating ISCCR
1.5 kA AC
Short-circuit current rating ISCCR
0.25 kA DC
Max. backup fuse with branch wiring
not required
Maximum backup fuse for through wiring
25 A (gG / B / C)

Standards and Regulations

Standards/specifications
EN 61643-11 2012

UL connection data

Conductor cross section AWG
14 - 12
Tightening torque
5 lbf-in. - 7 lbf-in.