Phoenix Contact
2905233
1 / 1
Descrizione
Replacement plug for type 3 device protection from the PLUGTRAB SEC T3 product range. 60 V nominal voltage.- Country of Origin
- DE
- Part Number
- 2905233
- Tariff Code
- 85363030
- EAN
- 4046356939737
- UPC
- 4046356939737
- ETIM
- Group Code : EG000021
- Group Description : Earthing, lightning and surge protection
- Class Description : Surge protection device for terminal equipment
- Class Code : EC000942
- Version : 7
- Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
- Sconti sulla rivendita fino al 40%!
Invia una richiesta di prezzo
1
Metodi di pagamento:
UL specifications
- SPD Type
- 4CA
- Maximum continuous operating voltage MCOV
- 100 V AC
- Maximum continuous operating voltage MCOV
- 80 V DC
- Nominal voltage
- 60 V DC
- Mode of protection
- L-N
- Mode of protection
- L-G
- Mode of protection
- N-G
- Mode of protection
- (L+) - (L-)
- Mode of protection
- (L+) - G
- Mode of protection
- (L-) - G
- Power distribution system
- Single phase
- Nominal frequency
- 50/60 Hz
- Measured limiting voltage MLV (L-N)
- 540 V
- Measured limiting voltage MLV (L-G)
- 830 V
- Measured limiting voltage MLV (N-G)
- 830 V
- Measured limiting voltage MLV (L+) - (L-)
- 540 V
- Measured limiting voltage MLV (L+) - G
- 830 V
- Measured limiting voltage MLV (L-) - G
- 830 V
- Nominal discharge current In
- 3 kA
Dimensions
- Height
- 60.9 mm
- Width
- 17.5 mm
- Depth
- 44.8 mm
- Horizontal pitch
- 1 Div.
Connection data
- Connection method
- pluggable
Ambient conditions
- Degree of protection
- IP20
- Ambient temperature (operation)
- -40 °C - 80 °C
- Ambient temperature (storage/transport)
- -40 °C - 80 °C
- Altitude
- ≤ 2000 m (amsl (above mean sea level))
- Permissible humidity (operation)
- 5 % - 95 %
- Shock (operation)
- 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
- Vibration (operation)
- 5g (10 - 150 Hz/20 cycles/axis/X, Y, Z)
Environmental Product Compliance
- REACh SVHC
- Lead 7439-92-1
- China RoHS
- Environmentally friendly use period: unlimited = EFUP-e
- China RoHS
- No hazardous substances above threshold values
Protective circuit
- Nominal voltage UN
- 60 V AC (TN-S)
- Nominal frequency fN
- 50 Hz (60 Hz)
- Maximum continuous voltage UC
- 100 V AC
- Maximum continuous voltage UC
- 80 V DC
- Residual current IPE
- ≤ 5 µA
- Nominal discharge current In (8/20) µs
- 2 kA
- Standby power consumption PC
- ≤ 75 mVA (at UREF)
- Standby power consumption PC
- ≤ 150 mVA (at UC)
- Reference test voltage UREF
- 66 V AC
- Combination wave UOC
- 4 kV
- Voltage protection level Up (L-N)
- ≤ 0.48 kV
- Voltage protection level Up (L-PE)
- ≤ 0.9 kV
- Voltage protection level Up (N-PE)
- ≤ 0.9 kV
- TOV behavior at UT (L-N)
- 120 V AC (5 s / withstand mode)
- TOV behavior at UT (L-N)
- 120 V AC (120 min / withstand mode)
- TOV behavior at UT (L-PE)
- 120 V AC (5 s / withstand mode)
- TOV behavior at UT (L-PE)
- 120 V AC (120 min / withstand mode)
- Response time tA (L-N)
- ≤ 25 ns
- Response time tA (L-PE)
- ≤ 100 ns
- Response time tA (N-PE)
- ≤ 100 ns
- Short-circuit current rating ISCCR
- 1.5 kA AC
- Short-circuit current rating ISCCR
- 1 kA DC
Standards and Regulations
- Standards/specifications
- EN 61643-11 2012
Altre categorie
AttuatoriBlocchiCavi, tubi e manichetteCompressoriControlloGiunzioni e raccordiCilindri e PistoniElettronicaFiltriHVACPC industriali e HMIsIlluminazioneTecnica lineareMotoriAlimentatoreTrasmissione di potenzaPompe e ValvoleEnergia rinnovabileRoboticaGuarnizioni, Anelli e ConnettoriSensori e dispositivi di misuraStrumenti e AccessoriCNCAltro