Type 2 surge arrester - VAL-MS 350VF/2+0-FM - 2907903
2907903
  • Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
  • Sconti sulla rivendita fino al 40%!
Registrati
Invia una richiesta di prezzo
1
Metodi di pagamento:
Offerta con tempi di consegna del produttore
Spedizione in:Su richiesta
Miglior prezzo:
Invia una richiesta di prezzo

Additional Information

Part Number
2907903
UPC
4055626257310
Country of Origin
DE
ETIM
Group Code : EG000021
Group Description : Earthing, lightning and surge protection
Class Description : Surge protection device for power supply systems
Class Code : EC000941
Version : 7

NEMA / UL data

Maximum continuous operating voltage MCOV (L-L)
700 V AC
Maximum continuous operating voltage MCOV (L-N)
350 V AC
Voltage protection rating VPR (L-L)
1.8 kV
Nominal discharge current In (L-L)
10 kA

Remote indication contact

Connection name
Remote fault indicator contact
Switching function
PDT contact
Connection method
Screw connection
Screw thread
M2
Tightening torque
0.25 Nm
Tightening torque
4 lbf-in. (UL)
Stripping length
7 mm
Conductor cross section flexible min.
0.14 mm²
Conductor cross section flexible max.
1.5 mm²
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section AWG
28 - 16
Conductor cross section AWG
30 - 14 (UL)

Connection, protective circuit

Connection method
Screw connection
Connection technology
Biconnect terminal block
Screw thread
M5
Tightening torque
4.5 Nm
Tightening torque
30 lbf-in. (UL)
Stripping length
16 mm
Conductor cross section flexible min.
1.5 mm²
Conductor cross section flexible max.
25 mm²
Conductor cross section solid min.
1.5 mm²
Conductor cross section solid max.
35 mm²
Conductor cross section AWG
15 - 2
Conductor cross section AWG
10 - 2 (UL)
Connection method
Fork-type cable lug

Note

Trade restriction
The products are offered exclusively for export outside the EU and the European Economic Area.

Dimensions

Height
97 mm
Width
35.6 mm
Depth
65.7 mm (incl. DIN rail 7.5 mm)
Horizontal pitch
2 Div.

Ambient conditions

Degree of protection
IP20 (only when all terminal points are used)
Ambient temperature (operation)
-40 °C - 80 °C
Ambient temperature (storage/transport)
-40 °C - 80 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % - 95 %
Shock (operation)
25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)
5g (10 - 500 Hz / 2.5 h / X, Y, Z)

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Protective circuit

IEC test classification
II
IEC test classification
T2
EN type
T2
Nominal voltage UN
240/415 V AC (Wye)
Maximum continuous operating voltage UC (L-PEN)
350 V AC
Nominal frequency fN
50 Hz (60 Hz)
Rated load current IL
80 A
Residual current IPE
≤ 10 µA
Standby power consumption PC
≤ 4 mVA
Max. discharge current Imax (8/20) µs
20 kA
Nominal discharge current In (8/20) µs
10 kA
Front of wave sparkover voltage at 6 kV (1.2/50) µs (L-PE)
≤ 1.5 kV
Insulation resistance Riso
> 1 GΩ (100 V DC)
Voltage protection level Up (L-N)
≤ 1.5 kV
Response time tA
≤ 100 ns
Max. backup fuse with branch wiring
125 A AC (gG)
Max. backup fuse with V-type through wiring
80 A AC (gG)
Short-circuit current rating ISCCR
25 kA

Standards and Regulations

Standards/regulations
IEC 61643-11 2011
Standards/regulations
EN 61643-11 2012