Schneider Electric
56230
1 / 1
Descrizione
Attivo maturo
- Country of Origin
- FR
- Part Number
- 56230
- Tariff Code
- 85364900
- EAN
- 3303430562306
- UNSPSC
- 39121601
- Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
- Sconti sulla rivendita fino al 40%!
Invia una richiesta di prezzo
1
Metodi di pagamento:
Environment
- Ambient Air Temperature For Operation
- -35-70 °C
- Electromagnetic Compatibility
- conducted and radiated emissionsB CISPR 11 || conducted radio-frequency immunity test3 IEC 61000-4-6 || electrostatic discharge immunity test4 IEC 61000-4-2 || high-energy conducted susceptibility4 IEC 61000-4-5 || low-energy conducted susceptibility4 IEC 61000-4-4 || radiated susceptibility3 IEC 61000-4-3
- Pollution Degree
- 3 IEC 60664-1
- Ambient Air Temperature For Storage
- -55-85 °C
- Relative Humidity
- 95-95 % 55-55 °C
- Electrical Shock Protection Class
- class II
- Overvoltage Category
- IV
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2310023EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI2310023EN
- Eu Rohs Directive
- Compliant with Exemptions
Complementary
- Ik Degree Of Protection
- IK07 EN 50102
- Mechanical Robustness
- fire resistance IEC 60695-2-1 || IK protection 2 joulesIK07 EN 50102 || vibrations 13.2...100 Hz0.7 g || vibrations 2...13.2 Hz+/- 1 mm
- Height
- 72 mm
- Standards
- EN/IEC 60947-2 Annex M || EN/IEC 60755 || UL 1053 || CAN/CSA C22.2 No. 144
- Type Of Measurement
- earth fault current internal measurement 80...100 %
- Net Weight
- 0.3 kg
- Tamperproof Of Settings
- protected by sealable cover
- Wire Stripping Length
- auxiliary power supply: 7 mm || fault: 7 mm || relay test and fault reset: 7 mm || sensor: 7 mm || voltage presence: 7 mm
- Connections - Terminals
- auxiliary power supply terminal block 0.2-2.5 mm² flexible AWG 24...AWG 12 || auxiliary power supply terminal block 0.2-2.5 mm² rigid AWG 24...AWG 12 || auxiliary power supply terminal block 0.25-2.5 mm² flexible AWG 24...AWG 12 || fault terminal block 0.2-2.5 mm² flexible AWG 24...AWG 12 || fault terminal block 0.2-2.5 mm² rigid AWG 24...AWG 12 || fault terminal block 0.25-2.5 mm² flexible AWG 24...AWG 12 || relay test and fault reset terminal block 0.2-2.5 mm² flexible AWG 24...AWG 12 || relay test and fault reset terminal block 0.2-2.5 mm² rigid AWG 24...AWG 12 || relay test and fault reset terminal block 0.25-2.5 mm² flexible AWG 24...AWG 12 || sensor terminal block 0.2-2.5 mm² flexible AWG 24...AWG 12 || sensor terminal block 0.2-2.5 mm² rigid AWG 24...AWG 12 || sensor terminal block 0.25-2.5 mm² flexible AWG 24...AWG 12 || voltage presence terminal block 0.2-2.5 mm² flexible AWG 24...AWG 12 || voltage presence terminal block 0.2-2.5 mm² rigid AWG 24...AWG 12 || voltage presence terminal block 0.25-2.5 mm² flexible AWG 24...AWG 12
- Cut-Out Dimensions
- 68 x 68 mm
- Ip Degree Of Protection
- on front face IP40 EN/IEC 60529 || on side parts IP30 EN/IEC 60529 || on connection terminals IP20 EN/IEC 60529
- Test Function
- remote test || local
- Monitoring
- electronics continuous) || power supply continuous) || relay/sensor link continuous)
- Width
- 72 mm
- Depth
- 78 mm
- Tightening Torque
- auxiliary power supply: 0.6-0.6 N.m || fault: 0.6-0.6 N.m || relay test and fault reset: 0.6-0.6 N.m || sensor: 0.6-0.6 N.m || voltage presence: 0.6-0.6 N.m
Specifications
- Type Of Setting
- none
- Reset
- manual reset
- Earth Leakage Current
- 0.03-0.03 A
- Mounting Support
- front panel
- Range Compatibility
- VigiPacT TOA earth leakage current sensor || VigiPacT A earth leakage current sensor || VigiPacT L earth leakage current sensor
- Earth-Leakage Protection Class
- type A
- Network Rated Voltage
- 1000-1000 V - AC 50/60 Hz maximum) || 1000-1000 V - AC 400 Hz maximum)
- [Ithe] Conventional Enclosed Thermal Current
- 8 A
- Earthing System
- TN-S || TT || IT
- Relay Application
- protection relay
- Product Or Component Type
- residual current protection relay
- Range
- VigiPacT
- Residual Earth-Leakage Time Delay Adjustment Type
- instantaneous
- Residual Earth-Leakage Sensitity Adjustment Type
- fixed
- Power Consumption In Va
- 4 VA
- [Us] Rated Supply Voltage
- 220...240 V AC 50/60 Hz 55...110 %
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Minimum Load
- 10 mA 12 V
- Device Short Name
- RH10P
Altre categorie
AttuatoriBlocchiCavi, tubi e manichetteCompressoriControlloGiunzioni e raccordiCilindri e PistoniElettronicaFiltriHVACPC industriali e HMIsIlluminazioneTecnica lineareMotoriAlimentatoreTrasmissione di potenzaPompe e ValvoleEnergia rinnovabileRoboticaGuarnizioni, Anelli e ConnettoriSensori e dispositivi di misuraStrumenti e AccessoriCNCAltro