1 / 5
thumbnail
thumbnail
thumbnail
thumbnail
thumbnail

Descrizione

Attivo maturo
This Altistart 22 soft starter can feed 3-phase asynchronous motors in supply line connection. It has a rating of 88A, a rated power from 22kW to 55kW and a rated voltage from 230V to 500V AC. It is designed for simple and complex machines such as centrifugal and piston pumps, fans, screw compressors and material handling equipment. Slim form factor improves versatility, allows mounting in frames of any kind of machines. It features an Integrated bypass, this reduces noise and decreases heat dissipation. Compatibility with SoMove software allows configurations and settings to be easily transferred, meaning spares can be quickly installed. It provides smooth starting for your machinery, avoiding mechanical stresses and extending their service life.
Country of Origin
ID
Part Number
ATS22D88S6
Tariff Code
85371098
EAN
3606480167324
UNSPSC
39121521
Metodi di pagamento:
Migliore offerta da:
SKFornitore Automa.Net di fiducia
Disponibilità:
10 pz.
Disponibile
Aggiornato il: 08-11-2024
Garanzia:
12 mesi
Consegna stimata:
Su richiesta
Condizione:
Nuovo sigillato in fabbrica
Nuovo sigillato in fabbrica - Un articolo nuovo di zecca, inutilizzato, non aperto, non danneggiato, nella sua confezione originale sigillata dal produttore.
Un totale di 11 Parts In-Stock da 2 Distributors
Consegna da:
SK
SK
DE
DE
Processo di Pagamento Sicuro
Politiche di Reso e Rimborso
Politiche di Spedizione
Politiche di Garanzia

Offerte Disponibili (1)

ATS22D88S6 product image
Schneider Electric

ATS22D88S6

Condizione:
Nuove eccedenze
Disponibile:
1 pz.
Disponibile
Aggiornato il: 08-11-2024
Offerta da:
DEFornitore Automa.Net di fiducia
Consegna stimata:
Su richiesta
Garanzia:
12 mesi
1
Offerta con tempi di consegna del produttore
Spedizione in:Su richiesta
Miglior prezzo:
€861.35

Environment

Product Certifications
CCC || GOST || C-tick || CSA || UL
Standards
IEC 60947-4-2
Electromagnetic Compatibility
conducted and radiated emissions level A IEC 60947-4-2 || damped oscillating waves level 3 IEC 61000-4-12 || electrostatic discharge level 3 IEC 61000-4-2 || immunity to electrical transients level 4 IEC 61000-4-4 || immunity to radiated radio-electrical interference level 3 IEC 61000-4-3 || voltage/current impulse level 3 IEC 61000-4-5
Ambient Air Temperature For Operation
-10-40 °C without derating) || 40-60 °C with current derating 2.2 % per °C)
Shock Resistance
15 gn 11 ms IEC 60068-2-27
Vibration Resistance
1 gn 13-200 Hz)IEC 60068-2-6 || 1.5 mm 2-13 Hz)IEC 60068-2-6
Pollution Degree
level 2 IEC 60664-1
Noise Level
45 dB
Ambient Air Temperature For Storage
-25-70 °C
Relative Humidity
0-95 % without condensation or dripping water IEC 60068-2-3
Operating Altitude
<= 3280.84 ft (1000 m) without derating || > 3280.84...< 6561.68 ft (> 1000...< 2000 m) with current derating of 2.2 % per additional 100 m

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Complementary

Device Connection
in the motor supply line
Network Frequency
45...66 Hz
Minimum Switching Current
100 mA 12 V DC relay outputs)
[Uc] Control Circuit Voltage
230 V - 15...10 % 50/60 Hz
Height
295 mm
Discrete Output Type
relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O || relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
Maximum Switching Current
5 A 250 V AC resistive 1 relay outputs || 5 A 30 V DC resistive 1 relay outputs || 2 A 250 V AC inductive 0.4 20 ms relay outputs || 2 A 30 V DC inductive 7 ms relay outputs
Discrete Input Voltage
24 V <= 30 V
Marking
CE
Power Range
55-100 kW 480-500 V 3 phase || 15-25 kW 200-240 V 3 phase || 30-50 kW 380-440 V 3 phase
Net Weight
12 kg
Output Current
0.4...1 Icl adjustable
Installed Device
31
Connector Type
1 RJ45
Motor Starter Type
soft starter
Communication Data Link
serial
Function Available
internal bypass
Discrete Output Number
2
Control Circuit Consumption
20 W
Communication Port Protocol
Modbus
Supply Voltage Limits
195-660 V
Discrete Input Type
LI1, LI2, LI3) logic, 5 mA 4.3 kOhm
Physical Interface
RS485 multidrop
Type Of Cooling
forced convection
Discrete Input Number
3
Assembly Style
with heat sink
Operating Position
vertical +/- 10 degree
Ptc Probe Input
750 Ohm
Width
145 mm
Transmission Rate
4800, 9600 or 19200 bps
Depth
207 mm
Discrete Input Logic
positive logic LI1, LI2, LI3 < 5 V <= 2 mA > 11 V, >= 5 mA
Protection Type
phase failure line || thermal protection motor || thermal protection starter
Supply Frequency
50...60 Hz - 10...10 %

Specifications

Product Destination
asynchronous motors
[Us] Rated Supply Voltage
230...600 V - 15...10 %
Range Of Product
Altistart 22
Product Or Component Type
soft starter
Component Name
ATS22
Phase
3 phase
Power Dissipation In W
66 W for standard applications
Icl Starter Rating
88 A connection in the motor supply line for standard applications
Type Of Start
start with torque control (current limited to 3.5 In)
Utilisation Category
AC-53A
Product Specific Application
pumps and fans
Ip Degree Of Protection
IP20
Factory Setting Current
77 A
Motor Power Kw
22 kW 230 V || 45 kW 400 V || 45 kW 440 V || 55 kW 500 V

Modelli CAD

traceparts
traceparts
Scaricare