1 / 1
thumbnail

Descrizione

Attivo maturo
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 40HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 415 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
Country of Origin
ID
Part Number
LC1D80AN7
Tariff Code
85364900
EAN
3606481312181
UNSPSC
39121529
  • Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
  • Sconti sulla rivendita fino al 40%!
Registrati
Invia una richiesta di prezzo
1
Metodi di pagamento:
Richiedete un preventivo e vi invieremo informazioni su disponibilità e prezzi.

Environment

Product Certifications
CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping)
Height
122 mm
Standards
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
Climatic Withstand
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Net Weight
0.86 kg
Flame Retardance
V1 conforming to UL 94
Protective Treatment
THIEC 60068-2-30
Ip Degree Of Protection
IP20 front face IEC 60529
Mechanical Robustness
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
Operating Altitude
0...9842.52 ft (0...3000 m)
Fire Resistance
850 °C IEC 60695-2-1
Width
55 mm
Depth
120 mm
Permissible Ambient Air Temperature Around The Device
-40-60 °C || 60-70 °C with derating

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1503009EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
ENVEOLI1503009EN
Eu Rohs Directive
Compliant

Complementary

Non-Overlap Time
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current
5 mA for signalling circuit
Power Dissipation Per Pole
9.6 W AC-1 || 6.3 W AC-3 || 6.3 W AC-3e
Average Impedance
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Auxiliary Contact Composition
1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current
10 A (at 60 °C) for signalling circuit || 80 A (at 60 °C) for power circuit
Control Circuit Voltage Limits
0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
Mounting Support
rail || plate
Contact Compatibility
M2
Control Circuit Type
AC 50/60 Hz
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree
3
Insulation Resistance
> 10 MOhm for signalling circuit
Rated Breaking Capacity
1000 A at 440 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V AC for power circuit conforming to IEC 60947
Associated Fuse Rating
10 A gG for signalling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
Inrush Power In Va
140-140 VA 60 Hz cos phi 0.75 (at 20 °C) || 160-160 VA 50 Hz cos phi 0.75 (at 20 °C)
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947
Pole Contact Composition
3 NO
Connections - Terminals
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible with cable end || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: solid || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: solid || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible
Coil Technology
without built-in suppressor module
Operating Time
4...19 ms opening || 12...26 ms closing
Minimum Switching Voltage
17 V for signalling circuit
Maximum Operating Rate
3600 cyc/h 60 °C
Signalling Circuit Frequency
25...400 Hz
Tightening Torque
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
Electrical Durability
0.7 Mcycles 80 A AC-1 <= 440 V || 1 Mcycles 66 A AC-3 <= 440 V || 1 Mcycles 66 A AC-3e <= 440 V
Mechanical Durability
6 Mcycles
Auxiliary Contacts Type
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Compatibility Code
LC1D
Hold-In Power Consumption In Va
13-13 VA 60 Hz cos phi 0.3 (at 20 °C) || 15-15 VA 50 Hz cos phi 0.3 (at 20 °C)
Overvoltage Category
III
Maximum Horse Power Rating
5 hp at 115 V AC 60 Hz for 1 phase motors || 10 hp at 230/240 V AC 60 Hz for 1 phase motors || 20 hp at 200/208 V AC 60 Hz for 3 phase motors || 20 hp at 230/240 V AC 60 Hz for 3 phase motors || 40 hp at 460/480 V AC 60 Hz for 3 phase motors || 50 hp at 575/600 V AC 60 Hz for 3 phase motors
Motor Power Kw
22 kW at 220...230 V AC 50/60 Hz (AC-3) || 37 kW at 380...400 V AC 50/60 Hz (AC-3) || 37 kW at 415 V AC 50/60 Hz (AC-3) || 37 kW at 440 V AC 50/60 Hz (AC-3) || 37 kW at 500 V AC 50/60 Hz (AC-3) || 37 kW at 660...690 V AC 50/60 Hz (AC-3) || 22 kW at 220...230 V AC 50/60 Hz (AC-3e) || 37 kW at 380...400 V AC 50/60 Hz (AC-3e) || 37 kW at 415 V AC 50/60 Hz (AC-3e) || 37 kW at 440 V AC 50/60 Hz (AC-3e) || 37 kW at 500 V AC 50/60 Hz (AC-3e) || 37 kW at 660...690 V AC 50/60 Hz (AC-3e)
[Ui] Rated Insulation Voltage
signalling circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-4-1
[Icw] Rated Short-Time Withstand Current
640 A 40 °C - 10 s for power circuit || 900 A 40 °C - 1 s for power circuit || 110 A 40 °C - 10 min for power circuit || 260 A 40 °C - 1 min for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
Heat Dissipation
4-5 W at 50/60 Hz
Protective Cover
with

Specifications

[Uc] Control Circuit Voltage
415 V AC 50/60 Hz
[Ue] Rated Operational Voltage
power circuit 690 V AC 25...400 Hz || power circuit 300 V DC
Range Of Product
TeSys Deca
Contactor Application
motor control || resistive load
Product Or Component Type
contactor
Range
TeSys || TeSys Deca
Utilisation Category
AC-1 || AC-4 || AC-3 || AC-3e
[Ie] Rated Operational Current
80 A (at <60 °C) at <= 440 V AC-1 for power circuit || 66 A (at <60 °C) at <= 440 V AC-3 for power circuit || 66 A (at <60 °C) at <= 440 V AC-3e for power circuit
Poles Description
3P
Device Short Name
LC1D

Modelli CAD

traceparts
traceparts
Scaricare