1 / 1
thumbnail

Descrizione

Attivo maturo
TeSys F contactor, 3 poles (3NO), 185A/690V AC-3, for motor applications up to 90kW@400V. It provides a 24V 50Hz AC coil, bolt terminals for bars or cables with lugs. For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Country of Origin
CZ
Part Number
LC1F185B5
Tariff Code
85364190
EAN
3389110226720
UNSPSC
39121529
Metodi di pagamento:
Migliore offerta da:
SKFornitore Automa.Net di fiducia
Disponibilità:
10 pz.
Disponibile
Aggiornato il: 08-11-2024
Garanzia:
12 mesi
Consegna stimata:
Su richiesta
Condizione:
Nuovo sigillato in fabbrica
Nuovo sigillato in fabbrica - Un articolo nuovo di zecca, inutilizzato, non aperto, non danneggiato, nella sua confezione originale sigillata dal produttore.
Un totale di 11 Parts In-Stock da 2 Distributors
Consegna da:
SK
SK
DE
DE
Processo di Pagamento Sicuro
Politiche di Reso e Rimborso
Politiche di Spedizione
Politiche di Garanzia

Offerte Disponibili (1)

LC1F185B5 product image
Schneider Electric

LC1F185B5

Condizione:
Nuove eccedenze
Disponibile:
1 pz.
Disponibile
Aggiornato il: 08-11-2024
Offerta da:
DEFornitore Automa.Net di fiducia
Consegna stimata:
Su richiesta
Garanzia:
12 mesi
1
Offerta con tempi di consegna del produttore
Spedizione in:Su richiesta
Miglior prezzo:
€247.09

Specifications

[Uc] Control Circuit Voltage
24 V AC 50 Hz
Range Of Product
TeSys F
[Ue] Rated Operational Voltage
<= 460 V DC || <= 690 V AC 50/60 Hz
Contactor Application
resistive load || motor control
Product Or Component Type
contactor
Range
TeSys
Utilisation Category
AC-3 || AC-4 || AC-1
[Ie] Rated Operational Current
275 A 40 °C) <= 440 V AC-1 || 185 A 55 °C) <= 440 V AC-3
Poles Description
3P
Device Short Name
LC1F

Contractual warranty

Warranty
18 months

Complementary

Product Certifications
LROS (Lloyds register of shipping) || DNV || RMRoS || UL || RINA || CB || CCC || BV || ABS || UKCA
Power Dissipation Per Pole
12 W AC-3 || 25 W AC-1
Average Impedance
0.33 mOhm - Ith 275 A 50 Hz
[Ith] Conventional Free Air Thermal Current
275 A 40 °C
Control Circuit Voltage Limits
operational 0.85...1.1 Uc 50/60 Hz 55 °C) || drop-out 0.35...0.55 Uc 50/60 Hz 55 °C)
Standards
JIS C8201-4-1 || IEC 60947-4-1 || EN 60947-4-1 || EN 60947-1 || IEC 60947-1
Mounting Support
plate
Control Circuit Type
AC 50 Hz
Rated Breaking Capacity
1480 A IEC 60947-4-1
Associated Fuse Rating
200 A aM <= 440 V || 315 A gG <= 440 V
[Uimp] Rated Impulse Withstand Voltage
8 kV
Inrush Power In Va
805-805 VA, 50 Hz 0.3 20 °C)
Connections - Terminals
control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bar 2 25 x 3 mm || power circuit lugs-ring terminals 1 150-150 mm² || power circuit connector 1 150-150 mm² || power circuit bolted connection
Pole Contact Composition
3 NO
Operating Time
20...35 ms closing || 7...15 ms opening
Maximum Operating Rate
2400 cyc/h 55 °C
Mechanical Durability
10 Mcycles
Tightening Torque
control circuit 1.2 N.m || power circuit 18 N.m
Compatibility Code
LC1F
Hold-In Power Consumption In Va
55-55 VA, 50 Hz 0.3 20 °C)
Overvoltage Category
III
Motor Power Kw
90 kW 380...400 V AC 50/60 Hz AC-3) || 100 kW 415 V AC 50/60 Hz AC-3) || 100 kW 440 V AC 50/60 Hz AC-3) || 110 kW 500 V AC 50/60 Hz AC-3) || 110 kW 660...690 V AC 50/60 Hz AC-3) || 55 kW 220...230 V AC 50/60 Hz AC-3) || 33 kW 400 V AC 50/60 Hz AC-4)
[Ui] Rated Insulation Voltage
1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
[Icw] Rated Short-Time Withstand Current
1500 A 40 °C - 10 s || 920 A 40 °C - 30 s || 740 A 40 °C - 1 min || 500 A 40 °C - 3 min || 400 A 40 °C - 10 min
Heat Dissipation
18-24 W

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP080208EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI100418
Eu Rohs Directive
Compliant

Environment

Ambient Air Temperature For Operation
-5-55 °C
Height
174 mm
Net Weight
4.65 kg
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH
Ip Degree Of Protection
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Operating Altitude
9842.52 ft (3000 m) without derating
Width
168.5 mm
Depth
181 mm
Permissible Ambient Air Temperature Around The Device
-40-70 °C

Modelli CAD

traceparts
traceparts
Scaricare