- Product Certifications
- UL || CSA || CCC || CB Scheme || EAC || UKCA
- Power Dissipation Per Pole
- 200 W AC-1
- Average Impedance
- 0.1 mOhm - Ith 2100 A 50 Hz
- [Ith] Conventional Free Air Thermal Current
- 2100 A (at 40 °C)
- Control Circuit Voltage Limits
- operational 0.85...1.1 Uc 40...400 Hz 55 °C) || drop-out 0.3...0.5 Uc 40...400 Hz 55 °C)
- Standards
- EN 60947-1 || JIS C8201-4-1 || EN 60947-4-1 || IEC 60947-4-1 || IEC 60947-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
- Mounting Support
- plate
- Control Circuit Type
- AC 40...400 Hz
- Rated Breaking Capacity
- 3150 A conforming to IEC 60947-4-1
- Associated Fuse Rating
- 2000 A gG at <= 440 V
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Inrush Power In Va
- 2200-2200 VA, 40...400 Hz 0.9 20 °C)
- Connections - Terminals
- control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bar 4 100 x 5 mm || power circuit bolted connection
- Pole Contact Composition
- 3 NO
- Operating Time
- 100...170 ms opening || 40...75 ms closing
- Maximum Operating Rate
- 600 cyc/h 55 °C
- Tightening Torque
- control circuit 1.2 N.m || power circuit 58 N.m
- Compatibility Code
- LC1F
- Hold-In Power Consumption In Va
- 36-36 VA, 40...400 Hz 0.9 20 °C)
- Overvoltage Category
- III
- [Ui] Rated Insulation Voltage
- 1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C || 1000 V UL 60947-4-1
- [Icw] Rated Short-Time Withstand Current
- 10000 A 40 °C - 10 s || 7500 A 40 °C - 30 s || 5500 A 40 °C - 1 min || 4200 A 40 °C - 3 min || 3000 A 40 °C - 10 min
- Heat Dissipation
- 36-36 W