LC1K0910E7 is a compact 3-pole TeSys K contactor from Schneider Electric for motor applications. Rated 9A AC-3 4kW@400V, it includes a 48V 50/60Hz AC coil and 1NO auxiliary contact. LC1K0910E7 is a 3-pole TeSys K contactor from Schneider Electric for simple motor applications rated up to 4kW@400V. Very compact, DIN-rail compatible, with connections by screw clamp terminals, it includes a 48V 50/60Hz AC coil and 1NO built-in auxiliary contact. Available worldwide, it complies with multi-standards (IEC, UL, CSA, CCC, EAC, Marine) and is certified Green Premium (RoHs/Reach). Very compact, 45mm wide, for DIN-rail and panel mounting. Provides a control circuit compatible with 50Hz and 60Hz supplies and 1NO built-in auxiliary contact. Optimized for simple power applications. Can be completed with auxiliary contact blocks (LA1K, LA2K) and thermal relays (LR2K).
Country of Origin
FR
Part Number
LC1K0910E7
Tariff Code
85364190
EAN
3389110374766
UNSPSC
39121529
€20.88
net
Spedizione da:
€25.00
1
Metodi di pagamento:
Migliore offerta da:
ITFornitore Automa.Net di fiducia
Disponibilità:
9 pz.
Disponibile
Aggiornato il: 22-11-2024
Garanzia:
12 mesi
Consegna stimata:
26-29 novembre a Regno Unito
Condizione:
Nuovo sigillato in fabbrica
Nuovo sigillato in fabbrica - Un articolo nuovo di zecca, inutilizzato, non aperto, non danneggiato, nella sua confezione originale sigillata dal produttore.
Informazioni sulla spedizione
Processo di Pagamento Sicuro
Politiche di Reso e Rimborso
Politiche di Spedizione
Politiche di Garanzia

Environment

Product Certifications
CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
Standards
EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1
Flame Retardance
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Protective Treatment
TC IEC 60068 || TC DIN 50016
Operating Altitude
6561.68 ft (2000 m) without derating

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1503003EN
Sustainable Offer Status
Green Premium product
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
ENVEOLI1503003EN
Eu Rohs Directive
Compliant

Complementary

Minimum Switching Current
5 mA for signalling circuit
Mechanical Robustness
shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27 || vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 || vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6
[Uc] Control Circuit Voltage
48 V AC 50/60 Hz
[Ue] Rated Operational Voltage
power circuit <= 690 V AC <= 400 Hz || signalling circuit <= 690 V AC <= 400 Hz
Height
58 mm
Average Impedance
3 mOhm - Ith 20 A 50 Hz for power circuit
Auxiliary Contact Composition
1 NO
Control Circuit Voltage Limits
operational: 0.8...1.15 Uc (at <50 °C) || drop-out: >= 0.20 Uc (at <50 °C)
Non Overlap Distance
0.5 mm
[Ith] Conventional Free Air Thermal Current
20 A (at 60 °C) for power circuit || 10 A (at 50 °C) for signalling circuit
Control Circuit Type
AC 50/60 Hz
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Insulation Resistance
> 10 MOhm for signalling circuit
Rated Breaking Capacity
110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conforming to IEC 60947
Irms Rated Making Capacity
110 A AC for power circuit conforming to IEC 60947 || 110 A AC for signalling circuit conforming to IEC 60947
Motor Power Kw
2.2 kW 220...230 V AC 50/60 Hz AC-3 || 4 kW 380...415 V AC 50/60 Hz AC-3 || 4 kW 440/690 V AC 50/60 Hz AC-3 || 2.2 kW 220...230 V AC 50/60 Hz AC-3e || 4 kW 380...415 V AC 50/60 Hz AC-3e || 4 kW 440/690 V AC 50/60 Hz AC-3e || 2.2 kW 220...230 V AC 50/60 Hz AC-4 || 4 kW 380...415 V AC 50/60 Hz AC-4 || 4 kW 440/690 V AC 50/60 Hz AC-4
Associated Fuse Rating
25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for signalling circuit conforming to IEC 60947 || 10 A gG for signalling circuit conforming to VDE 0660
[Uimp] Rated Impulse Withstand Voltage
8 kV
Inrush Power In Va
30-30 VA (at 20 °C)
Connections - Terminals
screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4 mm²flexible without cable end || screw clamp terminals 2 0.34-1.5 mm²flexible with cable end
Pole Contact Composition
3 NO
Utilisation Category
AC-3 || AC-3e || AC-1 || AC-4
[Ie] Rated Operational Current
9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit || 9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit || 20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit
Minimum Switching Voltage
17 V for signalling circuit
Maximum Operating Rate
3600 cyc/h
Signalling Circuit Frequency
<= 400 Hz
Electrical Durability
1.3 Mcycles 9 A AC-3 <= 440 V || 1.3 Mcycles 9 A AC-3e <= 440 V || 0.16 Mcycles 20 A AC-1 <= 690 V || 0.02 Mcycles 54 A AC-4 <= 440 V
Mechanical Durability
10 Mcycles
Auxiliary Contacts Type
instantaneous 1 NO
Poles Description
3P
Hold-In Power Consumption In Va
4.5-4.5 VA (at 20 °C)
Operating Time
10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing
Width
45 mm
Overvoltage Category
III
Depth
57 mm
[Icw] Rated Short-Time Withstand Current
90 A 50 °C - 1 s for power circuit || 85 A 50 °C - 5 s for power circuit || 80 A 50 °C - 10 s for power circuit || 60 A 50 °C - 30 s for power circuit || 45 A 50 °C - 1 min for power circuit || 40 A 50 °C - 3 min for power circuit || 20 A 50 °C - >= 15 min for power circuit || 80 A - 1 s for signalling circuit || 90 A - 500 ms for signalling circuit || 110 A - 100 ms for signalling circuit
Heat Dissipation
1.3-1.3 W

Specifications

Contactor Application
resistive load || motor control
Product Or Component Type
contactor
Range
TeSys
Device Application
control
Device Short Name