Schneider Electric
LC2D12G7V
1 / 1
Descrizione
Attivo maturo
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 12A reversing inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 3HP at 200-208VAC, 3HP at 240VAC, 7.5HP at 480VAC and 10HP at 600VAC three phase. Contactor is also rated for 1HP at 115VAC and 2HP at 240VAC single phase. Contactor is supplied with a 120 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 3.54 inches wide and 3.39 inches deep. It weighs 1.54 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.- Country of Origin
- FR
- Part Number
- LC2D12G7V
- Tariff Code
- 85364900
- EAN
- 3389110410884
- UNSPSC
- 39121529
Metodi di pagamento:
- Migliore offerta da:
- Fornitore Automa.Net di fiducia
- Disponibilità:
- 1 pz.DisponibileAggiornato il: 08-11-2024
- Garanzia:
- 12 mesi
- Consegna stimata:
- Su richiesta
- Condizione:
- Nuove eccedenze
Nuove eccedenze - Un articolo nuovo, inutilizzato e non danneggiato senza garanzia del produttore. L'articolo può arrivare senza confezione originale o in una confezione sostitutiva. Se fornita, la scatola potrebbe essere stata aperta.
Processo di Pagamento Sicuro
Politiche di Reso e Rimborso
Politiche di Spedizione
Politiche di Garanzia
Environment
- Mechanical Robustness
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
- Ambient Air Temperature For Operation
- -40-60 °C || 60-70 °C with derating
- Height
- 77 mm
- Climatic Withstand
- IACS E10 || IEC 60947-1 Annex Q category D
- Pollution Degree
- 3
- Net Weight
- 0.697 kg
- Flame Retardance
- V1 conforming to UL 94
- Ambient Air Temperature For Storage
- -60-80 °C
- Protective Treatment
- TH IEC 60068-2-30
- Ip Degree Of Protection
- IP20 front face IEC 60529
- Operating Altitude
- 0...9842.52 ft (0...3000 m)
- Fire Resistance
- 850 °C IEC 60695-2-1
- Width
- 90 mm
- Depth
- 86 mm
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1501004
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Toxic Heavy Metal Free
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
- Reach Free Of Svhc
- Yes
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Circularity Profile
- ENVEOLI1501004
- Eu Rohs Directive
- Compliant
Complementary
- Non-Overlap Time
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Minimum Switching Current
- 5 mA for signalling circuit
- Control Circuit Voltage Limits
- 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
- Insulation Resistance
- > 10 MOhm for signalling circuit
- Inrush Power In Va
- 70-70 VA 60 Hz cos phi 0.75 (at 20 °C) || 70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
- Coil Technology
- without built-in suppressor module
- Minimum Switching Voltage
- 17 V for signalling circuit
- Signalling Circuit Frequency
- 25...400 Hz
- Auxiliary Contacts Type
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Hold-In Power Consumption In Va
- 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C) || 7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
- Heat Dissipation
- 2-3 W 50/60 Hz
Specifications
- Product Certifications
- DNV || CSA || CCC || UL || GL || LROS (Lloyds register of shipping) || BV || RINA || GOST || UKCA
- Interlocking Type
- electrical and mechanical
- [Uc] Control Circuit Voltage
- 120 V AC 50/60 Hz
- [Ue] Rated Operational Voltage
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Power Dissipation Per Pole
- 1.56 W AC-1 || 0.36 W AC-3
- Average Impedance
- 2.5 mOhm - Ith 25 A 50 Hz for power circuit
- Auxiliary Contact Composition
- 1 NO + 1 NC
- [Ith] Conventional Free Air Thermal Current
- 10 A (at 60 °C) for signalling circuit || 25 A (at 60 °C) for power circuit
- Mounting Support
- plate || rail
- Control Circuit Type
- AC 50/60 Hz
- Standards
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Safety Reliability Level
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Contactor Application
- resistive load || motor control
- Rated Breaking Capacity
- 250 A at 440 V for power circuit conforming to IEC 60947
- Product Or Component Type
- reversing contactor
- Irms Rated Making Capacity
- 250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1
- Product Name
- TeSys D || TeSys Deca
- Associated Fuse Rating
- 10 A gG for signalling circuit conforming to IEC 60947-5-1 || 40 A gG at <= 690 V coordination type 1 for power circuit || 25 A gG at <= 690 V coordination type 2 for power circuit
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947
- Connections - Terminals
- power circuit screw clamp terminals 1 1-4 mm²flexible without cable end || power circuit screw clamp terminals 2 1-4 mm²flexible without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible with cable end || power circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || power circuit screw clamp terminals 1 1-4 mm²solid || power circuit screw clamp terminals 2 1-4 mm²solid || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid || control circuit screw clamp terminals 2 1-4 mm²solid
- Range
- TeSys || TeSys Deca
- Pole Contact Composition
- 3 NO
- Device Presentation
- preassembled with reversing power busbar
- Utilisation Category
- AC-3 || AC-1
- [Ie] Rated Operational Current
- 25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
- Maximum Operating Rate
- 3600 cyc/h 60 °C
- Tightening Torque
- power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
- Electrical Durability
- 2 Mcycles 12 A AC-3 <= 440 V || 0.8 Mcycles 25 A AC-1 <= 440 V
- Mechanical Durability
- 15 Mcycles
- Poles Description
- 3P
- Operating Time
- 12...22 ms closing || 4...19 ms opening
- Overvoltage Category
- III
- Motor Power Kw
- 3 kW at 220...230 V AC 50 Hz || 5.5 kW at 380...400 V AC 50 Hz || 5.5 kW at 415...440 V AC 50 Hz || 7.5 kW at 500 V AC 50 Hz || 7.5 kW at 660...690 V AC 50 Hz
- Maximum Horse Power Rating
- 1 hp at 115 V AC 60 Hz for 1 phase motors || 2 hp at 230/240 V AC 60 Hz for 1 phase motors || 3 hp at 200/208 V AC 60 Hz for 3 phase motors || 3 hp at 230/240 V AC 60 Hz for 3 phase motors || 7.5 hp at 460/480 V AC 60 Hz for 3 phase motors || 10 hp at 575/600 V AC 60 Hz for 3 phase motors
- [Ui] Rated Insulation Voltage
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
- Device Short Name
- LC2D
- [Icw] Rated Short-Time Withstand Current
- 30 A 40 °C - 10 min for power circuit || 61 A 40 °C - 1 min for power circuit || 105 A 40 °C - 10 s for power circuit || 210 A 40 °C - 1 s for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
- Protective Cover
- with
Modelli CAD
traceparts
ScaricareAltre categorie
AttuatoriBlocchiCavi, tubi e manichetteCompressoriControlloGiunzioni e raccordiCilindri e PistoniElettronicaFiltriHVACPC industriali e HMIsIlluminazioneTecnica lineareMotoriAlimentatoreTrasmissione di potenzaPompe e ValvoleEnergia rinnovabileRoboticaGuarnizioni, Anelli e ConnettoriSensori e dispositivi di misuraStrumenti e AccessoriCNCAltro