Reversing Contactor, TeSys Deca, 3P(3NO), AC-3, IEC, <=440V, 50A, 120V AC 60Hz coil
LC2D50G7
  • Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
  • Sconti sulla rivendita fino al 40%!
Registrati
Invia una richiesta di prezzo
1
Metodi di pagamento:
Offerta con tempi di consegna del produttore
Spedizione in:Su richiesta
Miglior prezzo:
Invia una richiesta di prezzo

Additional Information

Part Number
LC2D50G7
UNSPSC
39121529
Tariff Code
8536490065
Country of Origin
CZ

Environment

Product Certifications
GL || UL || RINA || GOST || CSA || LROS (Lloyds register of shipping) || CCC || DNV || BV || UKCA
Ambient Air Temperature For Operation
-5-60 °C
Standards
IEC 60947-4-1 || CSA C22.2 No 14 || UL 508 || IEC 60947-5-1 || EN 60947-4-1 || EN 60947-5-1
Shock Resistance
10 gn contactor closed || 8 gn contactor opened
Vibration Resistance
2 gn 5-300 Hz contactor opened || 3 gn 5-300 Hz contactor closed
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH 3)IEC 60068
Ip Degree Of Protection
IP2X IEC 60529 || IP2X VDE 0106
Operating Altitude
9842.52 ft (3000 m) without derating
Fire Resistance
850 °C IEC 60695-2-1
Permissible Ambient Air Temperature Around The Device
-40-70 °C at Uc
Heat Dissipation
6-10 W at 50/60 Hz for control circuit

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110205EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
N/A
Eu Rohs Directive
Compliant

Complementary

Non-Overlap Time
1.5 ms on de-energisation between NC and NO contacts || 1.5 ms on energisation between NC and NO contacts
Interlocking Type
mechanical
Minimum Switching Current
5 mA for control circuit
[Ue] Rated Operational Voltage
power circuit <= 1000 V AC 25...400 Hz
Height
132 mm
Power Dissipation Per Pole
3.7 W AC-3 - Ith 80 A
Average Impedance
Ith 80 A 50 Hz for power circuit
Auxiliary Contact Composition
1 NO + 1 NC
Control Circuit Voltage Limits
drop-out: 0.3...0.6 Uc at 50/60 Hz (at <60 °C) || operational: 0.8...1.1 Uc at 50 Hz (at <60 °C) || operational: 0.85...1.1 Uc at 60 Hz (at <60 °C)
[Ith] Conventional Free Air Thermal Current
10 A (at 60 °C) for control circuit || 80 A (at 60 °C) for power circuit
Mounting Support
plate || rail
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Insulation Resistance
> 10 MOhm for control circuit
Rated Breaking Capacity
900 A at 440 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity
140 A AC for control circuit conforming to IEC 60947-5-1 || 900 A at 440 V for power circuit conforming to IEC 60947
Associated Fuse Rating
10 A gG for control circuit conforming to IEC 60947-5-1 || 100 A gG at <= 690 V coordination type 1 for power circuit || 100 A gG at <= 690 V coordination type 2 for power circuit
Net Weight
2.4 kg
Inrush Power In Va
200-200 VA cos phi 0.75 (at 20 °C) || 220-220 VA cos phi 0.75 (at 20 °C)
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947
Coil Technology
without built-in bidirectional peak limiting diode suppressor
Flame Retardance
V1 conforming to UL 94
Minimum Switching Voltage
17 V for control circuit
Maximum Operating Rate
3600 cyc/h 60 °C
Tightening Torque
control circuit 1.7 N.m 1-2.5 mm² flat Ø 6 mm || control circuit 1.7 N.m 1-2.5 mm² Philips No 2 || control circuit 1.7 N.m 1-4 mm² flat Ø 6 mm || control circuit 1.7 N.m 1-4 mm² Philips No 2 || power circuit 5 N.m 1-25 mm² hexagonal || power circuit 8 N.m 1-35 mm² hexagonal
Assembly Style
ready assembled
Mechanical Durability
6000000 cycles
Auxiliary Contacts Type
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Hold-In Power Consumption In Va
20-20 VA 50 Hz cos phi 0.3 (at 20 °C) || 22-22 VA 60 Hz cos phi 0.3 (at 20 °C) || 26-26 VA 50 Hz cos phi 0.3 (at 20 °C) || 26-26 VA 60 Hz cos phi 0.3 (at 20 °C)
Operating Time
12...26 ms closing || 4...19 ms opening
Width
165 mm
Overvoltage Category
III
Depth
142 mm
[Ui] Rated Insulation Voltage
control circuit 600 V CSA || control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL || control circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-1
Protective Cover
with

Specifications

Control Circuit Type
AC
[Uc] Control Circuit Voltage
120 V AC 60 Hz
Range Of Product
TeSys Deca
Contactor Application
motor control
Product Or Component Type
reversing contactor
Connections - Terminals
control circuit 1 1-4 mm²flexible with cable end || power circuit 2 1-25 mm²flexible with cable end || power circuit 2 1-25 mm²flexible without cable end || power circuit 2 1-25 mm²solid without cable end || power circuit 2 1-35 mm²flexible with cable end || power circuit 2 1-35 mm²flexible without cable end || power circuit 2 1-35 mm²solid without cable end || control circuit 1 1-4 mm²flexible without cable end || control circuit 1 1-4 mm²solid without cable end || control circuit 2 1-2.5 mm²flexible with cable end || control circuit 2 1-4 mm²flexible without cable end || control circuit 2 1-4 mm²solid without cable end || power circuit 1 1-35 mm²flexible with cable end || power circuit 1 1-35 mm²flexible without cable end || power circuit 1 1-35 mm²solid without cable end
Pole Contact Composition
3 NO
Utilisation Category
AC-2 || AC-3 || AC-4
[Ie] Rated Operational Current
power circuit 50 A AC AC-3 60 °C)
Poles Description
3P
Motor Power Kw
15 kW 220...240 V AC 50/60 Hz || 22 kW 380...400 V AC 50/60 Hz || 25 kW 415 V AC 50/60 Hz || 30 kW 440 V AC 50/60 Hz || 30 kW 500 V AC 50/60 Hz || 33 kW 660...690 V AC 50/60 Hz
Device Short Name
LC2D
Coil Type
standard

Documenti

Data Sheet

Scaricare