1 / 1
thumbnail

Descrizione

Attivo maturo
TeSys D changeover contactor, 4 poles (4NO), for non-inductive load applications up to 32A/690V AC-1. It provides 230V 50/60Hz AC coils, 2NO+2NC built-in auxiliary contacts (NC mirror contacts), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired changeover power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Country of Origin
FR
Part Number
LC2DT32E7
Tariff Code
85364190
EAN
3389110245745
UNSPSC
39121529
€162.24
net
1
Metodi di pagamento:
Migliore offerta da:
FRFornitore Automa.Net di fiducia
Disponibilità:
4 pz.
Disponibile
Aggiornato il: 25-10-2024
Garanzia:
12 mesi
Consegna stimata:
Su richiesta
Condizione:
Nuove eccedenze
Nuove eccedenze - Un articolo nuovo, inutilizzato e non danneggiato senza garanzia del produttore. L'articolo può arrivare senza confezione originale o in una confezione sostitutiva. Se fornita, la scatola potrebbe essere stata aperta.
Un totale di 5 Parts In-Stock da 2 Distributors
Processo di Pagamento Sicuro
Politiche di Reso e Rimborso
Politiche di Spedizione
Politiche di Garanzia

Offerte Disponibili (1)

LC2DT32E7 product image
Schneider Electric

LC2DT32E7

Condizione:
Nuove eccedenze
Disponibile:
1 pz.
Disponibile
Aggiornato il: 28-10-2024
Offerta da:
DEFornitore Automa.Net di fiducia
Consegna stimata:
Su richiesta
Garanzia:
12 mesi
1
Offerta con tempi di consegna del produttore
Spedizione in:Su richiesta
Miglior prezzo:
€61.77

Environment

Mechanical Robustness
vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
Ambient Air Temperature For Operation
-40-60 °C || 60-70 °C with derating
Height
91 mm
Climatic Withstand
IACS E10 || IEC 60947-1 Annex Q category D
Pollution Degree
3
Net Weight
0.85 kg
Flame Retardance
V1 conforming to UL 94
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH IEC 60068-2-30
Ip Degree Of Protection
IP20 front face IEC 60529
Operating Altitude
0...9842.52 ft (0...3000 m)
Fire Resistance
850 °C IEC 60695-2-1
Width
90 mm
Depth
98 mm

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1501004
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
ENVEOLI1501004
Eu Rohs Directive
Compliant

Complementary

Non-Overlap Time
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current
5 mA for signalling circuit
Control Circuit Voltage Limits
0.3...0.6 Uc -40-60 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz
Insulation Resistance
> 10 MOhm for signalling circuit
Inrush Power In Va
70-70 VA 60 Hz cos phi 0.75 (at 20 °C) || 70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
Coil Technology
without built-in suppressor module
Minimum Switching Voltage
17 V for signalling circuit
Signalling Circuit Frequency
25...400 Hz
Auxiliary Contacts Type
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Hold-In Power Consumption In Va
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C) || 7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat Dissipation
2-3 W 50/60 Hz

Specifications

Product Certifications
UL || CSA || CCC || EAC || UKCA || CB || EU-RO-MR by DNV-GL
Interlocking Type
mechanical
[Uc] Control Circuit Voltage
48 V AC 50/60 Hz
[Ue] Rated Operational Voltage
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Power Dissipation Per Pole
2.5 W AC-1
Average Impedance
2.5 mOhm - Ith 32 A 50 Hz for power circuit
Auxiliary Contact Composition
1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current
10 A (at 60 °C) for signalling circuit || 32 A (at 60 °C) for power circuit
Mounting Support
plate || rail
Control Circuit Type
AC 50/60 Hz
Standards
CSA C22.2 No 60947-4-1 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Contactor Application
resistive load
Rated Breaking Capacity
300 A at 440 V for power circuit conforming to IEC 60947
Product Or Component Type
changeover contactor
Irms Rated Making Capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1 || 300 A at 440 V for power circuit conforming to IEC 60947
Product Name
TeSys Deca
Associated Fuse Rating
10 A gG for signalling circuit conforming to IEC 60947-5-1 || 50 A gG at <= 690 V coordination type 1 for power circuit || 35 A gG at <= 690 V coordination type 2 for power circuit
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947
Connections - Terminals
control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid || control circuit screw clamp terminals 2 1-4 mm²solid || power circuit connector 1 2.5-10 mm²flexible without cable end || power circuit connector 2 2.5-10 mm²flexible without cable end || power circuit connector 1 2.5-10 mm²flexible with cable end || power circuit connector 2 2.5-10 mm²flexible with cable end || power circuit connector 1 2.5-16 mm²solid || power circuit connector 2 2.5-16 mm²solid
Range
TeSys || TeSys Deca
Pole Contact Composition
4 NO
Device Presentation
preassembled, with prewired power connections
Utilisation Category
AC-1 || AC-3 || AC-3e || AC-4
[Ie] Rated Operational Current
32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
Maximum Operating Rate
3600 cyc/h 60 °C
Tightening Torque
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m connector flat Ø 6 mm || power circuit 1.7 N.m connector Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
Electrical Durability
1 Mcycles 32 A AC-1 <= 690 V
Mechanical Durability
15 Mcycles
Poles Description
4P
Operating Time
12...22 ms closing || 4...19 ms opening
Overvoltage Category
III
[Ui] Rated Insulation Voltage
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
Device Short Name
LC2D
[Icw] Rated Short-Time Withstand Current
40 A 40 °C - 10 min for power circuit || 84 A 40 °C - 1 min for power circuit || 145 A 40 °C - 10 s for power circuit || 240 A 40 °C - 1 s for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
Protective Cover
with