- Product Certifications
- RINA || DNV || GOST || BV || LROS (Lloyds register of shipping) || GL || CSA || UL || CCC
- Interlocking Type
- mechanical
- [Uc] Control Circuit Voltage
- 110 V AC 50/60 Hz
- [Ue] Rated Operational Voltage
- power circuit <= 690 V AC 25...400 Hz
- Standards
- EN 60947-5-1 || EN 60947-4-1 || UL 508 || IEC 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || IEC 60335-1
- Pole Contact Composition
- 3 x 3 NO
- Mounting Support
- plate
- Control Circuit Type
- AC 50/60 Hz
- Contactor Application
- motor control
- Product Or Component Type
- star delta starter
- Product Name
- TeSys Deca
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947
- Range
- TeSys || TeSys Deca
- Device Presentation
- pre-wired
- Utilisation Category
- AC-3
- [Ie] Rated Operational Current
- 18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
- Auxiliary Contact Composition
- 1 NC KM1 star contactor
- Electrical Durability
- 1.65 Mcycles 18 A AC-3 <= 440 V
- Provided Equipment
- protective cover
- Overvoltage Category
- III
- Motor Power Kw
- 11 kW 220/230 V AC 50/60 Hz || 22 kW 415 V AC 50/60 Hz || 22 kW 440 V AC 50/60 Hz || 18.5 kW 380/400 V AC 50/60 Hz
- [Ui] Rated Insulation Voltage
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
- Device Short Name
- LC3D
- Poles Description
- 3 x 3P