Schneider Electric
LR9F63
1 / 1
Descrizione
Attivo maturo
TeSys LR9F electronic overload relay, thermal setting range 48-80A, selectable class 10-10A-20, for protection of motors 30-37kW@400V. to be mounted directly below a TeSys F 3-pole contactor LC1 F115, F150, F185, use of a support mounting plate LA7F901 is recommended (to be ordered separately). The motor protection includes thermal overload of 1-phase and 3-phase motors, phase failure, phase unbalance, prolonged starting times, stalled rotor conditions, completed with an overheating alarm function. On the front, the relay provides a thermal adjustement dial, buttons for test, stop & reset, a trip indicator, trip auxiliary contacts 1NO+1NC, and alarm circuit terminals. Multi standards certified (IEC, UL, CSA, CCC, Marine), Green Premium compliant (RoHs/Reach).- Country of Origin
- FR
- Part Number
- LR9F63
- Tariff Code
- 85364900
- EAN
- 3389118057524
- UNSPSC
- 39122330
Metodi di pagamento:
- Migliore offerta da:
- Fornitore Automa.Net di fiducia
- Disponibilità:
- 1 pz.DisponibileAggiornato il: 12-11-2024
- Garanzia:
- 12 mesi
- Consegna stimata:
- Su richiesta
- Condizione:
- Nuove eccedenze
Nuove eccedenze - Un articolo nuovo, inutilizzato e non danneggiato senza garanzia del produttore. L'articolo può arrivare senza confezione originale o in una confezione sostitutiva. Se fornita, la scatola potrebbe essere stata aperta.
Processo di Pagamento Sicuro
Politiche di Reso e Rimborso
Politiche di Spedizione
Politiche di Garanzia
Specifications
- Network Type
- AC
- Thermal Protection Adjustment Range
- 48-80 A
- Relay Application
- motor protection
- Signalling Function
- pre-alarm indicator
- Product Or Component Type
- electronic thermal overload relay
- Product Name
- TeSys LRF
- Thermal Overload Class
- class 10/20 IEC 60947-4
- Range
- TeSys
- Product Compatibility
- LC1F115...LC1F185
- Device Short Name
- LR9F
Contractual warranty
- Warranty
- 18 months
Complementary
- Network Frequency
- 50/60 Hz
- Current Consumption
- <= 5 mA no-load
- Height
- 96 mm
- [Ith] Conventional Free Air Thermal Current
- 5 A control circuit
- Tightening Torque
- control circuit 1.2 N.m screw clamp terminals || power circuit 18 N.m screw clamp terminals || alarm circuit 0.45 N.m screw clamp terminals
- Reset
- manual reset
- Phase Failure Sensitivity
- tripping in 4 s +/- 20 % IEC 60947-4-1
- [Ue] Rated Operational Voltage
- 1000 V AC 50/60 Hz power circuit VDE 0110 group C
- Switching Capacity In Ma
- 0...150 mA
- Net Weight
- 0.9 kg
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947-1
- Maximum Voltage Drop
- <2.5 V closed state
- Connections - Terminals
- control circuit screw clamp terminals 1 0.75-2.5 mm² flexible - with cable end || control circuit screw clamp terminals 1 0.75-2.5 mm² solid || control circuit screw clamp terminals 1 0.75-4 mm² flexible - without cable end || control circuit screw clamp terminals 2 1-1.5 mm² flexible - with cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible - without cable end || control circuit screw clamp terminals 2 1-1 mm² solid || power circuit lugs-ring terminals M8 || alarm circuit screw clamp terminals 1 0.5-1.5 mm² flexible - without cable end
- [Ui] Rated Insulation Voltage
- power circuit 1000 V AC IEC 60947-4
- Contacts Type And Composition
- 1 NO + 1 NC
- Surge Withstand
- 4 kV IEC 61000-4-5
- Tripping Threshold
- 1.05 +/- 0.06 In alarm IEC 60947-4-1 || 1.12 +/- 0.06 In tripping IEC 60947-4-1
- Supply Voltage Limits
- 17-32 V alarm circuit)
- Mounting Support
- direct on contactor || plate
- Control Type
- dial White full-load current adjustment || test button Red || push-button reset || push-button Red stop || selector switch load balancing || selector switch class 10/20
- Local Signalling
- alarm || trip indicator
- Width
- 115 mm
- Depth
- 123.5 mm
- [Us] Rated Supply Voltage
- 24 V DC alarm circuit
- Temperature Compensation
- -20-70 °C
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP080207EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI100406
- Eu Rohs Directive
- Compliant
Environment
- Product Certifications
- UL || CSA || UKCA
- Mechanical Robustness
- shocks13 Gn for 11 ms IEC 60068-2-7 || vibrations 5...300 Hz2 GN IEC 60068-2-6
- Standards
- VDE 0660 || EN 60947-4-1 || IEC 60255-17 || IEC 60255-8 || IEC 60947-4-1
- Ambient Air Temperature For Operation
- -20-55 °C IEC 60255-8
- Electromagnetic Compatibility
- resistance to electrostatic discharge 6 kV in indirect mode IEC 61000-4-2 || resistance to electrostatic discharge 8 kV in air IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test 10 V/m IEC 61000-4-3 || fast transients immunity test 2 kV IEC 61000-4-4
- Dielectric Strength
- 6 kV 50 Hz IEC 255-5
- Ip Degree Of Protection
- IP20 conforming to IEC 60529
- Ambient Air Temperature For Storage
- -40-85 °C
- Protective Treatment
- TH
- Operating Altitude
- <= 6561.68 ft (2000 m) without derating
- Fire Resistance
- 850 °C IEC 60695-2-1
Modelli CAD
traceparts
ScaricareAltre categorie
AttuatoriBlocchiCavi, tubi e manichetteCompressoriControlloGiunzioni e raccordiCilindri e PistoniElettronicaFiltriHVACPC industriali e HMIsIlluminazioneTecnica lineareMotoriAlimentatoreTrasmissione di potenzaPompe e ValvoleEnergia rinnovabileRoboticaGuarnizioni, Anelli e ConnettoriSensori e dispositivi di misuraStrumenti e AccessoriCNCAltro