Schneider Electric
LV432086
trip unit MicroLogic 2.3 for ComPact NSX 400/630 circuit breakers, electronic, rating 250A, 4 poles 4d
- Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
- Sconti sulla rivendita fino al 40%!
Invia una richiesta di prezzo
1
Metodi di pagamento:
Un totale di 2 Parts In-Stock da 12 Distributors
Condizioni del prodotto:
Offerta con tempi di consegna del produttore
Spedizione in:Su richiesta
Miglior prezzo:
€387.35
Additional Information
- Part Number
- LV432086
- UNSPSC
- 43201542
- Country of Origin
- FR
Environment
- Product Certifications
- CCC || EAC || Marine
- Ambient Air Temperature For Operation
- -25-70 °C
- Standards
- UL 508 || EN/IEC 60947-2
- Ambient Air Temperature For Storage
- -50-85 °C
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP120606EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI120604EN
- Eu Rohs Directive
- Compliant with Exemptions
Important Information
- Important Message
- This product has been switched to new ComPacT range and is no longer commercialized. It will continue to be available in H1 2023 only limited to specific projects.
Complementary
- Thermal Memory
- 20 minutes before and after tripping
- Earth-Leakage Protection
- without
- Long Time Delay Adjustment Type
- fixed
- Instantaneous Pick-Up Adjustment Type Ii
- fixed
- Zone Selective Interlocking Zsi
- without
- [Tr] Long-Time Delay Adjustment Range
- 11-11 s 7.2 x Ir || 16-16 s 6 x Ir || 400-400 s 1.5 x Ir
- Short-Time Delay Adjustment Type
- fixed
- Instantaneous Pick-Up Adjustment Range
- 3000 A
- Neutral Protection Setting
- 0.5 x Ir 3t + N/2) || 1 x Ir 4t) || no protection 3t)
- Long Time Pick-Up Adjustment Type Ir
- adjustable 9 settings
- Long Time Pick-Up Adjustment Range
- 70...250 A
- [Tsd] Short-Time Delay Adjustment Range
- 0.02-0.02 s
- [Isd] Short-Time Pick-Up Adjustment Range
- 1.5...10 x Ir
- Short-Time Pick-Up Adjustment Type Isd
- adjustable 9 settings
Specifications
- Network Frequency
- 50/60 Hz
- Trip Unit Name
- MicroLogic 2.3
- Range Of Product
- ComPact NSX400...630
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz
- Trip Unit Protection Functions
- LSoI
- Network Type
- AC
- Protected Poles Description
- 4t || 3t || 3t + N/2
- Product Or Component Type
- trip unit
- Protection Type
- L : for overload protection (long time) || So : for short time short-circuit protection with fixed delay || I : for instantaneous short-circuit protection
- Range
- ComPact
- Poles Description
- 4P
- Neutral Position
- left
- Range Compatibility
- ComPact NSX400 || ComPact NSX630
- Device Application
- distribution
- Trip Unit Technology
- electronic
Documenti
Data Sheet
ScaricareModelli CAD
traceparts
Scaricare