Circuit breaker, ComPact NSX100R, 200kA/415VAC, MicroLogic 6.2E-M trip unit 25A, 3 poles 3d
LV433285
  • Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
  • Sconti sulla rivendita fino al 40%!
Registrati
Invia una richiesta di prezzo
1
Metodi di pagamento:
Offerta con tempi di consegna del produttore
Spedizione in:Su richiesta
Miglior prezzo:
€1,200.11

Additional Information

Part Number
LV433285
Country of Origin
FR

Specifications

Network Frequency
50/60 Hz
Line Rated Current
25 A 65 °C
Trip Unit Name
Micrologic 6.2 E-M
Range Of Product
ComPact NSX100...250
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz
Trip Unit Protection Functions
LSIG
Network Type
AC
Protected Poles Description
3t
Product Or Component Type
circuit breaker
Product Name
ComPact NSX
Range
ComPact
Control Type
toggle
Utilisation Category
category A
Mounting Mode
fixed
Breaking Capacity
200 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 || 200 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 || 200 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 80 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 65 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 45 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
Suitability For Isolation
yes EN/IEC 60947-2
Poles Description
3P
Breaking Capacity Code
R 200 kA 415 V AC
Device Application
motor
Device Short Name
NSX100R
Trip Unit Technology
electronic

Contractual warranty

Warranty
18 months

Complementary

[Tg] Ground-Fault Time Delay Adjustment Range
0-0.4 s
[Ics] Rated Service Breaking Capacity
200 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 200 kA 380/415 V AC 50/60 Hz IEC 60947-2 || 200 kA 440 V AC 50/60 Hz IEC 60947-2 || 80 kA 500 V AC 50/60 Hz IEC 60947-2 || 65 kA 525 V AC 50/60 Hz IEC 60947-2 || 45 kA 660/690 V AC 50/60 Hz IEC 60947-2
Height
161 mm
[Ig] Ground-Fault Pick-Up Adjustment Range
0.6...1 x In || Ig enable on/off
Thermal Memory
20 minutes before and after tripping
Earth-Leakage Protection
without
Ground-Fault Time Delay Adjustment Type -Tg
adjustable 5 settings
Mounting Support
backplate
Complementary Motor Protection
protracted starting time || phase unbalance || underload || stalled rotor
Ground-Fault Pick-Up Adjustment Type
adjustable 9 settings
Instantaneous Pick-Up Adjustment Range
425 A
Type Of Measurement
energy meter
Downside Connection
front
Number Of Slots
5
Communication Of Data
maximeters/minimeters || power quality || phase sequence || demand current and power || maintenance indicators || protection and alarm settings || instantaneous and demand values || thermal image function || energy metering || time-stamped histories and event tables
Protection Type
L : for overload protection (long time) || S : for short time short-circuit protection || I : for instantaneous short-circuit protection || G : for ground fault protection
Long Time Delay Adjustment Type
adjustable
Instantaneous Pick-Up Adjustment Type Ii
fixed
Zone Selective Interlocking Zsi
with
Net Weight
2.05 kg
[Tr] Long-Time Delay Adjustment Range
10-10 s 7.2 x Ir 10 || 120-120 s 1.5 x Ir 5 || 20-20 s 7.2 x Ir 20 || 240-240 s 1.5 x Ir 10 || 26-26 s 6 x Ir 20 || 480-480 s 1.5 x Ir 20 || 5-5 s 7.2 x Ir 5 || 13.5-13.5 s 6 x Ir 10 || 6.5-6.5 s 6 x Ir 5 || 30-30 s 7.2 x Ir 30 || 38-38 s 6 x Ir 30 || 720-720 s 1.5 x Ir 30
Electrical Durability
10000 cycles 690 V In || 20000 cycles 690 V In/2 || 30000 cycles 440 V In || 50000 cycles 440 V In/2
Short-Time Delay Adjustment Type
fixed
Long Time Pick-Up Adjustment Type Ir
adjustable 9 settings
Long Time Pick-Up Adjustment Range
12...25 A
Upside Connection
front
[Ui] Rated Insulation Voltage
800 V AC 50/60 Hz
Trip Unit Rating
25-25 A 65 °C
Local Signalling
for ready to operate flashing LED (green) || for temperature over set point LED 95 % Ith (red)
Mechanical Durability
50000 cycles
Motor Tripping Class
5 || 10 || 30 || 20
[Isd] Short-Time Pick-Up Adjustment Range
5...13 x Ir
Connection Pitch
35 mm
[Uimp] Rated Impulse Withstand Voltage
8 kV
Width
105 mm
Display Type
LCD display
Depth
86 mm
Short-Time Pick-Up Adjustment Type Isd
adjustable

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP120606EN
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI120604EN
Eu Rohs Directive
Compliant

Environment

Product Certifications
EAC || Marine || CCC
Ik Degree Of Protection
IK07 IEC 62262
Ambient Air Temperature For Operation
-25-70 °C
Standards
EN/IEC 60947
Ip Degree Of Protection
IP40 conforming to IEC 60529
Electrical Shock Protection Class
class II
Pollution Degree
3 IEC 60664-1
Ambient Air Temperature For Storage
-40-85 °C
Relative Humidity
0-95 %
Operating Altitude
0...6561.68 ft (0...2000 m) without derating || 2000 m...5000 m with derating
Overvoltage Category
class II

Modelli CAD

traceparts
traceparts
Scaricare

Prodotti correlati