Schneider Electric
LV433742
1 / 1
Descrizione
This Compact NSX630HB2 is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for motor protection applications. The breaking capacity (Icu) is 85kA rms at 500VAC 50/60Hz and 100kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic Micrologic 1.3 M trip unit, with 500A rating. Micrologic 1.3 M trip unit provides an adjustable short time protection and a fixed instantaneous protection. This 3 poles version (140mm x 255mm x 110mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. Compact NSX630HB2 is part of Schneider Electric EcoStruxure Power architecture.- Country of Origin
- FR
- Part Number
- LV433742
- Tariff Code
- 85362090
- EAN
- 3606480481307
Metodi di pagamento:
- Migliore offerta da:
- Fornitore Automa.Net di fiducia
- Disponibilità:
- 1 pz.DisponibileAggiornato il: 08-11-2024
- Garanzia:
- 12 mesi
- Consegna stimata:
- Su richiesta
- Condizione:
- Nuove eccedenze
Nuove eccedenze - Un articolo nuovo, inutilizzato e non danneggiato senza garanzia del produttore. L'articolo può arrivare senza confezione originale o in una confezione sostitutiva. Se fornita, la scatola potrebbe essere stata aperta.
Processo di Pagamento Sicuro
Politiche di Reso e Rimborso
Politiche di Spedizione
Politiche di Garanzia
Specifications
- Network Frequency
- 50/60 Hz
- Line Rated Current
- 500 A 65 °C
- Trip Unit Name
- Micrologic 1.3 M
- Range Of Product
- ComPact NSX400...630
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz
- Trip Unit Protection Functions
- I
- Network Type
- AC
- Protected Poles Description
- 3t
- Product Or Component Type
- circuit breaker
- Product Name
- ComPact NSX
- Range
- ComPact
- Control Type
- toggle
- Utilisation Category
- category A
- Mounting Mode
- fixed
- Breaking Capacity
- 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
- Suitability For Isolation
- yes EN/IEC 60947-2
- Poles Description
- 3P
- Breaking Capacity Code
- HB2 100 kA 690 V AC
- Device Application
- motor
- Device Short Name
- NSX630HB2
- Trip Unit Technology
- electronic
Contractual warranty
- Warranty
- 18 months
Complementary
- [Ics] Rated Service Breaking Capacity
- 100 kA 500 V AC 50/60 Hz IEC 60947-2 || 100 kA 525 V AC 50/60 Hz IEC 60947-2 || 100 kA 660/690 V AC 50/60 Hz IEC 60947-2
- Height
- 255 mm
- Earth-Leakage Protection
- without
- Mounting Support
- backplate
- Instantaneous Pick-Up Adjustment Range
- 6500 A
- Downside Connection
- front
- Number Of Slots
- 6
- Protection Type
- I : for short-circuit protection (magnetic)
- Instantaneous Pick-Up Adjustment Type Ii
- fixed
- Zone Selective Interlocking Zsi
- without
- Net Weight
- 6.2 kg
- Electrical Durability
- 2000 cycles 690 V In || 6000 cycles 690 V In/2 || 4000 cycles 440 V In || 8000 cycles 440 V In/2
- Short-Time Delay Adjustment Type
- fixed
- Upside Connection
- front
- [Ui] Rated Insulation Voltage
- 800 V AC 50/60 Hz
- Trip Unit Rating
- 500-500 A 65 °C
- Local Signalling
- for ready to operate flashing LED (green)
- Mechanical Durability
- 15000 cycles
- [Isd] Short-Time Pick-Up Adjustment Range
- 3000 A || 3500 A || 4500 A || 2500 A || 5000 A || 6500 A || 5500 A || 4000 A || 6000 A
- Connection Pitch
- 45 mm
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Width
- 140 mm
- Depth
- 110 mm
- Short-Time Pick-Up Adjustment Type Isd
- adjustable 9 settings
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP120606EN
- Sustainable Offer Status
- Green Premium product
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI120604EN
- Eu Rohs Directive
- Compliant
Environment
- Product Certifications
- CCC || EAC || Marine
- Ik Degree Of Protection
- IK07 IEC 62262
- Ambient Air Temperature For Operation
- -25-70 °C
- Standards
- EN/IEC 60947
- Ip Degree Of Protection
- IP40 conforming to IEC 60529
- Electrical Shock Protection Class
- class II
- Pollution Degree
- 3 IEC 60664-1
- Ambient Air Temperature For Storage
- -50-85 °C
- Relative Humidity
- 0-95 %
- Operating Altitude
- 0...6561.68 ft (0...2000 m) without derating || 2000 m...5000 m with derating
- Overvoltage Category
- class II
Modelli CAD
traceparts
Scaricare