- Power Consumption In W
- 0.5 W 12 V DC
- Safety Reliability Data
- B10d = 190000 || MTTFd = 205.4 years
- Contacts Type And Composition
- 1 C/O timed contact || 1 C/O timed or instantaneous contact
- Setting Accuracy Of Time Delay
- +/- 10 % of full scale 25 °C IEC 61812-1
- Maximum Delay Response
- 100 ms
- Control Type
- rotary knob front panel
- Insulation Resistance
- 100 MOhm 500 V DC IEC 60664-1
- Immunity To Microbreaks
- 10 ms
- Power Consumption In Va
- 1.2-1.2 VA 12 V AC
- Minimum Pulse Duration
- 30 ms || 100 ms under load
- Maximum Switching Current
- 8 mA
- Voltage Range
- 0.9...1.2 Us
- Net Weight
- 0.09 kg
- Mounting Position
- any position in relation to normal vertical mounting plane
- Voltage Drift
- +/- 0.2 %/V
- Reset Time
- 120 ms on de-energisation
- Maximum Switching Voltage
- 250 V
- Connections - Terminals
- screw terminals, 2 x 1.5 mm² with cable end || screw terminals, 2 x 2.5 mm² without cable end
- [Us] Rated Supply Voltage
- 12 V AC/DC
- Temperature Drift
- +/- 0.05 %/°C
- Time Delay Range
- 1...10 min || 6...60 min || 0.1...1 s || 6...60 s || 1...10 s || 1...10 h || 10...100 h
- Minimum Switching Current
- 10 mA 5 V
- Mounting Support
- 35 mm DIN rail conforming to IEC 60715
- Electrical Durability
- 100000 cycles for resistive load, 8 A at 250 V, AC
- Mechanical Durability
- 10000000 cycles
- Breaking Capacity
- 2000 VA
- Housing Material
- self-extinguishing
- Status Led
- Green LED flashing)timing in progress || Green LED steady)power ON || Yellow LEDrelay energised
- [Uimp] Rated Impulse Withstand Voltage
- 5 kV 1.2-50 µs IEC 60664-1 || 5 kV IEC 61812-1
- Width
- 22.5 mm
- Time Delay Type
- power on-delay || on-delay and off-delay || interval || off-delay || symmetrical flashing
- Tightening Torque
- 0.6-1 N.m IEC 60947-1
- Supply Frequency
- 50...60 Hz +/- 5 %
- Repeat Accuracy
- +/- 0.5 % IEC 61812-1