Schneider Electric
REL50469
PowerLogic P5F30 24-48V 3LPCT 1CSH 4LPVT 22DI-14DO 6 Arc Sensors Advanced Logic and Cybersec Backup memory ANSI
- Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
- Sconti sulla rivendita fino al 40%!
Invia una richiesta di prezzo
1
Metodi di pagamento:
Environment
- Mechanical Robustness
- vibrations class 2) IEC 60255-21-1 || shocks class 2) IEC 60255-21-2 || earthquakes class 2) IEC 60255-21-3 || vibrations GOST 17516.1
- Ambient Air Temperature For Operation
- -40-85 °C 16 h ) || -40-70 °C 96 h )
- Environmental Characteristic
- exposure to cold IEC 60068-2-1 || exposure to dry heat IEC 60068-2-2 || exposure to damp heat in service IEC 60068-2-78 || exposure to damp heat in service IEC 60068-2-30 || temperature variation IEC 60068-2-14 || salt mist IEC 60068-2-52 || influence of corrosion/gas test 2 IEC 60068-2-60 || influence of corrosion/gas test 4 IEC 60068-2-60 || stationary use at weatherprotected locations IEC 60721-3-3
- Electromagnetic Compatibility
- emission tests class A CISPR 11 || emission tests class A CISPR 22 || immunity to electromagnetic emissions IACS E10 || surge withstand ANSI C37.90.1 || immunity to electromagnetic interference ANSI C37.90.2 || electrostatic discharge class 4 ANSI C37.90.3 || electromagnetic field immunity test GOST 30804.4.3 || limits for harmonic current emissions GOST 30804.4.12 || EMC immunity GOST 32137 || EMC immunity class 4 IEC 61000-4-2 || EMC immunity level 3 IEC 61000-4-3 || EMC immunity level 4 IEC 61000-4-4 || EMC immunity level 4 IEC 61000-4-5 || EMC immunity level 3 IEC 61000-4-6 || EMC immunity level 5 IEC 61000-4-8 || EMC immunity level 5 IEC 61000-4-9 || EMC immunity level 5 IEC 61000-4-10 || EMC immunity IEC 61000-4-12 || EMC immunity level 4 IEC 61000-4-16 || EMC immunity level 3 IEC 61000-4-18
- Relative Humidity
- 0-93 % at 40-40 °C, without condensation, 56 days || 93-95 % at 25-55 °C, 6 cycles, 12 + 12 hours
- Protective Treatment
- conformal coating conforming to IEC 60068-2-52:Kb/1 || conformal coating conforming to IEC 60068-2-60:Ke || conformal coating conforming to IEC 60721-3-3:3C2
- Operating Altitude
- 6561.68 ft (2000 m)
Contractual warranty
- Warranty
- up to 10 years (Standard warranty 2 years. Please check with your local SE representative for extended warranty availability and conditions))
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1901010
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Circularity Profile
- ENVEOLI1901010
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Complementary
- Number Of Key
- 7 customizable
- Local Signalling
- 10 x LED tri-colour programmable || 4 x LED red
- Depth
- 219 mm
- Width
- 152 mm
- Height
- 176 mm
- Display Type
- colour LCD 480 x 272 pixels
- Net Weight
- 3.5 kg
- Software Name
- eSetup Easergy Pro virtual simulation test
Specifications
- Analogue Output Number
- 0
- Input Type
- 3 LPCT current || 1 CSH residual current || 4 voltage voltage || 22 digital
- Range Of Product
- PowerLogic P5
- Connections - Terminals
- pin (input) || pin (output) || ring lugs (current transformer) || ring lugs (voltage transformer)
- Network And Machine Diagnosis Type
- event recording || disturbance recording || trip context information || relay maintenance
- Device Mounting
- flush
- Number Of Outputs
- 13 digital || 1 watchdog
- Mounting Support
- rack
- Protection Type
- phase overcurrent 50/51 || directional phase overcurrent 67 || earth fault overcurrent 50N/51N || directional earth fault 67N || transient earth fault 67NI || neutral admittance 21YN || earth fault wattmetric 32N || capacitor bank unbalance 51C || current unbalance 46 I2/I1 || broken conductor || cold load pick-up || switch ON to fault (SOTF) || H2 detection || H5 detection || breaker failure 50BF || directional active underpower 37P || fault locator 21FL || recloser 79 || negative sequence overcurrent 46 || overvoltage 59 || undervoltage 27 || earth fault overvoltage 59N || underfrequency 81/81N || rate of change of frequency 81R || synchro-check 25 || lockout relay 86 || CT supervision 60 || VT supervision 60 || programmable stages 99 || programmable logic || programmable curve
- Relay Application
- feeder - directional over current
- Communication Port Protocol
- without
- Product Or Component Type
- protection relay
- Single Line Diagram
- 6 controlled + 2 monitored objects
- Mounting Case Size
- 30TE
- Monitoring Function
- trip circuit supervision 74 || circuit breaker monitoring || relay self-monitoring
- Mounting Mode
- withdrawable
- Control Type
- switchgear control and monitoring || programmable switchgear interlocking || local/remote control || advanced logic engine
- Setting
- 4
- Integrated Connection Type
- front USB 2.0 type A 2 || rear extension port 1 with backup memory
- Cybersecurity
- port hardening || firmware signature || client IP address filter || secured communication with assciated tools || role-based access control || security policy management || security log || IEC 62442-4-2 SL1
- Arc Flash Protection
- yes
- Type Of Measurement
- current 3-phase || current zero sequence || current positive sequence || current negative sequence || current ratio of negative and positive || current phasor diagram view || current 2nd, 15th harmonics with THD || voltage 3-phase || voltage residual || voltage zero sequence || voltage positive sequence || voltage negative sequence || voltage phasor diagram view || frequency
- Device Short Name
- P5F30-CCDE-IAAAH-AADK
- [Us] Rated Supply Voltage
- 24...48 V DC
Documenti
Data Sheet
ScaricareAltre categorie
AttuatoriBlocchiCavi, tubi e tubi flessibiliCompressoriControlloGiunzioni e raccordiCilindri e PistoniElettronicaFiltriHVACPC industriali e HMIsIlluminazioneTecnica lineareMotoriAlimentatoreTrasmissione di potenzaPompe e ValvoleEnergia rinnovabileRoboticaGuarnizioni, Anelli e ConnettoriSensori e dispositivi di misuraStrumenti e AccessoriCNCAltro