- Maximum Measuring Cycle
- 140 ms as true rms value
- Hysteresis
- 5-5 % threshold
- Insulation Resistance
- > 500 MOhm 500 V DC between supply and relay output 60255-5 || > 500 MOhm 500 V DC between measurement and relay output 60664-1 || > 1 MOhm 500 V DC between supply and measurement 60255-5 || > 500 MOhm 500 V DC between supply and relay output 60664-1 || > 500 MOhm 500 V DC between measurement and relay output 60255-5 || > 1 MOhm 500 V DC between supply and measurement 60664-1
- [Us] Rated Supply Voltage
- 208...480 V AC 3 phase || 230 V AC 1 phase
- Operating Rate
- <= 360 operations/hour full load
- Status Led
- 1 LED Green power ON || 1 LED Yellow fault || 1 LED Yellow relay ON
- Output Contacts
- 1 C/O
- Reset Time
- 2000 ms
- Marking
- CE : EMC 89/336/EEC || CE : 73/23/EEC
- Response Time
- < 300 ms (in the event of a fault)
- Input Current
- 11 A permanent at 25 °C E1-L2 terminals || 50 A non repetitive < 1 s at 25 °C E1-L2 terminals
- Maximum Switching Voltage
- 250 V AC/DC
- Connections - Terminals
- screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
- [Ui] Rated Insulation Voltage
- 400 V IEC 60664-1
- Overvoltage Category
- III IEC 60664-1
- Supply Voltage Limits
- 183-528 V AC
- Mounting Support
- 35 mm symmetrical DIN rail conforming to IEC 60715
- Nominal Output Current
- 5 A
- Mechanical Durability
- 30000000 cycles
- Housing Material
- self-extinguishing plastic
- Resistance Across Terminals
- 0.01 Ohm E1-L2 terminals
- Operating Position
- any position
- Control Circuit Voltage Limits
- 15 % + 10 % Un
- Measurement Accuracy
- +/- 10 % of the full scale value
- Measurement Error
- 1 % by volt over the whole range || +/- 0.05 %/°C
- Width
- 35 mm
- Tightening Torque
- 0.6-1 N.m IEC 60947-1
- Electrical Durability
- 100000 cycles
- [Us] Rated Supply Voltage
- 208...480 V AC 3 phase || 230 V AC single phase
- Run-Up Delay At Power-Up
- 0.5 s
- Supply Frequency
- 50/60 Hz +/- 10 %
- Repeat Accuracy
- +/- 1 % input and measurement circuit || +/- 1 % time delay