- Insulation Between Channels And Logic Bus
- 1500 V for 1 minute
- Cold Swapping
- yes
- Height
- 13.9 mm
- Reset
- manual reset COM fault
- Absolute Maximum Voltage
- 56 V 1.3 ms
- Discrete Output Logic
- positive or negative
- Status Led
- 1 LED (Green) module status (RDY) || 1 LED per channel (Green) channel status (OUT1 to OUT4) || 1 LED (Red) module error (ERR)
- Output Voltage
- 19.2...30 V DC
- Hot Swapping Fallback
- yes for standard NIMs
- Maximum Load Inductance
- 500 mH 4 Hz
- Supply
- power distribution module
- Response Time
- 560 µs off-to-on || 870 µs on-to-off
- Protection Type
- power protection integrated fuse on PDM time lag 10 A || reverse polarity protection || short-circuit protection || thermal overload protection
- Surge Current
- 5 A 0.5 ms
- Current Consumption
- 70 mA 5 V DC logic bus
- Marking
- CE
- Net Weight
- 0.11 kg
- Discrete Output Current
- 500 mA
- Fallback Status
- state 0 basic NIMs || user configurable standard NIMs
- Minimum Load
- 0.5 mA
- Width
- 128.3 mm
- Overvoltage Category
- II
- Depth
- 70 mm
- Product Compatibility
- power distribution module STBPDT3100/3105 || I/O base STBXBA1000
- Maximum Leakage Current
- 0.4 mA at state 0 30 V
- [Us] Rated Supply Voltage
- 24 V DC
- Maximum Load Capacitance