Schneider Electric
VW3A4554
line/motor choke - 1 mH - 31 A - 3 phases - 90 W - for variable speed drive
- Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
- Sconti sulla rivendita fino al 40%!
Invia una richiesta di prezzo
1
Metodi di pagamento:
Un totale di 28 Parts In-Stock da 20 Distributors
Condizioni del prodotto:
Offerta con tempi di consegna del produttore
Spedizione in:Su richiesta
Miglior prezzo:
€197.74
Additional Information
- Part Number
- VW3A4554
- UNSPSC
- 26111515
- Tariff Code
- 8504907500
- Country of Origin
- FR
Environment
- Standards
- EN 50178 || IEC 60076 (with HD398) || VDE 0160 level 1
- Ambient Air Temperature For Operation
- 45-55 °C with current derating of 2 % per °C) || 0-45 °C without current derating)
- Shock Resistance
- 15 gn 11 ms IEC 60068-2-27
- Environmental Characteristic
- 3B1 IEC 721-3-3 || 3C2 IEC 721-3-3 || 3S1 IEC 721-3-3
- Vibration Resistance
- 1 gn 13-200 Hz)IEC 60068-2-6 || 1.5 mm peak to peak 3-13 Hz)IEC 60068-2-6
- Relative Humidity
- 0-95 %
- Pollution Degree
- 2 EN 50178
- Ambient Air Temperature For Storage
- -25-70 °C
- Ip Degree Of Protection
- choke IP00 || terminals IP10
- Operating Altitude
- <= 3280.84 ft (1000 m) without current derating || 3280.84...9842.52 ft (1000...3000 m) with current derating 1 % per 100 m
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Toxic Heavy Metal Free
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Reach Free Of Svhc
- Yes
- China Rohs Regulation
- X
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Complementary
- Height
- 170 mm
- Net Weight
- 6 kg
- Leakage Distance
- 11.5 mm IEC 60664
- Electrical Insulation Class
- class F
- Minimum Clearance Distance
- 5.5 mm IEC 60664
- Max Current
- 1.65 x nominal current 60 s)
- Width
- 155 mm
- Depth
- 135 mm
- Maximum Voltage Drop At Rated Load
- 5 %
- Supply Frequency
- 50...60 Hz
Specifications
- Thermal Losses
- 90 W
- Range Of Product
- Altivar
- Product Or Component Type
- line/motor choke
- Phase
- three phase
- Value Of Inductance
- 1 mH
- Product Compatibility
- variable speed drive ATV310 7.5 kW - motor choke - 1 per drive || ATV31CD11N4 - line choke - 1 per drive || variable speed drive ATV320 15 kW 525...600 V - three phase - motor choke - 1 per drive || ATV312HU55M3 - line choke - 1 per drive || LXM32.D30N4 - line choke - 1 per drive || ATV71HD18Y - line choke - 1 per drive || ATV312HD15S6 - motor choke - 1 per drive || ATV312HD11S6 - motor choke - 1 per drive || ATV312HD15N4 - line choke - 1 per drive || ATV61WD11N4C - line choke - 1 per drive || ATV61HD15N4 - line choke - 1 per drive || ATV71WD15N4 - line choke - 1 per drive || variable speed drive ATV340 7.5 kW 380...480 V - line choke - 1 per drive || variable speed drive ATV930 18.5 kW 500...690 V - three phase - line choke - 1 per drive || LXM32MC10N4 - line choke - 1 per drive || ATV312HD11N4 - motor choke - 1 per drive || variable speed drive ATV320 5.5 kW 200...240 V - three phase - line choke - 1 per drive || variable speed drive ATV320 7.5 kW 380...500 V - three phase - motor choke - 1 per drive || variable speed drive ATV310 11 kW - line choke - 1 per drive || ATV312HU40M3 - line choke - 1 per drive || variable speed drive ATV320 5.5 kW 200...240 V - three phase - motor choke - 1 per drive || ATV312HU40M3 - motor choke - 1 per drive || ATV61HD22Y - line choke - 1 per drive || variable speed drive ATV340 11 kW 380...480 V - line choke - 1 per drive || ATV32HD11N4 - motor choke - 1 per drive || variable speed drive ATV930 600 V - three phase - line choke - 25 hp - 1 per drive || LXM32.D18N4 - line choke - 1 per drive || variable speed drive ATV320 15 kW 380...500 V - three phase - line choke - 1 per drive || ATV61HU55M3 - line choke - 1 per drive || ATV32HD11N4 - line choke - 1 per drive || ATV12PU40M3 - motor choke - 1 per drive || variable speed drive ATV340 15 kW 380...480 V - line choke - 1 per drive || LXM32.D72N4 - line choke - 1 per drive || ATV312HU75N4 - motor choke - 1 per drive || variable speed drive ATV320 11 kW 380...500 V - three phase - line choke - 1 per drive || ATV61WD11N4 - line choke - 1 per drive || ATV61HD11N4 - line choke - 1 per drive || ATV71WD11N4 - line choke - 1 per drive || ATV31CU75N4 - motor choke - 1 per drive || variable speed drive ATV630 600 V - three phase - line choke - 30 hp - 1 per drive || variable speed drive ATV320 4 kW 200...240 V - three phase - motor choke - 1 per drive || ATV312HU75M3 - line choke - 1 per drive || ATV61WD15N4 - line choke - 1 per drive || variable speed drive ATV320 15 kW 525...600 V - three phase - line choke - 1 per drive || variable speed drive ATV630 600 V - three phase - line choke - 25 hp - 1 per drive || ATV31CD15N4 - line choke - 1 per drive || ATV71PD11N4Z - line choke - 1 per drive || ATV312HD11N4 - line choke - 1 per drive || variable speed drive ATV320 11 kW 380...500 V - three phase - motor choke - 1 per drive || ATV312HD15S6 - line choke - 1 per drive || variable speed drive ATV320 7.5 kW 200...240 V - three phase - line choke - 1 per drive || ATV61HD18Y - line choke - 1 per drive || variable speed drive ATV630 18.5 kW 500...690 V - three phase - line choke - 1 per drive || ATV32HD15N4 - line choke - 1 per drive || ATV71HU40M3 - line choke - 1 per drive || variable speed drive ATV310 7.5 kW - line choke - 1 per drive || variable speed drive ATV930 600 V - three phase - line choke - 30 hp - 1 per drive || variable speed drive ATV320 4 kW 200...240 V - three phase - line choke - 1 per drive || ATV312HU55M3 - motor choke - 1 per drive || variable speed drive ATV320 7.5 kW 200...240 V - three phase - motor choke - 1 per drive || ATV312HU75M3 - motor choke - 1 per drive || ATV61HU40M3 - line choke - 1 per drive || variable speed drive ATV930 22 kW 500...690 V - three phase - line choke - 1 per drive || ATV32HU75N4 - motor choke - 1 per drive || variable speed drive ATV310 11 kW - motor choke - 1 per drive || LXM32MD85N4 - line choke - 1 per drive || ATV71HD11N4 - line choke - 1 per drive || variable speed drive ATV320 11 kW 525...600 V - three phase - line choke - 1 per drive || ATV71HD22Y - line choke - 1 per drive || ATV31CD11N4 - motor choke - 1 per drive || ATV71HD15N4 - line choke - 1 per drive || variable speed drive ATV630 22 kW 500...690 V - three phase - line choke - 1 per drive || ATV71HU55M3 - line choke - 1 per drive || ATV12HU40M3 - motor choke - 1 per drive || variable speed drive ATV320 11 kW 525...600 V - three phase - motor choke - 1 per drive || ATV61WD15N4C - line choke - 1 per drive
- Electrical Connection
- terminal 16 mm² / AWG 4, 1.2-1.4 N.m
- Line Rated Current
- 31 A
- Range Compatibility
- Lexium 32 || Altivar 312 Solar || Easy Altivar 310 || Altivar 12 || Lexium 62 || Altivar 71 || Altivar Machine ATV340 || Altivar Machine ATV320 || Altivar Process ATV900 || Altivar 31C || Altivar 61 || Lexium 52 || Altivar 32 || Altivar 312 || Altivar Process ATV600 || Easy Altivar 310L
- Device Application
- reduction of current harmonics || reduction of overvoltages at motor terminals