Schneider Electric

XMLB020A2S12

1 / 1
thumbnail

Descrizione

This XMLB electromechanical pressure switch has an adjustable differential for regulation of 2 thresholds and a zinc alloy body with a range scale window. This pressure switch is designed for regulation of pressure between 2 thresholds for air, fresh water and hydraulic oils at temperatures up to 70°C. It is fixed directly on tubage. It provides zinc alloy enclosure for robust performance. 5 million cycles mechanical durability for minimum required maintenance on your pressurized fluid circuits. It complies with CCC, EN/IEC 60947-5-1, CSA C22.2 No.14, LROS, UL 508, EAC, BV.
Country of Origin
CZ
Part Number
XMLB020A2S12
Tariff Code
90322000
EAN
3389110755916
UNSPSC
39122210
Metodi di pagamento:
Migliore offerta da:
DEFornitore Automa.Net di fiducia
Disponibilità:
1 pz.
Disponibile
Aggiornato il: 08-11-2024
Garanzia:
12 mesi
Consegna stimata:
Su richiesta
Condizione:
Nuove eccedenze
Nuove eccedenze - Un articolo nuovo, inutilizzato e non danneggiato senza garanzia del produttore. L'articolo può arrivare senza confezione originale o in una confezione sostitutiva. Se fornita, la scatola potrebbe essere stata aperta.
Processo di Pagamento Sicuro
Politiche di Reso e Rimborso
Politiche di Spedizione
Politiche di Garanzia

Specifications

Contacts Type And Composition
1 C/O
Pressure Sensor Type
electromechanical pressure sensor
Pressure Actuator
diaphragm
Electrical Connection
screw-clamps terminals, 1 x 0.5...2 x 2.5 mm²
Range Of Product
Telemecanique Pressure sensors XM
Line Rated Current
3 A, B300, AC-15 (Ue = 120 V)EN/IEC 60947-5-1 || 1.5 A, B300, AC-15 (Ue = 240 V)EN/IEC 60947-5-1 || 0.1 A, R300, DC-13 (Ue = 250 V)EN/IEC 60947-5-1
Pressure Switch Type Of Operation
regulation between 2 thresholds
Cable Entry
cable gland 7-13 mm
Product Or Component Type
electromechanical pressure sensor
Adjustable Range Of Switching Point On Falling Pressure
0.3-18.4 bar
Materials In Contact With Fluid
brass || nitrile || zinc alloy
Local Display
with
Fluid Connection Type
G 1/4 (female) ISO 228
Pressure Sensor Size
20 bar
Controlled Fluid
air 0-70 °C) || fresh water 0-70 °C) || hydraulic oil 0-70 °C)
Awg Gauge
AWG 20...AWG 14
Scale Type
adjustable differential
Electrical Circuit Type
control circuit
Enclosure Material
zinc alloy
Adjustable Range Of Switching Point On Rising Pressure
1.3-20 bar
Maximum Permissible Accidental Pressure
45 bar
Possible Differential Maximum At High Setting
11 bar
Destruction Pressure
90 bar
Device Short Name
XMLB

Contractual warranty

Warranty
18 months

Complementary

Repeat Accuracy
2 %
Height
113 mm
Terminal Block Type
4 terminals
Short-Circuit Protection
10 A cartridge fuse gG (gl)
Contacts Material
silver contacts
Possible Differential Minimum At High Setting
1.6 bar +/- 0.25 bar)
Auxiliary Contacts Operation
snap action
Net Weight
0.705 kg
[Uimp] Rated Impulse Withstand Voltage
6 kV EN/IEC 60947-1
Maximum Permissible Pressure - Per Cycle
25 bar
Maximum Operating Rate
120 cyc/mn
[Ui] Rated Insulation Voltage
300 V UL 508 || 500 V EN/IEC 60947-1 || 300 V CSA C22.2 No 14
Setting
external
Mechanical Durability
5000000 cycles
Width
35 mm
Depth
75 mm
Maximum Resistance Across Terminals
25 mOhm IEC 255-7 category 3 || 25 mOhm NF C 93-050 method A
Possible Differential Minimum At Low Setting
1 bar +/- 0.25 bar)

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110914EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Environment

Product Certifications
BV || CSA || LROS (Lloyds register of shipping) || UL || EAC || CCC
Ambient Air Temperature For Operation
-25-70 °C
Standards
CE || UL 508 || EN/IEC 60947-5-1 || CSA C22.2 No 14
Vibration Resistance
4 gn 30-500 Hz)IEC 60068-2-6
Shock Resistance
50 gn IEC 60068-2-27
Ip Degree Of Protection
IP66 conforming to EN/IEC 60529
Ambient Air Temperature For Storage
-40-70 °C
Protective Treatment
TC standard version
Operating Position
any position
Electrical Shock Protection Class
class I IEC 1140 || class I IEC 536 || class I NF C 20-030