- Contacts Usage
- standard contacts
- Terminals Description Iso N°1
- (11-12)NC
- Short-Circuit Protection
- 4 A cartridge fuse gG IEC 60947-5-1
- Operating Travel
- 1.5 mm NC changing electrical state) || 2.6 mm NO changing electrical state) || 4.3 mm total travel)
- Contacts Material
- silver alloy (Ag/Ni)
- Positive Opening
- with IEC 60947-5-1 appendix K
- [Ith] Conventional Free Air Thermal Current
- 10 A IEC 60947-5-1
- Net Weight
- 0.064 kg
- [Uimp] Rated Impulse Withstand Voltage
- 4 kV IEC 60947-1
- Cad Overall Height
- 47 mm
- Electrical Durability
- 1000000 cycles, AC-15, 1 A 230 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C || 1000000 cycles, AC-15, 1.5 A 120 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C || 1000000 cycles, AC-15, 3 A 24 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.15 A 110 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.4 A 24 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C
- [Ui] Rated Insulation Voltage
- 250 V 3)IEC 60947-1
- Operating Torque
- 0.05 N.m NO changing electrical state
- [Ie] Rated Operational Current
- 3 A 240 V, AC-15, A300 IEC 60947-5-1 || 6 A 120 V, AC-15, A300 IEC 60947-5-1 || 0.1 A 250 V, DC-13, R300 IEC 60947-5-1 || 0.22 A 125 V, DC-13, R300 IEC 60947-5-1
- Mechanical Durability
- 5000000 cycles
- Electrical Reliability
- λ < 10exp(-6) 5 V, 1 mA in clean environment IEC 60947-5-4 || λ < 10exp(-8) 17 V, 5 mA in clean environment IEC 60947-5-4
- Cad Overall Width
- 30 mm
- Cad Overall Depth
- 37 mm