The Supplementary Protector features a trip characteristic curve D and is designed for installation in applications requiring a 3-pole configuration. With a rated current of 0.5 Amps and a voltage of 480 VAC, this device is UL1077 rated and complies with IEC standards for mini circuit breakers.
Measuring 54mm in width and 70mm in depth, this protector has a pollution degree of 3 and an overvoltage category of 3. The product is rated for a short-circuit breaking capacity of 10 kA at 400 V and 35 kA at 400 V according to IEC 60947-2. The rated insulation voltage is 440 V, and it provides IP20 protection. It supports a connectable conductor cross-section of 0.75 mm² for both solid-core and multi-wired conductors.
For installations in environments with ambient temperatures ranging from -40 °C, this product allows for additional equipment connections and is not designed for flush-mounted installation. It is listed under UL File E116386 in Volume 1, Section 2.