Square D
LC1F115G6
- Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
- Sconti sulla rivendita fino al 40%!
Invia una richiesta di prezzo
1
Metodi di pagamento:
Additional Information
- Part Number
- LC1F115G6
- UPC
- 785901079781
Main
- Commercial Status
- Commercialised
- Range
- TeSys
- Product name
- TeSys F
- Product or component type
- Contactor
- Device short name
- LC1F
- Contactor application
- Motor control
- Contactor application
- Resistive load
- Utilisation category
- AC-1
- Utilisation category
- AC-3
- Poles description
- 3P
- Pole contact composition
- 3 NO
- [Ie] rated operational current
- 115 A ( 200 A (
- Motor power kW
- 30 kW at 220...230 V AC 50/60 Hz
- Motor power kW
- 65 kW at 1000 V AC 50/60 Hz
- Motor power kW
- 80 kW at 660…690 V AC 50/60 Hz
- Motor power kW
- 75 kW at 500 V AC 50/60 Hz
- Motor power kW
- 59 kW at 440 V AC 50/60 Hz
- Motor power kW
- 59 kW at 415 V AC 50/60 Hz
- Motor power kW
- 55 kW at 380...400 V AC 50/60 Hz
- Control circuit type
- AC 60 Hz
- Control circuit voltage
- 120 V AC 60 Hz
- Overvoltage category
- III
- [Ith] conventional free air thermal current
- 200 A at
- Irms rated making capacity
- 1150 A AC conforming to IEC 60947-4-1
- Rated breaking capacity
- 920 A conforming to IEC 60947-4-1
- [Icw] rated short-time withstand current
- 320 A 400 A 520 A 640 A 1100 A
- Associated fuse rating
- 200 A gG at 125 A aM at
- Average impedance
- 0.37 mOhm at 50 Hz - Ith 200 A
- [Ui] rated insulation voltage
- 1500 V conforming to VDE 0110 group C
- [Ui] rated insulation voltage
- 1000 V conforming to IEC 60947-4-1
- Power dissipation per pole
- 5 W AC-3
- Power dissipation per pole
- 15 W AC-1
- Mounting support
- Plate
- Standards
- EN 60947-1
- Standards
- EN 60947-4-1
- Standards
- IEC 60947-1
- Standards
- IEC 60947-4-1
- Standards
- JEM 1038
- Product certifications
- BV
- Product certifications
- CCC
- Product certifications
- CSA
- Product certifications
- DNV
- Product certifications
- GL
- Product certifications
- RINA
- Product certifications
- RMRoS
- Product certifications
- UL
- Product certifications
- LROS
- Connections - terminals
- Control circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: solid - without cable end
- Connections - terminals
- Control circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: solid - without cable end
- Connections - terminals
- Control circuit: screw clamp terminals 2 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - with cable end
- Connections - terminals
- Control circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - with cable end
- Connections - terminals
- Control circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - without cable end
- Connections - terminals
- Control circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - without cable end
- Connections - terminals
- Power circuit: connector 1 cable(s) 0.15 in² (95 mm²)
- Connections - terminals
- Power circuit: lugs-ring terminals 1 cable(s) 0.15 in² (95 mm²)
- Connections - terminals
- Power circuit: bar 2 x ( 20 x 3 mm)
- Tightening torque
- Control circuit: 10.62 lbf.in (1.2 N.m)
- Tightening torque
- Power circuit: 88.5 lbf.in (10 N.m)
- Operating time
- 5...15 ms opening
- Operating time
- 23...35 ms closing
- Mechanical durability
- 10 Mcycles
- Operating rate
- 2400 cyc/h at
Complementary
- Control circuit voltage limits
- 0.35...0.55 Uc at 131 °F (55 °C) drop-out 50/60 Hz
- Control circuit voltage limits
- 0.85...1.1 Uc at 131 °F (55 °C) operational 50/60 Hz
- Inrush power in VA
- 660 VA at 68 °F (20 °C) (cos ϕ 0.3) 60 Hz
- Hold-in power consumption in VA
- 55 VA at 68 °F (20 °C) (cos ϕ 0.3) 60 Hz
- Heat dissipation
- 12...16 W
Environment
- IP degree of protection
- IP2x front face with shrouds (ordered separately) conforming to VDE 0106
- IP degree of protection
- IP2x front face with shrouds (ordered separately) conforming to IEC 60529
- Protective treatment
- TH
- Ambient air temperature for operation
- 23...131 °F (-5...55 °C)
- Ambient air temperature for storage
- -76...176 °F (-60...80 °C)
- Permissible ambient air temperature around the device
- -40...158 °F (-40...70 °C)
- Operating altitude
- 9842.52 ft (3000 m) without derating in temperature
- Mechanical robustness
- Shocks contactor closed 15 Gn for 11 ms
- Mechanical robustness
- Shocks contactor open 9 Gn for 11 ms
- Mechanical robustness
- Vibrations contactor closed 6 Gn, 5...300 Hz
- Mechanical robustness
- Vibrations contactor open 2 Gn, 5...300 Hz
- Height
- 6.38 in (162 mm)
- Width
- 6.43 in (163.3 mm)
- Depth
- 6.73 in (171 mm)
- Product weight
- 7.56 lb(US) (3.43 kg)
Ordering and Shipping Details
- Category
- 22336 - CTR,F-LINE,AC,OPEN,NONREV
- Discount Schedule
- I12
- GTIN
- 00785901079781
- Nbr. of units in pkg.
- 1
- Product availability
- Stock - Normally stocked in distribution facility
- Returnability
- Y
- Country of origin
- CZ
Offer Sustainability
- Sustainable offer status
- Green Premium product
- RoHS (date code: YYWW)
- Compliant - since 0843 -
- RoHS (date code: YYWW)
- Schneider Electric declaration of conformity
- REACh
- Reference not containing SVHC above the threshold
- Product environmental profile
- Available
- Product environmental profile
- Download Product Environmental Profile
- Product end of life instructions
- Available
- Product end of life instructions
- Download End of life manual
Contractual Warranty
- Warranty period
- 18 months
Documenti
Data Sheet
ScaricareAltre categorie
AttuatoriBlocchiCavi, tubi e manichetteCompressoriControlloGiunzioni e raccordiCilindri e PistoniElettronicaFiltriHVACPC industriali e HMIsIlluminazioneTecnica lineareMotoriAlimentatoreTrasmissione di potenzaPompe e ValvoleEnergia rinnovabileRoboticaGuarnizioni, Anelli e ConnettoriSensori e dispositivi di misuraStrumenti e AccessoriCNCAltro