Wago
2102-5303
1 / 2
- Part Number
- 2102-5303
- Tariff Code
- 85369010000
- UPC
- 4055144019117
- ETIM
- Group Code : EG000012
- Group Description : Terminal blocks
- Class Description : Feed-through terminal block
- Class Code : EC000897
- Version : 7
- Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
- Sconti sulla rivendita fino al 40%!
Invia una richiesta di prezzo
1
Metodi di pagamento:
Ratings Per Iec/En
- Ratings per
- IEC/EN 60947-7-1
- Nominal voltage (III/3)
- 800 V
- Rated impulse voltage (III/3)
- 8 kV
- Rated current
- 24 A
- Current at conductor cross-section (max.) mm²
- 30 A
- Legend (ratings)
- (III / 3) ≙ Overvoltage category III / Pollution degree 3
Environmental Requirements
- Processing temperature
- -35 … +85 °C
- Continuous operating temperature
- -60 … +105 °C
Physical Data
- Width
- 5.2 mm / 0.205 inches
- Height
- 72.2 mm / 2.843 inches
- Depth from upper-edge of DIN-rail
- 32.9 mm / 1.295 inches
Material Data
- Note (material data)
- <a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
- Color
- Red
- Material group
- I
- Insulation material
- Polyamide (PA66)
- Flammability class per UL94
- V0
- Fire load
- 0.186 MJ
- Weight
- 8.092 g
Mechanical Data
- Mounting type
- DIN-35 rail
- Marking level
- Center/side marking
Connection 2
- Actuation type 2
- Push-button
Specifications
- Product Group Code
- 0035
Commercial Data
- Packaging type
- Box
- Country of origin
- PL
- GTIN
- 4055144019117
- Customs tariff number
- 85369010000
Ex Information
- Reference hazardous areas
- See “Downloads – Documentation – Additional Information: Technical Section; Technical Explications”
- Ratings per
- ATEX: PTB 18 ATEX 1010 U / IECEx: PTB 18.0001U (Ex eb IIC Gb)
- Rated voltage EN (Ex e II)
- 550 V
- Rated current (Ex e II)
- 20.5 A
- Rated current (Ex e II) with jumper
- 20 A
Ratings Per Csa
- Approvals per
- CSA 22.2 No 158
- Rated voltage CSA (Use Group B)
- 600 V
- Rated current CSA (Use Group B)
- 20 A
- Rated voltage CSA (Use Group C)
- 600 V
- Rated current CSA (Use Group C)
- 20 A
Power Loss
- Power loss, per pole (potential)
- 0.7661 W
- Rated current IN for specified power loss
- 24 A
- Resistance value for specified, current-dependent power loss
- 0.00133 Ω
Connection 1
- Connection technology
- Push-in CAGE CLAMP®
- Actuation type
- Lever
- Connectable conductor materials
- Copper
- Nominal cross-section
- 2.5 mm²
- Solid conductor
- 0.25 … 4 mm² / 22 … 12 AWG
- Solid conductor; push-in termination
- 0.75 … 4 mm² / 18 … 12 AWG
- Fine-stranded conductor
- 0.25 … 4 mm² / 22 … 12 AWG
- Fine-stranded conductor; with insulated ferrule
- 0.25 … 2.5 mm² / 22 … 14 AWG
- Fine-stranded conductor; with ferrule; push-in termination
- 1 … 2.5 mm² / 18 … 14 AWG
- Note (conductor cross-section)
- Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
- Strip length
- 10 … 12 mm / 0.39 … 0.47 inches
- Wiring direction
- Front-entry wiring
Ratings Per Ul 1059
- Approvals per
- UL 1059
- Rated voltage UL (Use Group B)
- 600 V
- Rated current UL (Use Group B)
- 20 A
- Rated voltage UL (Use Group C)
- 600 V
- Rated current UL (Use Group C)
- 20 A