- Number of analog outputs
- 4
- Total number of channels (module)
- 4
- Signal type
- Current
- Signal type (current)
- 4 … 20 mADC
- Actuator connection
- 4 x (2-wire)
- Resolution [bit]
- 12 bits
- Data width
- 4 x 16-bit data; 4 x 8-bit control/status (optional)
- Load impedance
- Either 0 … 300 Ω or 300 … 600 Ω (same resistance for all load impedances)
- Conversion time (typ.)
- 10 ms
- Output error, reference temperature
- 25 °C
- Output error, deviation (max.) of the upper-range value
- 0.1 %
- Temperature error (max.) of the output range value
- 0.01 %/K
- Recovery time (typ.)
- 100 ms
- Supply voltage (system)
- 5 VDC; via data contacts
- Current consumption (5 V system supply)
- 60 mA
- Supply voltage (field)
- 24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission via spring contact)
- Isolation
- 500 V system/field
- Indicators
- LED (A) green: Function; LED (B) red: Error
- Number of incoming power jumper contacts
- 2
- Number of outgoing power jumper contacts
- 2