Weidmuller

2580230000

PRO INSTA 60W 24V 2.5A
2580230000
2580230000
  • Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
  • Sconti sulla rivendita fino al 40%!
Registrati
Invia una richiesta di prezzo
1
Metodi di pagamento:
Un totale di 154 Parts In-Stock da 17 Distributors

Additional Information

Part Number
2580230000

General Data

Degree of efficiency
89%
Housing version
Plastic, protective insulation
MTBF
> 750.000 h nach IEC 61709 (SN29500)
Mounting position, installation notice
Horizontal on DIN rail TS 35, top and bottom 50 mm clearance for free air flow, 10 mm clearance to neighbouring active subassemblies with full load, 5 mm with passive neighbouring subassemblies, direct row mounting with 90% rated load
Operating temperature
-25 °C...70 °C
Power loss, idling
0.44 W
Power loss, nominal load
6.6 W
Protection against reverse voltages from the load
30…35 V DC
Protection degree
IP20

Signalling

LED green
Operating voltage OK

Connection Data (Input)

Conductor cross-section, AWG/kcmil , max.
12
Conductor cross-section, AWG/kcmil , min.
24
Conductor cross-section, flexible , min.
0.25 mm²
Conductor cross-section, rigid , max.
2.5 mm²
Conductor cross-section, rigid , min.
0.25 mm²
Connection system
PUSH IN
Number of terminals
2 (L,N)
Wire connection cross section, flexible (input), max.
2.5 mm²

Approvals

Approvals
CCSAUS, TUEV
ROHS
Conform

Dimensions And Weights

Width
72 mm
Width (inches)
2.835 inch
Height
90 mm
Height (inches)
3.543 inch
Depth
60 mm
Depth (inches)
2.362 inch
Net weight
258 g

Electrical Safety (Applied Standards)

Electrical machine equipment
Acc. to EN60204
For use with electronic equipment
Acc. to EN50178 / VDE0160
Protection against dangerous shock currents
Acc. to VDE0106-101
Protective separation / protection against electrical shock
VDE0100-410 / acc. to DIN57100-410
Safety transformers for switch-mode power supplies
According to EN 61558-2-16

Emc / Shock / Vibration

Limiting of mains voltage harmonic currents
EN 61000-4-2 (ESD)|EN 61000-4-3 and EN 61000-4-8 (fields)|EN 61000-4-4 (burst)|EN 61000-4-5 (surge)|EN 61000-4-6 (conducted)|EN 61000-4-11 (dips), EN 61000-4-11 (Dips)
Noise emission in accordance with EN55032
Class B
Vibration resistance IEC 60068-2-6
2.3 g
Interference immunity test acc. to
EN 61000-4-2 (ESD)|EN 61000-4-3 and EN 61000-4-8 (fields)|EN 61000-4-4 (burst)|EN 61000-4-5 (surge)|EN 61000-4-6 (conducted)|EN 61000-4-11 (dips), EN 61000-4-11 (Dips)
Shock resistance IEC 60068-2-27
15 g In all directions

Input

AC current consumption
0.7 A @ 230 V AC / 1.5 A @ 100 V AC
AC input voltage range
85...264 V AC (derating at 100 V AC)
Connection system
PUSH IN
DC current consumption
0.25 A @ 370 V DC / 0.8 A @ 120 V DC
DC input voltage range
95…370 V DC
Frequency range AC
45…65 Hz
Input fuse (internal)
Yes
Inrush current
max. 40 A
Rated input voltage
100 - 240 V AC / 120 - 340 V DC
Recommended back-up fuse
2 A / DI, safety fuse6 A, Char. B, circuit breaker2...4 A, Char. C circuit breaker

Classifications

ETIM 6.0
EC002540
ETIM 7.0
EC002540
EClass 9.0
27-04-07-01
EClass 9.1
27-04-07-01
EClass 10.0
27-04-07-01

Output

Capacitive load
unrestricted
Connection system
PUSH IN
Continous output current @ U
2.5 A @ 55 °C, 1.56 A @ 70 °C
Nominal output current for U
2.5 A @ 55 °C
Output voltage
22...28 V (adjustable via potentiometer on front)
Ramp-up time
≤ 100 ms
Rated output voltage
24 V DC ± 1 %
Residual ripple, breaking spikes
< 50 mVss @ UNenn, Full Load

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Insulation Coordination

Insulation voltage input / earth
3.5 kV
Insulation voltage output / earth
0.5 kV
Insulation voltage, input/output
4 kV
Pollution severity
2
Protection class
II

Connection Data (Output)

Conductor cross-section, AWG/kcmil , max.
12
Conductor cross-section, AWG/kcmil , min.
24
Conductor cross-section, flexible , max.
2.5 mm²
Conductor cross-section, flexible , min.
0.25 mm²
Conductor cross-section, rigid , max.
2.5 mm²
Conductor cross-section, rigid , min.
0.25 mm²
Connection system
PUSH IN
Number of terminals
4 (++ / --)

Temperatures

Operating temperature, max.
70 °C
Operating temperature, min.
-25 °C
Storage temperature, max.
85 °C
Storage temperature, min.
-40 °C
Operating temperature
-25 °C...70 °C
Storage temperature
-40 °C...85 °C