Weidmuller
7760054118
ACT20P-CI1-CO-OLP
- Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
- Sconti sulla rivendita fino al 40%!
€179.00
1
Metodi di pagamento:
Un totale di 5 Parts In-Stock da 9 Distributors
Condizioni del prodotto:
Offerta con tempi di consegna del produttore
Spedizione in:Su richiesta
Miglior prezzo:
€105.20
Additional Information
- Part Number
- 7760054118
General Data
- Accuracy
- < 0.1 % of end value
- Configuration
- none
- Galvanic isolation
- 2-way isolator
- Rail
- TS 35
- Step response time
- ≤ 1 ms
- Temperature coefficient
- ≤ 100 ppm/K
- Voltage supply
- via output current loop, min. 12 V DC/ max. 30 V DC
Approvals
- Approvals
- EAC
Dimensions And Weights
- Width
- 12.5 mm
- Width (inches)
- 0.492 inch
- Height
- 117.2 mm
- Height (inches)
- 4.614 inch
- Depth
- 114 mm
- Depth (inches)
- 4.488 inch
- Weight
- 126 g
- Net weight
- 100 g
Connection Data
- Type of connection
- Screw connection
- Tightening torque, min.
- 0.4 Nm
- Tightening torque, max.
- 0.6 Nm
- Clamping range, rated connection
- 2.5 mm²
- Clamping range, min.
- 0.5 mm²
- Clamping range, max.
- 2.5 mm²
- Wire connection cross section AWG, min.
- AWG 26
- Wire connection cross section AWG, max.
- AWG 12
Input
- Number of inputs
- 1
- Sensor
- Current source
- Input current
- 0...20 mA
- Voltage drop, current input
- < 3 V
Classifications
- ETIM 6.0
- EC002475
- ETIM 7.0
- EC002475
- EClass 9.0
- 27-21-01-23
- EClass 9.1
- 27-21-01-23
- EClass 10.0
- 27-21-01-23
Output
- Number of outputs
- 1
- Output current
- 4...20 mA, loop-powered
- Load impedance current
- ≤ 600 Ω
Product Information
- Product information
- The ACT20P-CIX-CO-OLP-S single-channel fixed passive isolator isolates analogue standard current source signals. An analogue input current signal is converted linear and galvanic isolated into an analogue output current signal. The device is powered via the output current loop. Features 2-way galvanic isolation between input and output.
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
Insulation Coordination
- EMC standards
- EN 61010-1:2011, UL 61010-1, IEC61000-6-2, IEC 61000-6-4
- Galvanic isolation
- 2-way isolator
- Impulse withstand voltage
- 4 kV (1.2/50 µs)
- Insulation voltage
- 2 kV inputs / outputs
- Pollution severity
- 2
- Rated voltage
- 300 V
- Surge voltage category
- III
Temperatures
- Humidity
- 5...95 %, no condensation
- Operating temperature, max.
- 60 °C
- Operating temperature, min.
- -20 °C
- Operating temperature
- -20 °C...60 °C
- Ambient temperature
- -20 °C...+60 °C
Altre categorie
AttuatoriBlocchiCavi, tubi e manichetteCompressoriControlloGiunzioni e raccordiCilindri e PistoniElettronicaFiltriHVACPC industriali e HMIsIlluminazioneTecnica lineareMotoriAlimentatoreTrasmissione di potenzaPompe e ValvoleEnergia rinnovabileRoboticaGuarnizioni, Anelli e ConnettoriSensori e dispositivi di misuraStrumenti e AccessoriCNCAltro