Schneider Electric
LC1D80AEHE
1 / 1
Opis
Końcówka Serii
TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 40HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Equipped with an electronic coil, wide band voltage 48-130V, AC/DC compatible, low consumption. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.- Country of Origin
- FR
- Part Number
- LC1D80AEHE
- Tariff Code
- 85364900
- EAN
- 3606481312334
- UNSPSC
- 39121529
- Termin płatności do 90 dni od 500+ dostawców.
- Rabaty na odsprzedaż do 40%!
Wyślij zapytanie o cenę
1
Metody płatności:
Environment
- Product Certifications
- CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
- Height
- 122 mm
- Standards
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
- Climatic Withstand
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Net Weight
- 1.002 kg
- Flame Retardance
- V1 conforming to UL 94
- Ip Degree Of Protection
- IP20 front face IEC 60529
- Mechanical Robustness
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
- Operating Altitude
- 0...9842.52 ft (0...3000 m)
- Fire Resistance
- 850 °C IEC 60695-2-1
- Width
- 55 mm
- Depth
- 120 mm
- Permissible Ambient Air Temperature Around The Device
- -40-60 °C || 60-70 °C with derating
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1607010EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI1607010EN
- Eu Rohs Directive
- Compliant with Exemptions
- Halogen Content Performance
- Halogen free plastic parts & cables product
Complementary
- Non-Overlap Time
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Minimum Switching Current
- 5 mA for signalling circuit
- Power Dissipation Per Pole
- 9.6 W AC-1 || 6.3 W AC-3 || 6.3 W AC-3e
- Average Impedance
- 1.5 mOhm - Ith 80 A 50 Hz for power circuit
- Auxiliary Contact Composition
- 1 NO + 1 NC
- [Ith] Conventional Free Air Thermal Current
- 80 A (at 60 °C) for power circuit || 10 A (at 60 °C) for signalling circuit
- Control Circuit Voltage Limits
- <= 0.1 Uc -40-70 °C drop-out AC/DC || 0.85...1.1 Uc -40-60 °C operational AC/DC || 1...1.1 Uc 60-70 °C operational AC/DC
- Mounting Support
- plate || rail
- Control Circuit Type
- AC/DC 50/60 Hz AC/DC electronic
- Safety Reliability Level
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Pollution Degree
- 3
- Hold-In Power Consumption In W
- 0.9-0.9 W 20 °C
- Insulation Resistance
- > 10 MOhm for signalling circuit
- Rated Breaking Capacity
- 1000 A at 440 V for power circuit conforming to IEC 60947
- Irms Rated Making Capacity
- 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V AC for power circuit conforming to IEC 60947
- Associated Fuse Rating
- 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit || 10 A gG for signalling circuit conforming to IEC 60947-5-1
- Inrush Power In Va
- 23-23 VA 50/60 Hz (at 20 °C)
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947
- Pole Contact Composition
- 3 NO
- Connections - Terminals
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible without cable end || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible with cable end || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: solid || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible without cable end || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible with cable end || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: solid
- Coil Technology
- built-in bidirectional peak limiting
- Operating Time
- 55...65 ms closing || 20...80 ms opening
- Minimum Switching Voltage
- 17 V for signalling circuit
- Maximum Operating Rate
- 3600 cyc/h 60 °C
- Signalling Circuit Frequency
- 25...400 Hz
- Tightening Torque
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm || power circuit 5 N.m pozidriv No 2 M4 || control circuit 1.7 N.m pozidriv No 2 M3.5
- Electrical Durability
- 1 Mcycles 66 A AC-3 <= 440 V || 0.5 Mcycles 80 A AC-1 <= 440 V || 1 Mcycles 66 A AC-3e <= 440 V
- Mechanical Durability
- 6 Mcycles
- Inrush Power In W
- 19-19 W 20 °C)
- Auxiliary Contacts Type
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Compatibility Code
- LC1D
- Hold-In Power Consumption In Va
- 1.4-1.4 VA 50/60 Hz (at 20 °C)
- Overvoltage Category
- III
- Maximum Horse Power Rating
- 5 hp at 115 V AC 60 Hz for 1 phase motors || 10 hp at 230/240 V AC 60 Hz for 1 phase motors || 20 hp at 200/208 V AC 60 Hz for 3 phase motors || 20 hp at 230/240 V AC 60 Hz for 3 phase motors || 40 hp at 460/480 V AC 60 Hz for 3 phase motors || 50 hp at 575/600 V AC 60 Hz for 3 phase motors
- Motor Power Kw
- 22 kW at 220...230 V AC 50/60 Hz (AC-3) || 37 kW at 380...400 V AC 50/60 Hz (AC-3) || 37 kW at 415 V AC 50/60 Hz (AC-3) || 37 kW at 440 V AC 50/60 Hz (AC-3) || 37 kW at 500 V AC 50/60 Hz (AC-3) || 37 kW at 660...690 V AC 50/60 Hz (AC-3) || 22 kW at 220...230 V AC 50/60 Hz (AC-3e) || 37 kW at 380...400 V AC 50/60 Hz (AC-3e) || 37 kW at 415 V AC 50/60 Hz (AC-3e) || 37 kW at 440 V AC 50/60 Hz (AC-3e) || 37 kW at 500 V AC 50/60 Hz (AC-3e) || 37 kW at 660...690 V AC 50/60 Hz (AC-3e)
- [Ui] Rated Insulation Voltage
- power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1
- [Icw] Rated Short-Time Withstand Current
- 110 A 40 °C - 10 min for power circuit || 260 A 40 °C - 1 min for power circuit || 640 A 40 °C - 10 s for power circuit || 900 A 40 °C - 1 s for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
- Heat Dissipation
- 0.9-0.9 W at 50/60 Hz
- Protective Cover
- with
Specifications
- [Uc] Control Circuit Voltage
- 48...130 V AC 50/60 Hz || 48...130 V DC
- [Ue] Rated Operational Voltage
- power circuit <= 690 V AC 25...400 Hz
- Range Of Product
- TeSys Deca
- Contactor Application
- motor control || resistive load
- Product Or Component Type
- contactor
- Range
- TeSys || TeSys Deca
- Utilisation Category
- AC-3 || AC-1 || AC-3e
- [Ie] Rated Operational Current
- 80 A (at <60 °C) at <= 440 V AC-1 for power circuit || 66 A (at <60 °C) at <= 440 V AC-3 for power circuit || 66 A (at <60 °C) at <= 440 V AC-3e for power circuit
- Poles Description
- 3P
- Device Short Name
- LC1D
Modele CAD
traceparts
PobierzInne kategorie
SiłownikiBlokiKable, rury i wężeSprężarkiSterowanieŁączniki i osprzętCylindry i tłokiElektronikaFiltryHVACKomputery przemysłowe i interfejsy HMIOświetlenieTechnika liniowaSilnikiZasilaniePrzeniesienie napęduPompy i zaworyEnergia odnawialnaRobotykaUszczelki, pierścienie i złączaCzujniki i urządzenia pomiaroweNarzędzia i akcesoriaCNCInne