1 / 2
thumbnail
thumbnail

Opis

Końcówka Serii
LADN04 is a Schneider Electric add-on auxiliary contact block for TeSys D and TeSys F contactors. Front mounting block, it provides 4NC instantaneous contacts rated up to 10A 690V AC. It can be used in safety applications. LADN04 is a Schneider Electric add-on auxiliary contact block for TeSys D and TeSys F contactors. It provides 4NC instantaneous contacts rated up to 10A 690V AC. It can be used in safety applications thanks to its NC certified mirror contacts. Easy to mount on front by clip-on, it procures high reliability and durability. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Add-on block with 4NC mechanically linked auxiliary contacts, with instantaneous operation. Suitable to be included in the control of safety systems thanks to its NC certified mirror contacts. High electrical durability , several millions of operating cycles in AC-14/AC-15/DC-13 according conditions. Mounting by clip-on on front of all TeSys D and TeSys F contactors.
Country of Origin
FR
Part Number
LADN04
Tariff Code
85365080
EAN
3389110383904
UNSPSC
39121522
€8.47
net
€9.42
Wysyłka od:
€25.00
1
Metody płatności:
Najlepsza oferta od:
ITZaufany dostawca Automa.Net
Dostępność:
1 szt.
W magazynie
Zaktualizowano: 19-11-2024
Gwarancja:
12 miesięcy
Szacowany czas dostawy:
21-25 listopada do Wielka Brytania
Stan produktu:
Fabrycznie Nowe, Zapieczętowane
Fabrycznie Nowe, Zapieczętowane - Nowy, nieużywany, nieotwarty, nieuszkodzony przedmiot w oryginalnym opakowaniu zapieczętowanym przez producenta.
Informacje o wysyłce
Bezpieczny proces płatności
Zasady zwrotów i reklamacji
Zasady wysyłki
Gwarancja

Environment

Ambient Air Temperature For Operation
-5-60 °C
Ip Degree Of Protection
IP20 conforming to IEC 60529
Ambient Air Temperature For Storage
-60-80 °C
Environmental Characteristic
normal environment
Protective Treatment
TH IEC 60068
Operating Altitude
9842.52 ft (3000 m)

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110807EN_V3
Sustainable Offer Status
Green Premium product
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
N/A
Eu Rohs Directive
Compliant

Complementary

Non-Overlap Time
1.5 ms on de-energisation no overlap between NC and NO contact || 1.5 ms on energisation no overlap between NC and NO contact
Permissible Short-Time Rating
100 A 1 s || 120 A 500 ms || 140 A 100 ms
Minimum Switching Current
5 mA
Height
48 mm
Protection Type
gG fuse 10 A
Insulation Resistance
> 10 MOhm
Irms Rated Making Capacity
140 A AC conforming to IEC 60947-5-1 || 250 A DC conforming to IEC 60947-5-1
Net Weight
0.05 kg
Connections - Terminals
screw clamp terminals 1 1-4 mm²flexible with cable end || screw clamp terminals 1 1-4 mm²flexible without cable end || screw clamp terminals 2 1-2.5 mm²flexible with cable end || screw clamp terminals 2 1-4 mm²flexible without cable end || screw clamp terminals 1 1-4 mm²rigid without cable end || screw clamp terminals 2 1-4 mm²rigid without cable end
Minimum Switching Voltage
17 V
Tightening Torque
1.7 N.m flat Ø 6 mm || 1.7 N.m Philips No 2 || 1.7 N.m pozidriv No 2
Mechanical Durability
30 Mcycles
Color
dark grey
Width
44 mm
Depth
42 mm

Specifications

Product Certifications
CB || UL || CSA || CCC || EAC || UKCA
[Ith] Conventional Free Air Thermal Current
10 A (at 60 °C)
Standards
EN/IEC 60947-5-1 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.5
[Ue] Rated Operational Voltage
690 V AC 25...400 Hz
Range Compatibility
TeSys D LC1D || TeSys D CAD || TeSys F LC1F || TeSys F CR1F || TeSys Deca CAD || TeSys Deca LC1D
Product Or Component Type
auxiliary contact block
Product Name
TeSys Deca
Range
TeSys || TeSys Deca
Mounting Location
front
Pole Contact Composition
4 NC
[Ui] Rated Insulation Voltage
690 V IEC 60947-5-1 || 600 V UL || 600 V CSA
[Ie] Rated Operational Current
6 A at 120 V AC-15 || 1.04 A at 690 V AC-15 || 0.55 A at 125 V DC-13 || 0.1 A at 600 V DC-13
Auxiliary Contacts Operation
instantaneous
Device Short Name
LADN

Modele CAD

traceparts
traceparts
Pobierz