1 / 1
thumbnail

Opis

This Compact NSX160H is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 70kA rms at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds a 80A rating thermal-magnetic trip unit (TMD). TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection. This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. Compact NSX160H is part of Schneider Electric EcoStruxure Power architecture.
Country of Origin
PL
Part Number
LV430673
Tariff Code
85362090
EAN
3606480011580
UNSPSC
39121633
Metody płatności:
Najlepsza oferta od:
DEZaufany dostawca Automa.Net
Dostępność:
1 szt.
W magazynie
Zaktualizowano: 08-11-2024
Gwarancja:
12 miesięcy
Szacowany czas dostawy:
Na zapytanie
Stan produktu:
Nowy, Rynek wtórny
Nowy, Rynek wtórny - Nowy, nieużywany, nieuszkodzony przedmiot bez gwarancji producenta. Przedmiot może być dostarczony bez oryginalnego opakowania lub w zastępczym opakowaniu. Jeśli dostarczono, pudełko mogło zostać otwarte.
Bezpieczny proces płatności
Zasady zwrotu i refundacji
Zasady wysyłki
Gwarancja

Specifications

Network Frequency
50/60 Hz
Line Rated Current
80 A 40 °C
Trip Unit Name
TM-D
Range Of Product
ComPact NSX100...250
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz
Trip Unit Protection Functions
LI
Network Type
AC
Protected Poles Description
3t
Product Or Component Type
circuit breaker
Product Name
ComPact NSX
Range
ComPact
Control Type
toggle
Utilisation Category
category A
Mounting Mode
fixed
Breaking Capacity
10 kA 600 V AC 50/60 Hz UL 508 || 85 kA 240 V AC 50/60 Hz UL 508 || 65 kA 480 V AC 50/60 Hz UL 508 || 10 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 65 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 70 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2
Suitability For Isolation
yes EN/IEC 60947-2
Poles Description
3P
Breaking Capacity Code
H 70 kA 415 V AC
Device Application
distribution
Device Short Name
NSXm 160H
Trip Unit Technology
thermal-magnetic

Contractual warranty

Warranty
18 months

Complementary

[Ics] Rated Service Breaking Capacity
10 kA 660/690 V AC 50/60 Hz IEC 60947-2 || 100 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 525 V AC 50/60 Hz IEC 60947-2 || 50 kA 500 V AC 50/60 Hz IEC 60947-2 || 65 kA 440 V AC 50/60 Hz IEC 60947-2 || 70 kA 380/415 V AC 50/60 Hz IEC 60947-2
Height
161 mm
Earth-Leakage Protection
without
Mounting Support
backplate
Downside Connection
front
Number Of Slots
5
Protection Type
L : for overload protection (thermal) || I : for short-circuit protection (magnetic)
Long Time Delay Adjustment Type
fixed
Net Weight
2.2 kg
[Tr] Long-Time Delay Adjustment Range
120-400 s 1.5 x In || 15-15 s 6 x Ir
Electrical Durability
7500 cycles 690 V In || 15000 cycles 690 V In/2 || 20000 cycles 440 V In || 40000 cycles 440 V In/2
Short-Time Delay Adjustment Type
fixed
Long Time Pick-Up Adjustment Type Ir
adjustable
Long Time Pick-Up Adjustment Range
0.7...1 x In
Upside Connection
front
[Ui] Rated Insulation Voltage
800 V AC 50/60 Hz
Trip Unit Rating
80-80 A 40 °C
Mechanical Durability
40000 cycles
[Isd] Short-Time Pick-Up Adjustment Range
640 A
Connection Pitch
35 mm
[Uimp] Rated Impulse Withstand Voltage
8 kV
Width
105 mm
Depth
86 mm
Short-Time Pick-Up Adjustment Type Isd
fixed

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP120606EN
Sustainable Offer Status
Green Premium product
California Proposition 65
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI120604EN
Eu Rohs Directive
Compliant

Environment

Product Certifications
CCC || EAC || Marine
Ik Degree Of Protection
IK07 IEC 62262
Ambient Air Temperature For Operation
-25-70 °C
Standards
EN/IEC 60947
Ip Degree Of Protection
IP40 conforming to IEC 60529
Electrical Shock Protection Class
class II
Pollution Degree
3 IEC 60664-1
Ambient Air Temperature For Storage
-50-85 °C
Relative Humidity
0-95 %
Operating Altitude
0...6561.68 ft (0...2000 m) without derating || 2000 m...5000 m with derating
Overvoltage Category
class II

Modele CAD

traceparts
traceparts
Pobierz