Circuit breaker, ComPact NSX400HB2, 100kA/690VAC, MicroLogic 6.3E trip unit 400A, 4 poles 4d
LV433649
  • Termin płatności do 90 dni od 500+ dostawców.
  • Rabaty na odsprzedaż do 40%!
Zarejestruj się
Wyślij zapytanie o cenę
1
Metody płatności:
Oferta z czasem realizacji przez producenta
Wysyłka:1 - 2 Dni robocze
Najlepsza cena:
€3,110.78

Additional Information

Part Number
LV433649
UNSPSC
39121601
Country of Origin
FR

Specifications

Network Frequency
50/60 Hz
Line Rated Current
400 A 40 °C
Trip Unit Name
Micrologic 6.3 E
Range Of Product
ComPact NSX400...630
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz
Trip Unit Protection Functions
LSIG
Network Type
AC
Protected Poles Description
3t + OSN || 3t + N/2 || 3t || 4t
Product Or Component Type
circuit breaker
Product Name
ComPact NSX
Range
ComPact
Control Type
toggle
Utilisation Category
category A
Mounting Mode
fixed
Breaking Capacity
100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
Suitability For Isolation
yes EN/IEC 60947-2
Poles Description
4P
Breaking Capacity Code
HB2 100 kA 690 V AC
Neutral Position
left
Device Application
distribution
Device Short Name
NSX400HB2
Trip Unit Technology
electronic

Contractual warranty

Warranty
18 months

Complementary

[Tg] Ground-Fault Time Delay Adjustment Range
0-0.4 s I²t=off || 0.1-0.4 s I²t=on
[Ics] Rated Service Breaking Capacity
100 kA 500 V AC 50/60 Hz IEC 60947-2 || 100 kA 525 V AC 50/60 Hz IEC 60947-2 || 100 kA 660/690 V AC 50/60 Hz IEC 60947-2
Height
255 mm
[Ig] Ground-Fault Pick-Up Adjustment Range
0.2...1 x In || Ig enable on/off
Thermal Memory
20 minutes before and after tripping
Earth-Leakage Protection
without
Ground-Fault Time Delay Adjustment Type -Tg
adjustable 5 settings
Mounting Support
backplate
Ground-Fault Pick-Up Adjustment Type
adjustable 9 settings
Instantaneous Pick-Up Adjustment Range
1.5...12 x In
Type Of Measurement
energy meter
Downside Connection
front
Number Of Slots
6
Communication Of Data
time-stamped histories and event tables || maximeters/minimeters || instantaneous and demand values || demand current and power || power quality || protection and alarm settings || maintenance indicators || energy metering
Protection Type
L : for overload protection (long time) || S : for short time short-circuit protection || I : for instantaneous short-circuit protection || G : for ground fault protection
Long Time Delay Adjustment Type
adjustable
Instantaneous Pick-Up Adjustment Type Ii
adjustable
Zone Selective Interlocking Zsi
with
Net Weight
7.9 kg
[Tr] Long-Time Delay Adjustment Range
15-400 s 1.5 x Ir || 0.35-11 s 7.2 x Ir || 0.5-16 s 6 x Ir
Electrical Durability
3000 cycles 690 V In || 6000 cycles 690 V In/2 || 6000 cycles 440 V In || 12000 cycles 440 V In/2
Short-Time Delay Adjustment Type
adjustable 5 settings
Neutral Protection Setting
0.5 x Ir 3t + N/2) || 1 x Ir 4t) || 1.6 x Ir 3t + OSN) || no protection 3t)
Long Time Pick-Up Adjustment Type Ir
adjustable 9 settings
Long Time Pick-Up Adjustment Range
160...400 A
Upside Connection
front
[Tsd] Short-Time Delay Adjustment Range
0-0.4 s
[Ui] Rated Insulation Voltage
800 V AC 50/60 Hz
Trip Unit Rating
400-400 A 40 °C
Local Signalling
for ready to operate flashing LED (green) || for overload LED 105 % Ir (red) || for overload LED 90 % Ir (orange)
Mechanical Durability
15000 cycles
[Isd] Short-Time Pick-Up Adjustment Range
1.5...12 x In
Connection Pitch
45 mm
[Uimp] Rated Impulse Withstand Voltage
8 kV
Width
185 mm
Display Type
LCD display
Depth
110 mm
Short-Time Pick-Up Adjustment Type Isd
adjustable

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP120606EN
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI120604EN
Eu Rohs Directive
Compliant

Environment

Product Certifications
EAC || Marine || CCC
Ik Degree Of Protection
IK07 IEC 62262
Ambient Air Temperature For Operation
-25-70 °C
Standards
EN/IEC 60947
Ip Degree Of Protection
IP40 conforming to IEC 60529
Electrical Shock Protection Class
class II
Pollution Degree
3 IEC 60664-1
Ambient Air Temperature For Storage
-40-85 °C
Relative Humidity
0-95 %
Operating Altitude
0...6561.68 ft (0...2000 m) without derating || 2000 m...5000 m with derating
Overvoltage Category
class II

Modele CAD

Części śladowe
Części śladowe
Pobierz