- Network Frequency
- 47...440 Hz
- Coordination Type
- type 1 || type 2
- [Uc] Control Circuit Voltage
- 4...32 V DC
- Height
- 93.2 mm
- Connections - Terminals
- screw terminals, clamping connection capacity:1...4 mm², AWG 18...AWG 12 for input || screw terminals, clamping connection capacity:1...6 mm², AWG 18...AWG 10 for output
- Output Voltage
- 48...600 V AC
- Tightening Torque
- 1.5...1.7 N.m for control input || 13...15 lb.in for control input || 1.5...1.7 N.m for load output || 13...15 lb.in for load output
- Insulation Resistance
- 1000 MOhm at 500 V DC
- Maximum I²T For Fusing
- 8320 A².s for 10 ms || 7593 A².s for 8.33 ms
- Maximum Voltage Drop
- <1.15 V on-state
- Dielectric Strength
- 4 kV AC for input/output circuit || 4 kV AC for input or output to case
- Response Time
- 0.5 cycle (turn-on) || 0.5 cycle (turn-off)
- Load Current
- 0.15-35 A
- Motor Power Kw
- 1.5 kW/2 hp at 120 V AC || 3.73 kW/5 hp at 240 V AC || 7.46 kW/10 hp at 480 V AC
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV for input/output circuit || 6 kV for input or output to case
- Net Weight
- 0.298 kg
- Minimum Switching Voltage
- 4 V DC turn-on
- Maximum Leakage Current
- 1 mA off-state
- Device Presentation
- complete product
- Electromagnetic Compatibility
- electrostatic discharge 6 kV criteria A contact discharge conforming to IEC 61000-4-2 || electrostatic discharge 8 kV criteria A air discharge conforming to IEC 61000-4-2 || conducted RF disturbances 10 V, 0.15...80 MHz criteria A level 3 conforming to IEC 61000-4-6 || electrical fast transient/burst immunity test 2 kV, 5/100 kHz criteria B output ports conforming to IEC 61000-4-4 || electrical fast transient/burst immunity test 1 kV, 5/100 kHz criteria B input ports conforming to IEC 61000-4-4 || radiated radio-frequency electromagnetic field immunity test 10 V/m, 80 MHz...1 GHz criteria A conforming to IEC 61000-4-3 || radiated radio-frequency electromagnetic field immunity test 3 V/m, 1.4...2 GHz criteria A conforming to IEC 61000-4-3 || radiated radio-frequency electromagnetic field immunity test 1 V/m, 2...2.7 GHz criteria A conforming to IEC 61000-4-3 || surge immunity test 1 kV criteria A output ports line to line conforming to IEC 61000-4-5 || surge immunity test 2 kV criteria B output ports line to earth conforming to IEC 61000-4-5 || radiated emission environment B for DC input supply conforming to IEC 60947-4-3 || conducted emission environment B for DC input supply conforming to IEC 60947-4-3 || immunity to microbreaks and voltage drops 30 %, 500 ms criteria A conforming to IEC 61000-4-11 || immunity to microbreaks and voltage drops 100 %, 20 ms criteria B conforming to IEC 61000-4-11
- Absolute Maximum Voltage
- 1200 V
- Dv/Dt
- 500 V/µs off-state at maximum rated voltage
- Local Signalling
- for control voltage LED (green)
- Maximum Switching Voltage
- 1 V DC turn-off
- Solid State Output Type
- zero voltage switching
- Contact Form
- Form 5 semiconductor output DOL contactor
- Width
- 22.5 mm
- Input Current Limits
- 10-15 mA
- Overvoltage Category
- III
- Inrush Current
- 1350 A at 60 Hz
- Depth
- 116.5 mm
- Rated Duty
- uninterrupted
- Power Factor
- 0.5 with maximum load