Linergy power distribution blocks are for terminating wires and are designed to NEMA standards. This three pole block has one lug opening on the line (main) side and four lug openings on the load (branch) side. The line side lug is rated to accept one #14 to #2 copper or aluminum wire. Each load side lug is rated to accept one #18 to #10 copper or aluminum wire. The lugs are made of aluminum. The lugs are rated for 115 amperes with copper wire and 90 amperes with aluminum wire. The lugs are rated to 600 volts. The housing is made of high impact thermoplastic. These Linergy power distribution blocks are UL component recognized and CSA certified.
Country of Origin
US
Part Number
9080LBA361104
Tariff Code
8536904000
EAN
39121410
UPC
785901097433
UNSPSC
39121410
Metodi di pagamento:
Migliore offerta da:
DEFornitore Automa.Net di fiducia
Disponibilità:
1 pz.
Disponibile
Aggiornato il: 08-11-2024
Garanzia:
12 mesi
Consegna stimata:
Su richiesta
Condizione:
Nuove eccedenze
Nuove eccedenze - Un articolo nuovo, inutilizzato e non danneggiato senza garanzia del produttore. L'articolo può arrivare senza confezione originale o in una confezione sostitutiva. Se fornita, la scatola potrebbe essere stata aperta.
Processo di Pagamento Sicuro
Politiche di Reso e Rimborso
Politiche di Spedizione
Politiche di Garanzia

Environment

Product Certifications
CE || UL recognized E60616 CCN XCFR2 || CSA file 70361 class 6228 01

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Eu Rohs Directive
Compliant

Complementary

[Ics] Rated Service Breaking Capacity
100 kA UL 508 A
Ambient Air Temperature For Operation
-40-257 °F
Height
2.29 in
Mounting Support
surface mount
Electrical Connection
tin plated aluminium lugs
Connections - Terminals
line lug 50 lbf.in AWG 3...AWG 2 copper or aluminium || line lug 45 lbf.in AWG 6...AWG 4 copper or aluminium || line lug 40 lbf.in AWG 8 copper or aluminium || line lug 35 lbf.in AWG 12...AWG 10 copper or aluminium || line lug 35 lbf.in AWG 14 copper || load lug 7 lbf.in AWG 18...AWG 10 copper
Net Weight
.10 kg
Wire Stripping Length
line: 0.5 in || load: 0.38 in for top connection || load: 0.63 in for bottom connection
Number Of Cables
line 1 , AWG 14...AWG 2, copper or aluminium || load 4 , AWG 18...AWG 10, copper or aluminium
Material
thermoplastic: block
Width
2.12 in
Depth
1.62 in
Product Compatibility
9080LB13
Number Of Poles
3
[Ue] Rated Operational Voltage
600 V AC/DC
Number Of Terminals
1 line || 4 load

Specifications

Range Of Product
9080LB
Product Or Component Type
Miniature Power Distribution Block
Short-Circuit Current
65 kA
Line Rated Current
115-115 A copper || 90-90 A aluminium

Documenti