- Non-Overlap Time
- 1.5 ms on energisation between NC and NO contact || 1.5 ms on de-energisation between NC and NO contact
- Minimum Switching Current
- 5 mA
- Mechanical Robustness
- shocks control relay open10 Gn for 11 ms IEC 60068-2-27 || shocks control relay closed15 Gn for 11 ms IEC 60068-2-27 || vibrations control relay open2 Gn, 5...300 Hz IEC 60068-2-6 || vibrations control relay closed4 Gn, 5...300 Hz IEC 60068-2-6
- [Ue] Rated Operational Voltage
- <= 690 V AC 25...400 Hz
- Height
- 77 mm
- [Ith] Conventional Free Air Thermal Current
- 10 A (at 60 °C)
- Control Circuit Voltage Limits
- 0.1...0.25 Uc -40-70 °C drop-out DC || 0.7...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
- Mounting Support
- plate || rail
- Control Circuit Type
- DC low consumption
- [Uc] Control Circuit Voltage
- 24 V DC
- Hold-In Power Consumption In W
- 2.4-2.4 W 20 °C
- Insulation Resistance
- > 10 MOhm
- Irms Rated Making Capacity
- 140 A AC IEC 60947-5-1 || 250 A DC IEC 60947-5-1
- Associated Fuse Rating
- 10 A gG conforming to IEC 60947-5-1
- Net Weight
- 0.58 kg
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947
- Connections - Terminals
- screw clamp terminals 1 1-4 mm²flexible without cable end || screw clamp terminals 2 1-4 mm²flexible without cable end || screw clamp terminals 1 1-4 mm²flexible with cable end || screw clamp terminals 2 1-2.5 mm²flexible with cable end || screw clamp terminals 1 1-4 mm²solid without cable end || screw clamp terminals 2 1-4 mm²solid without cable end
- Pole Contact Composition
- 3 NO + 2 NC
- Time Constant
- 40 ms
- Utilisation Category
- AC-15 || DC-13 || AC-14
- Minimum Switching Voltage
- 17 V
- Maximum Operating Rate
- 180 cyc/mn
- Tightening Torque
- 1.2 N.m screw clamp terminals Philips No 2 || 1.2 N.m screw clamp terminals flat Ø 6 mm || 1.2 N.m screw clamp terminals pozidriv No 2
- Mechanical Durability
- 30 Mcycles
- Inrush Power In W
- 2.4-2.4 W 20 °C)
- Operating Time
- 65...88 ms coil energisation and NO closing || 14...25 ms coil de-energisation and NO opening || 57...77 ms coil energisation and NC opening || 28...42 ms coil de-energisation and NC closing
- Width
- 45 mm
- Depth
- 93 mm
- [Ui] Rated Insulation Voltage
- 600 V UL || 600 V CSA || 690 V IEC 60947-5-1
- [Icw] Rated Short-Time Withstand Current
- 100 A - 1 s || 120 A - 500 ms || 140 A - 100 ms