- Contacts Usage
- standard contacts
- Height
- 42 mm
- Terminals Description Iso N°1
- (13-14)NO || (21-22)NC
- Operating Force
- 3.5 N NC changing electrical state || 3.8 N
- Short-Circuit Protection
- 10 A cartridge fuse gG IEC 60947-5-1
- Operating Travel
- 1.5 mm NC changing electrical state) || 2.6 mm NO changing electrical state) || 4.3 mm total travel)
- Contacts Material
- silver alloy (Ag/Ni)
- Positive Opening
- with IEC 60947-5-1 appendix K
- [Ith] Conventional Free Air Thermal Current
- 10 A IEC 60947-5-1
- Net Weight
- 0.056 kg
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947-1
- Current Consumption
- 14 mA
- Device Presentation
- complete product
- Resistance To High Pressure Washer
- 7000000 Pa 55 °C 0.1 m
- Electrical Durability
- 1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C || 1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C || 1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C
- Service Life
- 100000 h at rated voltage and 25 °C
- Surge Withstand
- 1 kV IEC 61000-4-5
- [Ui] Rated Insulation Voltage
- 600 V 3)IEC 60947-1
- Signalling Type
- steady
- [Ie] Rated Operational Current
- 3 A 240 V, AC-15, A600 IEC 60947-5-1 || 6 A 120 V, AC-15, A600 IEC 60947-5-1 || 0.1 A 600 V, DC-13, Q600 IEC 60947-5-1 || 0.27 A 250 V, DC-13, Q600 IEC 60947-5-1 || 0.55 A 125 V, DC-13, Q600 IEC 60947-5-1 || 1.2 A 600 V, AC-15, A600 IEC 60947-5-1
- Supply Voltage Limits
- 100-132 V AC
- Mechanical Durability
- 10000000 cycles
- Electrical Reliability
- λ < 10exp(-6) 5 V, 1 mA in clean environment IEC 60947-5-4 || λ < 10exp(-8) 17 V, 5 mA in clean environment IEC 60947-5-4
- Width
- 30 mm
- Depth
- 57 mm
- Tightening Torque
- 0.8-1.2 N.m IEC 60947-1
- Shape Of Screw Head
- cross Philips no 1 || cross pozidriv No 1 || slotted flat Ø 4 mm || slotted flat Ø 5.5 mm