Wago
2000-5357/101-000
1 / 3
- Part Number
- 2000-5357/101-000
- Tariff Code
- 85369010000
- UPC
- 4055143497107
- ETIM
- Group Code : EG000012
- Group Description : Terminal blocks
- Class Description : Sensor/actuator terminal block
- Class Code : EC000900
- Version : 7
- Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
- Sconti sulla rivendita fino al 40%!
Invia una richiesta di prezzo
1
Metodi di pagamento:
Ratings Per Iec/En
- Ratings per
- IEC/EN 60947-7-1
- Nominal voltage (III/3)
- 250 V
- Rated current
- 28 A
- Legend (ratings)
- (III / 3) ≙ Overvoltage category III / Pollution degree 3
Environmental Requirements
- Processing temperature
- -35 … +85 °C
- Continuous operating temperature
- -60 … +105 °C
Physical Data
- Width
- 7 mm / 0.276 inches
- Height
- 81.1 mm / 3.193 inches
- Depth from upper-edge of DIN-rail
- 52.4 mm / 2.063 inches
Material Data
- Note (material data)
- <a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
- Color
- Orange
- Material group
- I
- Insulation material
- Polyamide (PA66)
- Flammability class per UL94
- V0
- Fire load
- 0.314 MJ
- Weight
- 17.832 g
Mechanical Data
- Mounting type
- DIN-35 rail
- Marking level
- Center/side marking
Connection 2
- Solid conductor 2
- 0.25 … 4 mm² / 22 … 12 AWG
- Solid conductor; push-in termination 2
- 0.25 … 4 mm² / 22 … 12 AWG
- Fine-stranded conductor 2
- 0.25 … 4 mm² / 22 … 12 AWG
Specifications
- Product Group Code
- 0022
Commercial Data
- Packaging type
- Box
- Country of origin
- DE
- GTIN
- 4055143497107
- Customs tariff number
- 85369010000
Ratings Per Csa
- Approvals per
- CSA 22.2 No 158
- Rated voltage CSA (Use Group C)
- 300 V
- Rated current CSA (Use Group C)
- 20 A
Power Loss
- Power loss, per pole (potential)
- 1.0427 W
- Rated current IN for specified power loss
- 28 A
- Resistance value for specified, current-dependent power loss
- 0.00133 Ω
Connection 1
- Connection technology
- Push-in CAGE CLAMP®
- Actuation type
- Operating tool
- Connectable conductor materials
- Copper
- Nominal cross-section
- 1 mm²
- Solid conductor
- 0.14 … 1.5 mm² / 24 … 16 AWG
- Solid conductor; push-in termination
- 0.5 … 1.5 mm² / 20 … 16 AWG
- Fine-stranded conductor
- 0.14 … 1.5 mm² / 24 … 16 AWG
- Fine-stranded conductor; with insulated ferrule
- 0.14 … 0.75 mm² / 24 … 18 AWG
- Fine-stranded conductor; with ferrule; push-in termination
- 0.5 … 0.75 mm² / 20 … 18 AWG
- Note (conductor cross-section)
- Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
- Strip length
- 9 … 11 mm / 0.35 … 0.43 inches
- Wiring direction
- Front-entry wiring
Ratings Per Ul 1059
- Approvals per
- UL 1059
- Rated voltage UL (Use Group B)
- 300 V
- Rated current UL (Use Group B)
- 20 A
- Rated voltage UL (Use Group D)
- 300 V
- Rated current UL (Use Group D)
- 20 A