- Mounting Mode
- clip-on 35 mm symmetrical DIN rail) || by screws plate)
- Network Frequency
- 50/60 Hz
- [Ics] Rated Service Breaking Capacity
- 25 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 14 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 18 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 18 kA 440 V AC 50/60 Hz IEC 60947-2
- Trip Unit Technology
- thermal-magneticTM-D,
- Trip Unit Name
- TM-D
- Height
- 137 mm
- Connection Pitch
- 27 mm
- [Ue] Rated Operational Voltage
- 525 V AC 50/60 Hz UL 489
- Tightening Torque
- 5-5 N.m 2.5-16 mm² (AWG 14...AWG 4) || 9-9 N.m 25-95 mm² (AWG 3...AWG 3/0)
- Breaking Capacity Code
- D
- 9 Mm Pitches
- 9
- Local Signalling
- presence of auxiliary contacts flag green)
- Number Of Slots
- 1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in) || 1 alarm switch SD plug-in)
- Protected Poles Description
- 3t
- Electrical Connection
- terminal nut, ON and OFF end
- Net Weight
- 0.924 kg
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947-2
- Control Type
- toggle
- Circuit Breaker Application
- HACR rated
- Wire Stripping Length
- 20 mm
- Utilisation Category
- category A
- Line Rated Current
- 60-60 A
- Continuous Current Rating
- 80 %
- Breaking Capacity
- 25 kA 208Y/120 V AC 50/60 Hz UL 489 || 18 kA 240 V AC 50/60 Hz UL 489 || Icu 25 kA 480/277 V AC 50/60 Hz UL 489 || Icu 14 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600Y/347 V AC 50/60 Hz UL 489 || 14 kA 250 V DC UL 489 || 25 kA || Icu 18 kA
- [Ui] Rated Insulation Voltage
- 800 V IEC 60947-2
- Mechanical Durability
- 15000 cycles IEC 947-1 Annex K ed 5.2
- Suitability For Isolation
- yes IEC 60947-2
- Electrical Durability
- 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
- Poles Description
- 3P
- Quantity Per Set
- set of 1
- Awg Gauge
- AWG 14...AWG 8 aluminium/copper || AWG 6...AWG 3/0 aluminium/copper
- Color
- Gray RAL 7016)
- Width
- 81 mm
- Depth
- 80 mm