- Rated Operational Current AC-21A (Ie)
- (380 ... 415 V) 200 A(500 V) 200 A(690 V) 200 A(1000 V) 200 A
- Rated Operational Current AC-22A (Ie)
- (380 ... 415 V) 200 A(500 V) 200 A(690 V) 200 A
- Rated Operational Current AC-23A (Ie)
- (380 ... 415 V) 200 A(500 V) 200 A(690 V) 200 A
- Rated Operational Power AC-23A (Pe)
- (220 ... 240 V) 60 kW(400 ... 415 V) 110 kW(500 V) 132 kW(690 V) 200 kW
- Conventional Free-air Thermal Current (Ith)
- Θ = 40 °C 200 A
- Conventional Thermal Current (Ithe)
- Fully Enclosed 200 A
- Rated Impulse Withstand Voltage (Uimp)
- 12 kV
- Rated Insulation Voltage (Ui)
- acc. to IEC/EN 60664-1 1000 V
- Rated Operational Voltage
- Main Circuit 1000 V
- Rated Short-Circuit Making Capacity (Icm)
- (690 V) 30 kA
- Rated Short-time Withstand Current Low Voltage (Icw)
- for 1 s 8 kA
- Rated Conditional Short-Circuit Current (Inc)
- (315 A fuse, 500 V) 100 kA(355 A fuse, 690 V) 80 kA(250 A fuse, 690 V) 100 kA
- Power Loss
- at Rated Operating Conditions per Pole 4.0 W
- Pollution Degree
- 3
- Handle Color
- Black
- Handle Type
- Handle and shaft included
- Fourth Pole Position
- Right Side
- Fourth Pole Type
- Switched - Simultaneous Function
- Switches Operating Mechanism
- Mechanism Between the Poles22 (Between the Poles)
- Distance Between Phases
- Standard
- Position of Line Terminals
- Top In - Bottom OutBottom In - Top Out
- Operating Mode
- Front operated
- Standards
- IEC 60947-3
- Special Functions
- No
- Mounting Type
- Base mounting
- Number of Poles
- 4
- Degree of Protection
- Front IP00
- Terminal Type
- Lug terminals
- Terminal Width
- 20 mm
- Tightening Torque
- acc. IEC 60947-1 15 … 22 N·m
- Mechanical Durability
- 20000
- Lock Type
- Yes