- Standards
- IEC/EN 60898-1IEC/EN 60947-2UL 1077
- Tripping Characteristic
- B
- Rated Operational Voltage
- acc. to IEC 60898-1 400 V ACacc. to IEC 60947-2 440 V AC
- Operational Voltage
- Maximum (Incl. Tolerance) 440 V ACMinimum 12 V ACMinimum 12 V DC
- Rated Insulation Voltage (Ui)
- acc. to IEC/EN 60664-1 440 V
- Rated Impulse Withstand Voltage (Uimp)
- 4 kVat 2000 m 5 kVat Sea Level 6.2 kV
- Dielectric Test Voltage
- 50/60 Hz, 1 min: 2 kV
- Input Voltage Type
- AC/DC
- Rated Current (In)
- 20 A
- Rated Short-Circuit Capacity
- (AC) 6 kA(DC) 6 kA(400 V AC) 6 kA
- Rated Ultimate Short-Circuit Breaking Capacity (Icu)
- (230 V AC) 20 kA(400 V AC) 10 kA(440 V AC) 10 kA
- Rated Conditional Short-Circuit Current (Inc)
- (230 V) 20 kA(400 V) 20 kA
- Rated Service Short-Circuit Breaking Capacity (Ics)
- (230 V AC) 15 kA(400 V AC) 7.5 kA(440 V AC) 7.5 kA
- Frequency (f)
- 50 Hz
- Rated Frequency (f)
- 50 / 60 Hz
- Power Loss
- 10 Wat Rated Operating Conditions per Pole 2.5 W
- Power Supply Connection
- Arbitrary
- Contact Position Indication
- Red ON / Green OFF
- Energy Limiting Class
- 3
- Electrical Endurance
- 20000 AC cycle
- Mechanical Endurance
- 20000 cycle
- Number of Poles
- 4
- Number of Protected Poles
- 4
- Overvoltage Category
- III
- Tightening Torque
- 2.8 N·m
- Mounting Type
- DIN-Rail
- Screw Terminal Type
- Failsafe Bi-directional Cylinder-lift Terminal
- Actuator Marking
- I / O
- Actuator Material
- Insulation Group II, Black, Sealable
- Housing Material
- Insulation Group II, RAL 7035
- Mounting on DIN Rail
- TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
- Mounting Position
- any
- Recommended Screw Driver
- Pozidriv 2
- Accessories Available
- Yes
- Connecting Capacity
- Busbar 10 / 10 mm²Flexible with Ferrule 0.75 ... 25 mm²Flexible 0.75 ... 25 mm²Rigid 0.75 ... 35 mm²Stranded 0.75 ... 35 mm²
- Installation Size
- acc. to DIN 43880 1
- Wire Stripping Length
- 12.5 mm
- Terminal Type
- Screw Terminals