Soft starter, Altistart 480, 480A, 208 to 690V AC, control supply 110 to 230V AC
ATS480C48Y
ATS480C48Y
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
$4,676.73
1
Formas de pago:
Un total de 23 Parts In-Stock de 20 Distributors

Additional Information

Part Number
ATS480C48Y
Tariff Code
8504404000

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2102013EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Circularity Profile
ENVEOLI2102013EN
Upgradeability
Upgraded components available
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Environment

Maximum Acceleration Under Vibratory Load (During Transport)
15 m/s² at 200...500 Hz || 10 m/s² at 9...200 Hz
Maximum Acceleration Under Shock Load (During Transport)
100 m/s² at 11 ms
Maximum Deflection Under Vibratory Load (During Operation)
1.5 mm at 2...13 Hz
Maximum Acceleration Under Shock Impact (During Operation)
150 m/s² at 11 ms
[Uimp] Rated Impulse Withstand Voltage
6 kV
Pollution Degree
level 3
Electromagnetic Compatibility
conducted and radiated emissions level A IEC 60947-4-2 || conducted and radiated emissions with bypass level B IEC 60947-4-2 || damped oscillating waves level 3 IEC 61000-4-12 || electrostatic discharge level 3 IEC 61000-4-11 || immunity to electrical transients level 4 IEC 61000-4-4 || immunity to radiated radio-electrical interference level 3 IEC 61000-4-3 || voltage/current impulse level 3 IEC 61000-4-5
Ambient Air Temperature For Operation
40-60 °C with current derating of 2 % per °C) || -15-40 °C without derating)
Maximum Deflection Under Vibratory Load (During Transport)
1.75 mm at 2...9 Hz
[Ui] Rated Insulation Voltage
690 V
Maximum Acceleration Under Vibrational Stress (During Operation)
10 m/s² at 13...200 Hz
Maximum Acceleration Under Vibratory Load (During Storage)
15 m/s² at 200...500 Hz || 10 m/s² at 9...200 Hz
Ambient Air Temperature For Storage
-25-70 °C
Relative Humidity
0-95 % without condensation or dripping water IEC 60068-2-3
Operating Altitude
<= 3280.84 ft (1000 m) without derating || > 3280.84...13123.36 ft (> 1000...4000 m) with current derating 1 % per 100 m
Maximum Acceleration Under Shock Load (During Storage)
100 m/s² at 11 ms
Environmental Class (During Operation)
class 3C3 according to IEC 60721-3-3 || class 3S2 according to IEC 60721-3-3
Maximum Deflection Under Vibratory Load (During Storage)
1.75 mm at 2...9 Hz

Specifications

Product Destination
asynchronous motors
Range Of Product
Altivar Soft Starter ATS480
Product Or Component Type
soft starter
Maximum Permanent Current
410.0 A at 40 °C heavy duty
Motor Power Kw
132.0 kW 230 V in the motor supply line normal duty || 110.0 kW 230 V in the motor supply line heavy duty || 250.0 kW 400 V in the motor supply line normal duty || 220.0 kW 400 V in the motor supply line heavy duty || 250.0 kW 440 V in the motor supply line normal duty || 220.0 kW 440 V in the motor supply line heavy duty || 315.0 kW 500 V in the motor supply line normal duty || 250.0 kW 500 V in the motor supply line heavy duty || 315.0 kW 525 V in the motor supply line normal duty || 250.0 kW 525 V in the motor supply line heavy duty || 400.0 kW 660 V in the motor supply line normal duty || 355.0 kW 660 V in the motor supply line heavy duty || 500.0 kW 690 V in the motor supply line normal duty || 400.0 kW 690 V in the motor supply line heavy duty || 250.0 kW 230 V to the motor delta terminals normal duty || 220.0 kW 230 V to the motor delta terminals heavy duty || 355.0 kW 400 V to the motor delta terminals normal duty || 315.0 kW 400 V to the motor delta terminals heavy duty
Phase
3 phase
Utilisation Category
AC-3A || AC-53A
[Ie] Rated Operational Current
normal duty 480.0 A 40 °C)
[Us] Rated Supply Voltage
208...690 V - 15...10 %
Product Specific Application
process and infrastructures
Torque Control
true
Maximum Horse Power Rating
150.0 hp 208 V normal duty || 125.0 hp 208 V heavy duty || 150.0 hp 230 V heavy duty || 350.0 hp 460 V normal duty || 300.0 hp 460 V heavy duty || 400.0 hp 575 V normal duty || 350.0 hp 575 V heavy duty
Device Short Name
ATS480
Ip Degree Of Protection
IP00
Supply Frequency
50...60 Hz - 20...20 %
Option Card
communication module Profibus DP V1 || communication module PROFINET || communication module Modbus TCP/EtherNet/IP || communication module CANopen daisy chain || communication module CANopen Sub-D || communication module CANopen open style

Complementary

Product Certifications
CE || cULus || CCC || UKCA || RCM || EAC || DNV || ABS || BV || CCS
Device Connection
in the motor supply line || to the motor delta terminals
Height
670.0 mm
Standards
IEC 60947-4-2 || UL 60947-4-2 || IEC 60664-1
Transmission Frame
RTU
Analogue Output Type
current output AQ1 0...20 mA or 0...10 V 500 Ohm
[Uc] Control Circuit Voltage
110...250 V AC 50/60 Hz - 15...10 %
Maximum Switching Current
relay outputs 2 A 250 V AC || relay outputs 2 A 30 V DC || relay outputs
Relay Output Number
3
Data Format
8 bits, configurable odd, even or no parity
Marking
CE || CCC || UKCA || EAC || RCM || cULus
Output Current Drift
150-700 %
Display Screen Available
true
Net Weight
51.4 kg
Relay Output Type
relay outputs R1A 1 NO || relay outputs R1B 1 NO || relay outputs RIC NO/NC programmable
Connector Type
1 RJ45
Analogue Input Number
1
Communication Data Link
serial
Function Available
external bypass control || pre-heating || smoke extraction || multi-motor cascade || second motor set || user management || ports and services hardening || security event logging || cybersecure firmware update || single direction
Discrete Output Number
2
Communication Port Protocol
Modbus serial
Discrete Input Type
STOP) logic inputs, 3500 Ohm || RUN) logic inputs, 3500 Ohm || DI3) programmable as logic input, 3500 Ohm || DI4) programmable as logic input, 3500 Ohm
Minimum Switching Current
100 mA 12 V DC relay outputs
Analogue Output Number
1
Physical Interface
2-wire RS 485
Method Of Access
slave Modbus serial
Integrated Motor Overload Protection
true
[In] Rated Current Pwr Loss Specifctn
480.0 A
Discrete Input Number
4
Accuracy Class
class 10E
Power Loss Per Device Current Dependent
1366.0 W
Number Of Addresses
0-227 Modbus serial
Apparent Power
0.125 kVA
Operating Position
vertical +/- 10 degree
Power Loss Static Current Independent
25.0 W
Type Of Polarization
no impedance Modbus serial
Width
400.0 mm
Transmission Rate
1200...256000 bit/s
Depth
314.0 mm
Discrete Input Logic
programmable digital input < 5 V
Protection Type
phase failure line || integrated thermal protection motor || thermal protection starter || current overload motor || underload motor || excessive starting time, locked rotor motor || motor phase loss motor || line supply phase loss line || line supply phase loss motor || thermal protection motor
Discrete Output Type
DQ1) programmable digital output <= 30 V || DQ2) programmable digital output <= 30 V

Documentos

Data Sheet

Descargar

Modelos CAD

Rastrear piezas
Rastrear piezas
Descargar

Productos relacionados