Activo maduro
LR9D01 is a TeSys LR9D electronic overload relay from Schneider Electric to be used with a TeSys D contactor. With a thermal range 0.1-0.5A, selectable tripping class 5-10-20-30 and phase unbalance protection, it protects motors 0.06 to 0.18kW@400V. LR9D01 is a TeSys LR9D electronic overload relay from Schneider Electric for direct mounting on TeSys D contactors. With a large thermal setting range 0.1-0.5A, a selectable tripping class 5-10-20-30 and phase unbalance detection, it protects motors 0.06 to 0.18kW@400V. It provides manual test & reset buttons, automatic reset, trip auxiliary contact and flag indicator. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Thermal overload protection, electronic type, with phase unbalance protection (differential), self powered (no external power supply needed). Direct mounting on the bottom terminals of a Tesys LC1D09-D38 to form a compact starter contactor to form a compact starter. Light and compact, 45mm wide. Manual control with test & reset buttons, manual / automatic reset selector. High accuracy, temperature compensated to keep a precise tripping over the ambient temperature range. Wide protection adjustment range 1.6-8A and selectable tripping class 5-10-20 -30. Trip signaling with 1NO+1NC auxiliary contacts and trip flag indicator. 90% reduction in energy dissipation compared to a thermal overload relay. Can be completed with terminal blocks and separate mounting accessories (LAD7B).
Country of Origin
CN
Part Number
LR9D01
Tariff Code
85364900
EAN
3606485420929
UNSPSC
39122330
Métodos de pago:
Mejor oferta de:
GBProveedor de confianza de Automa.Net
Disponibilidad:
1 pieza
En stock
Actualizado en: 21-10-2024
Entrega Estimada:
Bajo pedido
Condición:
Nuevos excedentes
Nuevos excedentes - Un artículo nuevo, sin usar, sin daños y sin garantía del fabricante. El artículo puede venir sin embalaje original o en embalaje de reemplazo. Si se proporciona, es posible que la caja haya sido abierta.
Proceso de Pago Seguro
Políticas de Devolución y Reembolso
Políticas de Envío
Políticas de Garantía

Specifications

Thermal Protection Adjustment Range
0.1-0.5 A
Power Consumption In W
300 mW
Relay Application
motor protection
Product Or Component Type
electronic thermal overload relay
Product Name
TeSys LRD
Thermal Overload Class
class 5…30
Range
TeSys
Mounting Support
under contactor || plate, with specific accessories || rail, with specific accessories
Product Compatibility
LC1D09 || LC1D25 || LC1D32 || LC1D12 || LC1D38 || LC1D18
Device Short Name
LR9D

Complementary

Time Range
1.5...4 min - automatic reset time
Height
72.5 mm
[Ith] Conventional Free Air Thermal Current
5 A signalling circuit
Tightening Torque
control circuit 0.8 N.m screw clamp terminals || power circuit 3.1 N.m screw clamp terminals
Phase Failure Sensitivity
phase difference > 40% 3-3 s IEC 60947-4-1
[Ue] Rated Operational Voltage
690 V power circuit || 660 V signalling circuit
Electromagnetic Compatibility
surge withstand 2 kV common mode IEC 61000-4-5 || resistance to electrostatic discharge 8 kV IEC 61000-4-2 || immunity to radiated radio-electrical interference 10 V/m IEC 61000-4-3 || immunity to fast transients 2 kV IEC 61000-4-4
Associated Fuse Rating
5 A gG signalling circuit || 5 A BS signalling circuit
Net Weight
0.18 kg
[Uimp] Rated Impulse Withstand Voltage
6 kV
Connections - Terminals
control circuit screw clamp terminals 1 2.5-2.5 mm² solid or flexible - without cable end || power circuit screw clamp terminals 1 16-16 mm² solid or flexible - without cable end
[Ui] Rated Insulation Voltage
power circuit 1000 V || signalling circuit 690 V
Tripping Threshold
1.25 In IEC 60947-4-1
Control Type
Red push-button stop and manual reset || White 2 microswitches adjustable trip class || Red knob automatic reset || White dial full-load current adjustment
Width
45 mm
Depth
79.9 mm

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1502001EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1502001EN
Eu Rohs Directive
Compliant

Environment

Product Certifications
IECEE CB Scheme || UL || CSA || CCC
Mechanical Robustness
vibrations 10...150 Hz6 Gn IEC 60068-2-6 || shocks 11 ms15 gn IEC 60068-2-7
Standards
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4 || GB/T 14048.5
Ambient Air Temperature For Operation
-25-70 °C IEC 60255-8
Dielectric Strength
6 kV 50 Hz IEC 60255-5
Ambient Air Temperature For Storage
-55-80 °C
Ip Degree Of Protection
IP20 front face IEC 60529
Operating Altitude
6561.68 ft (2000 m) without derating